IV. WIRING
Wiring for synchronized strobes and horns.
Using this method you may:
w
Use only two wires to synchronize the temporal horn and strobe with the ability to mute the horn (place
switches
1
and
2
in the ON position on the GEC3-12).
w
Mute the horn
only
when the temporal horn option has been selected.
w
Use the Gentex synchronization protocol to provide synchronization and mute the horn, if available.
Wiring for synchronized parallel (unison) horn/strobe operation.
Using this method you may:
w
Use four wires where two wires are used to power and synchronize the strobe and two additional wires are
used to power and synchronize the horn (place switches
1
and
2
in the OFF position on the GEC3-12).
w
Choose either continuous horn and allow the FACP to control the horn or choose temporal horn and
synchronize the horns with the Gentex synchronization protocol.
w
Use the Gentex synchronization protocol to provide synchronization and mute the horn, if available.
NOTICE:
w
FOR THIS OPTION, SWITCHES
1
AND
2
ON THE GEC3-12 MUST BE IN THE OFF POSITION TO ISOLATE POWER TO THE AUDIBLE AND VISIBLE PORTION OF THE
CIRCUIT.
w
ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE. THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR
PULSING SIGNALING CIRCUITS. HOWEVER, USE OF THE AVSM CONTROL MODULE IS PERMITTED TO SYNCHRONIZE THE STROBE AND/OR MUTE THE HORN.
w
SEE AVSM CONTROL MODULE MANUAL (550-0284, MANUAL ISSUE DATE 2-1-03) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM MANUAL CAN
BE OBTAINED AT HTTP://WWW.GENTEX.COM/FIRE/PRODUCTS OR CALL GENTEX CORPORATION AT 1-800-436-8391.
Conventional Method:
You may connect both the strobe and the horn directly from a source of rated power without the use of a control module. However, the horns and strobe lights will NOT
be synchronized. Place switches
1
and
2
in the ON position on the GEC3-12 to power both the audible and visible from a single pair of power wires. If you wish to power
the horn and strobe from independent sources of power, place switches
1
and
2
in the OFF position on the GEC3-12 and connect power to the appropriate terminals.
12VDC CLEAR Lens Strobe Current Ratings
Use with GEC3-12 and GES3-12 Products
Candela
Regulated 12VDC
Max. Operating
Current (mA)
Regulated 12VFWR
Max. Operating
Current (mA)
1
15
92 mA
145 mA
30
141 mA
224 mA
60
260 mA
459 mA
75
312 mA
460 mA
Horn Decibel Levels
Horn Current Ratings Over
Input Voltage Range of 8-17.5V
Horn Mode
Minimum SPL
at 10Ft. Per
ANSI/UL 464 (HIGH)
Minimum SPL
at 10Ft. Per
ANSI/UL 464 (LOW)
Regulated 12VDC Max.
Operating Current (mA)
HIGH Setting
Regulated 12VFWR Max.
Operating Current (mA)
HIGH Setting
Temp 3 2400Hz
76 dBA
69* dBA
29 mA
48 mA
Temp 3 Mechanical
75 dBA
68* dBA
26 mA
45 mA
Temp 3 Chime
62* dBA
60* dBA
13 mA
24 mA
Continuous 2400Hz
79 dBA
74* dBA
29 mA
48 mA
Continuous Mechanical
78 dBA
72* dBA
26 mA
45 mA
Continuous Chime
63* dBA
61* dBA
13 mA
24 mA
Whoop
78 dBA
71* dBA
55 mA
61 mA
NOTICE:
w
THE THREE PULSE TEMPORAL PATTERN IS TO BE USED FOR EVACUATION USE ONLY.
w
THE SOUND OUTPUT FOR THE TEMPORAL 3 TONE IS RATED LOWER SINCE THE TIME THE HORN IS OFF IS AVERAGED INTO THE SOUND
OUT PUT RATING. WHILE THE HORN IS PRODUCING A TONE IN THE TEMPORAL 3 MODE ITS SOUND PRESSURE IS THE SAME AS THE
CONTINUOUS MODE. UNITS HAVE BEEN TESTED TO 0°C, 49°C AND 93% HUMIDITY.
* Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 sound level required for public mode
fire protection service. These settings are acceptable only for private mode fire alarm signaling use. Use the high dBA setting for public
mode applications (the chime tone is always private mode).
MAX. WIRE
DISTANCE
(IN FEET)
(PANEL VOLTAGE/
APPLIANCE MIN. VOLT)
`
TOTAL CURRENT DRAW
=
[
[
WIRE
CONDUCTIVITY
18 AWG
16 AWG
14 AWG
12 AWG
60
95
153
244
Includes wire to and from appliance.
CAUTION:
Applies only to regulated supplies.
Assumes all appliances are at the end of wire run (worse case).
X
WIRE CONDUCTIVITY
550-0636
Page 2
NOTICE:
DC VOLTAGE RANGE LIMITS: 8-17.5V. THIS PRODUCT WAS ONLY
TESTED TO THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND
110% OF THIS RANGE FOR SYSTEM OPERATION.
1 When using products manufactured after 7-1-10, these values are to be
used when calculating current draws.
+
-
First Signal
S+ S+
H+ H-
S-
Last Signal
S+ S+
H+ H-
S-
E
O
L
R
UL Listed
Control Panel
Supervised
Signal Circuit
+
-
+
-
First Signal
S+ S+
H+ H-
S-
Last Signal
S+ S+
H+ H-
S-
E
O
L
R
UL Listed
Control Panel
Supervised
Signal Circuit
E
O
L
R
CAUTION:
When using only a single power source to
energize the strobe and horn (switches 1 and 2 in the ON
position), the in/out wiring must be under the S+ and S-
terminals only. Failure to do so may result in damage to
your signal. For the horn only (GEH12) and strobe only
(GES3-12), only the top three terminals are to be used.
HORN DECIBEL AND CURRENT RATINGS PRODUCT INFORMATION