GE-VX WIRING DIAGRAM
GE-VX
Section A-5
GE-V1 and GE-V2
Electrician’s notes
wiring tips and hints (see guide for details)
SEE THE ELECTRICIAN’S NOTE OF THE MASTER CONTROL. IF NOT STATED
USE: COMMUNICATION WIRING SHEILDED, TWISTED PAIR (8 TWIST/FT).
MAX LENGTH FOR 350pF/M CABLE: 492FT (150M). MAX LENGTH FOR 89pF/M
CABLE: 820FT (250M).
HIGH VOLTAGE WIRE INSTALLED ACCORDING TO LOCAL WIRING CODE.
INSTALL LOW VOLTAGE WIRES (PROBES, COMPUTER LINK OR
POTENTIOMETER WIRES) AT LEAST 12 INCHES (30cm) AWAY FROM HIGH
VOLTAGE WIRES (120/230VAC, 24VDC). ALWAYS CROSS HIGH AND LOW
VOLTAGE WIRES AT A 90-DEGREE ANGLE.
THE CURRENT SHALL NOT EXCEED 12.5A AT EACH OUTPUT (OUT 1-2) FOR
A RESISTIVE LOAD. FOR AN INDUCTIVE LOAD, THE CURRENT SHALL NOT
EXCEED 10A AT EACH OUTPUT (OUT 1-2).
1 WIRE ONLY PER GREEN TERMINAL. USE WIRE CONNECTOR IF YOU
WANT TO CONNECT MORE THAN 1 WIRE.
THESE MODULES MUST BE ON SAME POWER PHASE AND LINE VOLTAGE
AS THE BOARD TO WHICH IT IS CONNECTED TO.
USE THE WIRE CONNECTOR TO CONNECT THE GROUND WIRE TO THE
GROUND OF THE ELECTRICAL INSTALLATION.
1
2
3
4
6
5
7