IV. WIRING

Wiring for synchronized strobes and horns.

Using this method you may:

w

  Use only two wires to synchronize the temporal horn and strobe with the ability to mute the horn (place 

 switches 

1

 and 

2

 in the ON position on the GEC3-12).

w

  Mute the horn 

only

 when the temporal horn option has been selected.

w

  Use the Gentex synchronization protocol to provide synchronization and mute the horn, if available.

Wiring for synchronized parallel (unison) horn/strobe operation.

Using this method you may:

w

  Use four wires where two wires are used to power and synchronize the strobe and two additional wires are 

 

used to power and synchronize the horn (place switches 

1

 and 

2

 in the OFF position on the GEC3-12).

w

  Choose either continuous horn and allow the FACP to control the horn or choose temporal horn and 

 

synchronize the horns with the Gentex synchronization protocol. 

w

  Use the Gentex synchronization protocol to provide synchronization and mute the horn, if available.  

NOTICE: 

FOR THIS OPTION, SWITCHES 

1

 AND 

2

 ON THE GEC3-12 MUST BE IN THE OFF POSITION TO ISOLATE POWER TO THE AUDIBLE AND VISIBLE PORTION OF THE 

 CIRCUIT.

ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE.  THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR 

 

PULSING SIGNALING CIRCUITS. HOWEVER, USE OF THE AVSM CONTROL MODULE IS  PERMITTED TO SYNCHRONIZE THE STROBE AND/OR MUTE THE HORN.

SEE AVSM CONTROL MODULE MANUAL (550-0284, MANUAL ISSUE DATE 2-1-03) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS.  AVSM MANUAL CAN 

 

BE OBTAINED AT HTTP://WWW.GENTEX.COM/FIRE/PRODUCTS OR CALL GENTEX CORPORATION AT 1-800-436-8391.

Conventional Method:

You may connect both the strobe and the horn directly from a source of rated power without the use of a control module.  However, the horns and strobe lights will NOT 

be synchronized.  Place switches 

1

 and 

2

 in the ON position on the GEC3-12 to power both the audible and visible from a single pair of power wires. If you wish to power 

the horn and strobe from independent sources of power, place switches 

1

 and 

2

 in the OFF position on the GEC3-12 and connect power to the appropriate terminals.

12VDC CLEAR Lens Strobe Current Ratings

Use with GEC3-12 and GES3-12 Products

Candela

Regulated 12VDC  

Max. Operating 

Current (mA)

Regulated 12VFWR 

Max. Operating 

Current (mA)

1

15

92 mA

145 mA

30

141 mA

224 mA

60

260 mA

459 mA

75

312 mA

460 mA

Horn Decibel Levels

Horn Current Ratings Over 

Input Voltage Range of 8-17.5V

Horn Mode

Minimum SPL 

at 10Ft. Per 

ANSI/UL 464 (HIGH)

Minimum SPL 

at 10Ft. Per 

ANSI/UL 464 (LOW)

Regulated 12VDC Max. 

Operating Current (mA)  

HIGH Setting

Regulated 12VFWR Max. 

Operating Current (mA)

HIGH Setting

Temp 3 2400Hz

76 dBA

69* dBA

29 mA

48 mA

Temp 3 Mechanical

75 dBA

68* dBA

26 mA

45 mA

Temp 3 Chime

62* dBA

60* dBA

13 mA

24 mA

Continuous 2400Hz

79 dBA

74* dBA

29 mA

48 mA

Continuous Mechanical

78 dBA

72* dBA

26 mA

45 mA

Continuous Chime

63* dBA

61* dBA

13 mA

24 mA

Whoop

78 dBA

71* dBA

55 mA

61 mA

NOTICE:

w

  THE THREE PULSE TEMPORAL PATTERN IS TO BE USED FOR EVACUATION USE ONLY.

w

  THE SOUND OUTPUT FOR THE TEMPORAL 3 TONE IS RATED LOWER SINCE THE TIME THE HORN IS OFF IS AVERAGED INTO THE SOUND 

 

OUT PUT RATING.  WHILE THE HORN IS PRODUCING A TONE IN THE TEMPORAL 3 MODE ITS SOUND PRESSURE IS THE SAME AS THE 

 

CONTINUOUS MODE.  UNITS HAVE BEEN TESTED TO 0°C, 49°C AND 93% HUMIDITY.   

*   Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 sound level required for public mode 

 

fire protection service.  These settings are acceptable only for private mode fire alarm signaling use.  Use the high dBA setting for public 

 

mode applications (the chime tone is always private mode).

MAX. WIRE

DISTANCE

(IN FEET)

(PANEL VOLTAGE/

APPLIANCE MIN. VOLT) 

`

TOTAL CURRENT DRAW

=

[

[

WIRE

CONDUCTIVITY

18 AWG
16 AWG
14 AWG

12 AWG

60
95

153

244

Includes wire to and from appliance. 

 CAUTION: 

Applies only to regulated supplies.

Assumes all appliances are at the end of wire run (worse case).

X

WIRE CONDUCTIVITY

550-0636

Page 2

NOTICE: 

DC VOLTAGE RANGE LIMITS: 8-17.5V.  THIS PRODUCT WAS ONLY 

TESTED TO THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND 

110% OF THIS RANGE FOR SYSTEM OPERATION.
1 When using products manufactured after 7-1-10, these values are to be 

used when calculating current draws.

+

-

First Signal

S+ S+

H+ H-

S-

Last Signal

S+ S+

H+ H-

S-

E

O

L

R

UL Listed

Control Panel

Supervised

Signal Circuit

+

-

+

-

First Signal

S+ S+

H+ H-

S-

Last Signal

S+ S+

H+ H-

S-

E

O

L

R

UL Listed

Control Panel

Supervised

Signal Circuit

E

O

L

R

CAUTION:

 When using only a single power source to 

energize the strobe and horn (switches 1 and 2 in the ON 

position), the in/out wiring must be under the S+ and S- 

terminals only.  Failure to do so may result in damage to 

your signal.  For the horn only (GEH12) and strobe only 

(GES3-12), only the top three terminals are to be used.  

HORN DECIBEL AND CURRENT RATINGS PRODUCT INFORMATION

Содержание GEC3-12 Series

Страница 1: ...tic tab NOTICE WIRING SHOULD BE CONNECTED TO MOUNTING BRACKET PRIOR TO MOUNTING SIGNAL INCOMING POSITIVE POWER LEAD MUST BE BROKEN AND EACH LEAD IS TO BE INSERTED INTO EACH OF THE TOP TWO TERMINALS IF TWO POWER RUNS ARE MADE TO THE SIGNAL ONE FOR THE STROBE AND ONE FOR THE HORN ONLY ONE OF THE RUNS MUST HAVE ITS POSITIVE LEAD BROKEN AND PLACED UNDER THE TWO SEPARATE TOP TERMINALS A BARRIER IS PROV...

Страница 2: ...A 30 141 mA 224 mA 60 260 mA 459 mA 75 312 mA 460 mA Horn Decibel Levels Horn Current Ratings Over Input Voltage Range of 8 17 5V Horn Mode Minimum SPL at 10Ft Per ANSI UL 464 HIGH Minimum SPL at 10Ft Per ANSI UL 464 LOW Regulated 12VDC Max Operating Current mA HIGH Setting Regulated 12VFWR Max Operating Current mA HIGH Setting Temp 3 2400Hz 76 dBA 69 dBA 29 mA 48 mA Temp 3 Mechanical 75 dBA 68 dB...

Страница 3: ...zel and pull in a downward and outward motion Candela selection slider switch Depress center and slide switch to desired brightness level Break off pin and insert into hole at the bottom of the selector to lock candela setting Signal must be removed from bracket and pin pushed forward from backside out of hole to change candela SWITCH POSITION TONE 3 4 5 Mechanical Temporal 3 ON ON ON Mechanical C...

Страница 4: ...rom defects in workmanship and materials under normal use and service This warranty does not apply and is void if damage or failure is caused by accident abuse misuse abnormal use faulty installation liquid contact fire earthquake or other external cause operating the appliance outside Gentex s published guidelines or service alteration maintenance or repairs performed by anyone other than Gentex ...

Отзывы: