I. INTRODUCTION
The Gentex models GEC3-12, GES3-12, GEH12,are high quality audible and/or visible signaling appliances. The high intensity strobe utilizes a Xenon flash tube that
generates a high-intensity flash visible from all angles. This appliance is intended to provide a visible, audible or audible/visible, depending on the model, notification
signal for the purpose of life safety and property protection. The GEC3-12 and GES3-12 are provided with a slider switch which allows for candela intensity selection at the
installation site; the intensities which can be selected are 15Cd, 30Cd, 60Cd or 75Cd. This appliance is ideal for any occupancy that requires notification appliances per the
applicable building or fire code or wherever dependable alarms are required. The strobe is listed in compliance with ANSI/UL 1971.
II. LOCATION
This appliance is intended for use in fire alarm systems and is to be installed in accordance with this manual, the recommendation of the local authorities having
jurisdiction, and other NFPA documents that provide standards on notification appliances for protective signaling systems. The GEC3-12, GES3-12, GEH-12 is intended for
indoor installations only; this appliance is
not
listed for
outdoor
or drip proof applications.
Wall mounted strobe and horn/strobe appliances shall have their entire lens at heights above the finished floor of not less than 80 in. (2m) and not greater than 96 in.
(2.4m)**. Spacing shall be in accordance with Table A. If a room configuration is not square, the room size that will entirely encompass the room or subdivide the room
into multiple squares shall be used. Wall mounted horn only appliances shall have their tops above the finished floors at heights of not less than 90in. (2.30m) and below
the finished ceilings at heights of not less than 6 in. (152mm). Different mounting heights shall be permitted by the AHJ provided the sound pressure level requirements of
NFPA 72 are met.
III. MOUNTING, ROUGH-IN BOX AND RUN WIRING
This unit is designed for mounting to most single gang boxes, 4” square outlet boxes, 2-gang masonry boxes or non-metallic 2-gang switch boxes. Conduit entrance to
boxes should be selected to insure sufficient wiring clearance.
1. Run a minimum 18 gauge insulated 2 or more conductor cable.
2. Mount a box for each remote signaling appliance. Screw bracket onto box. Insert signal into bracket and slide to the right firmly into the terminal block
receptacle. Place housing over mounted assembly and screw together with single screw at the bottom of the signal. Cover screw with plastic tab.
NOTICE:
WIRING SHOULD BE CONNECTED TO MOUNTING BRACKET PRIOR TO MOUNTING SIGNAL. INCOMING POSITIVE POWER LEAD MUST BE BROKEN AND EACH
LEAD IS TO BE INSERTED INTO EACH OF THE TOP TWO TERMINALS. IF TWO POWER RUNS ARE MADE TO THE SIGNAL, ONE FOR THE STROBE AND ONE FOR THE HORN,
ONLY ONE OF THE RUNS MUST HAVE ITS POSITIVE LEAD BROKEN AND PLACED UNDER THE TWO SEPARATE TOP TERMINALS. A BARRIER IS PROVIDED TO PREVENT
BOTH LEADS FROM BEING PLACED UNDER THE SAME TERMINAL.
GEC3-12, GES3-12
& GEH12 SERIES
ANSI/UL 1971 AND/OR ANSI/UL 464 COMPLIANT
VISIBLE AND/OR AUDIBLE
SIGNALING APPLIANCES
550-0636
Page 1
GEC3-12, GES3-12 PRODUCT INFORMATION
550-0636-000
550-0636-000
Degrees
% of Rating
0
5-25
30-45
50
100
95
75
55
Degrees
% of Rating
0
5-30
35
40
100
90
65
46
LIGHT OUTPUT IN PERCENTAGE WHEN MEASURED
FROM THE FOLLOWING DIRECTIONS - PER UL 1971
Wall and Ceiling Mount Horizontal Dispersion
Ceiling Mount Vertical Dispersion
Wall Mount Horizontal Dispersion
0
30
60
90
30
90
60
Light
Light
65
35
60
40
55
45
90
12
85
12
80
12
75
13
70
15
65
16
60
18
55
22
50
27
45
34
70
35
75
30
80
30
85
25
90
25
75
75
15
15
45
45
NA = Not allowable
Table A
Room Spacing for Wall-Mounted Visible Appliances per NFPA 72, 2019 Edition
Maximum Room Size
Minimum Required Light Output
( Effective Intensity, Cd)
Meters
Feet
One Light
per Room
Four Lights per Room
(One Light per Wall)
6.10 x 6.10
20 x 20
15
NA
8.53 x 8.53
28 x 28
30
NA
9.14 x 9.14
30 x 30
34
NA
12.2 x 12.2
40 x 40
60
15
13.7 x 13.7
45 x 45
75
19
15.2 x 15.2
50 x 50
94
30
16.5 x 16.5
54 x 54
110
30
16.8 x 16.8
55 x 55
115
30
18.3 x 18.3
60 x 60
135
30
19.2 x 19.2
63 x 63
150
37
20.7 x 20.7
68 x 68
177
43
21.3 x 21.3
70 x 70
184
60
24.4 x 24.4
80 x 80
240
60
27.4 x 27.4
90 x 90
304
95
30.5 x 30.5
100 x 100
375
95
33.5 x 33.5
110 x 110
455
135
36.6 x 36.6
120 x 120
540
135
39.6 x 39.6
130 x 130
635
185
**Effective Intensity Requirements for Sleeping Areas
Visible Notification Appliance
Distance from Ceiling to Top of Lens
Intensity
greater than or equal to 24”
110cd
less than 24”
177cd
VISUAL APPLIANCE
SLEEPING ROOM
STROBE LIGHT MUST BE WITHIN 16 FEET OF PILLOW
CAUTION:
Strobe light must
be installed within
16 feet of the pillow
when used in a
sleeping area.
Strobe light can not be seen when objects such as doors, furniture or walls block strobe light.
NOTICE:
w
THE VISUAL SIGNAL MUST BE IN THE DIRECT VIEWING AREA OF THE OCCUPANT IN ORDER TO BE SEEN.
w
VISUAL SIGNALS FOR THE HEARING IMPAIRED ARE ONLY ONE METHOD OF ALERTING THE HEARING IMPAIRED. VISUAL SIGNALS MAY NOT BE THE PREFERRED
METHOD FOR NOTIFYING ALL HEARING IMPAIRED INDIVIDUALS.
w
THE STROBE LIGHT MUST BE SEEN BY THE SLEEPING PERSON. IF THE PERSON HAS HEAD TURNED OR OTHERWISE UNABLE TO BE ALERTED BY VISUAL, THE STROBE WILL NOT
BE EFFECTIVE.