ADVANCED PROGRAMMING

Default

FS

Fail-safe:

If this function is active, it enables a functional test of the photocells 
before any movement of the gate occurs (§ 6.1-

  10

, § 6.2). 

If the test fails, the gear motor does not control the movement.

Y

     = Active 

no

  = Disabled

no

SA

Safe:

If active and 

FS

=

Y

, it enables a functional test of the safety devices 

connected to the EDGE terminal before every gate movement
(§ 6.1-

 10

).

Y

     = Active 

no

  = Disabled

no

PF

Pre-flashing:

If active, it sets a 5 second pre-flashing on the LAMP output
(§ 6.1-

 11

).

no

 = disabled

oP

 = only before opening

CL

 = only before closing

OC

 = before every movement

no

SP

W.L.: 

(

§ 6.1

-

 10

)

Do not exceed the maximum load of the output
(24 V

"

 - 3 W). If necessary, use a relay and a power 

supply that is external to the board.

00

 = 

standard indicator lamp

 (on during opening, when open 

and open in pause; flashing during closing; off when gate closed).
From 

01

 to 

4.1

 = 

timed output

. E.g. courtesy light: The time can 

be adjusted from 

0

 to 

59

, in 1 second steps and subsequently from 

1.0

 to 

4.1

 in 10 second steps.

E1

 = electric lock 

command

 before the opening movement.

E2

 = electric lock 

command

 before opening and closing move-

ments.

E3

 = traffic light 

function

: the output is active when the gate is 

open and open in pause. It is disabled 3 seconds before the closing 
manoeuvre starts, during which there are 3 seconds of pre-flashing 
on the LAMP output (

§ 6.1-

 11

). Disabled during closing and 

when the gate is closed.

E4

 = traffic light function: the output is active only in the closing 

state.

00

Ph

Closing photocells logic:

Sets the tripping mode of the photocells during closing (FSW CL).

Y

    = Stop and reverse to opening when disengaged.

no

  = Immediate reverse to opening

no

oP

Opening photocells logic:

Sets the tripping mode of photocells during opening (FSW OP).

Y

   = Immediate reverse to closing

no

 = Stop and reverse to opening when disengaged

no

EC

Encoder:

The encoder operates as an anti-crushing device: if the gate 
strikes an obstacle, it reverses the gate movement for 2 seconds. 
If, during the two seconds in which it reverses, another obstacle is 
encountered, it stops moving (

St

=

02

). The sensitivity of the anti-

crushing system must be set by regulating the function between 

01

 

(maximum sensitivity) to 

99

 (minimum sensitivity).

00

         = Encoder not installed or disabled

01

-

99

  = Encoder active and sensitivity adjustment.

The encoder also controls decelerations and partial opening.

00

ADVANCED PROGRAMMING

Default

rP

Pre-limit switch deceleration:

This sets the deceleration of the gate before the opening and closing 
limit switches are tripped. 
The time can be regulated from 

00

 to 

99

, in 0.1 second steps.

If an encoder is installed and active, the deceleration is not de-
termined on a time basis but by the number of motor revs, which 
enables a greater precision to be obtained.

00

        = Deceleration disabled

01

-

99

 = Deceleration active

10

rA

Post-limit switch deceleration:

This sets the deceleration of the gate after the opening and closing 
limit switches have been tripped. 
The time can be regulated from 

00

 to 

20

, in 0.1 second steps.

If an encoder is installed and active, the deceleration is not de-
termined on a time basis but by the number of motor revs, which 
enables a greater precision to be obtained.

00

        = Deceleration disabled

01

-

20

 = Deceleration active

05

PO

Partial opening:

This sets the partial opening width (OPEN B). It can be regulated 
from 

01

 to 

20

.

If an encoder is installed and active, partial opening is determined 
by the number of motor revs, which enables a greater precision to 
be obtained. 

05

t

Cycle time-out:

Set a value of 5 or 10 seconds more than the time it takes the gate 
to travel from one limit switch to another. This prevents the motor 
from overheating in the event that the limit switches are broken.
It can be regulated from 

0

 to 

59

, in 1 second steps. The display 

subsequently changes to minutes and tens of seconds, separated 
by a point, in 10 second steps up to a maximum of 

4.1

minutes.

E.g.  

2.5

=2 min. and 50 sec.

The set value does not exactly correspond to the 
maximum operating time of the motor because this 
is modified by the deceleration times.

2.0

AS

Assistance request:

If active, at the end of the countdown of the following function 
(“Cycle programming”) there are 2 seconds of pre-flashing on 
the LAMP output (§ 6.1-

  11

), in addition to that set in the 

PF

function, at every OPEN pulse. This can be useful for setting 

scheduled maintenance work.

Y

   = Active

no

 = Disabled

no

nc

Cycle programming:

This function is linked to the previous one (“Assistance request”). It 
allows a countdown for the operating cycles of the gear motor to 
be set.  It is settable, in thousands, from 

00

 to 

99

 thousand cycles.

00

St

Gate status:

Exit from the programming function and view the gate status
(§ 7.4-

 14

).

https://smartel.ua

Содержание Blizzard 500 C

Страница 1: ...BLIZZARD 500 C BLIZZARD 900 C https smartel ua ...

Страница 2: ...pective manufac turers Customers may make copies exclusively for their own use This manual was published in 2016 Copyright FAAC S p A depuis 2016 Tous droits réservés Aucunepartiedecemanuelnepeutêtrereproduite archivéeoudistribuéeàdestiers ni copiée sous tout format et avec tout moyen qu il soit électronique mécanique ou par photocopie sans le consentement écrit préalable de FAAC S p A Tous les no...

Страница 3: ...acturer Company name FAAC S p A Soc Unipersonale Address Via Calari 10 40069 Zola Predosa BOLOGNA ITALY hereby declares under his sole responsibility that the following product Description Gear motor for sliding gates Model BLIZZARD 500 C BLIZZARD 900 C Complies with the following relevant Union harmonization legislations 2014 30 EU 2011 65 EU Furthermore the following harmonised standards have be...

Страница 4: ...monised standards Anyone automating a gate new or existing is classified as the Manufacturer of the Machine They are therefore required by law among other things to carry out a risk analysis of the machine automatic gate in its entirety and take protective measures to fulfil the essential safety requirements specified in Annex I of the Machinery Directive This manual also contains general informat...

Страница 5: ...a tion and for completing the Register of the system The installer must prove or declare to possess technical and profes sional proficiency to perform installation testing and maintenance activities according to the requirements in these instructions Installationactivitiesrequirespecialworkconditionstoreducetothe minimum the risks of accidents and serious damage Furthermore the suitable precaution...

Страница 6: ...900 C The packaging materials plastic polystyrene etc must not be left within reach of children as they are potential hazards When you have finished with them dispose of the packaging in the appropriate containers as per applicable waste disposal regulations 2 4 DISPOSAL OF THE PRODUCT It is prohibited to install the automation system to create fire doors Itisprohibitedtoinstalltheautomationsystem...

Страница 7: ...rce 300 N 220 N 410 N 380 N Pinion Z16 Module 4 Z16 Module 4 Z16 Module 4 Z16 Module 4 Max sliding gate section length 15 m 15 m 15 m 15 m Max sliding gate section weight 500 kg 500 kg 900 kg 900 kg Sliding gate section speed 12 m min 14 m min 12 m min 14 m min Ambient operating temperature 20 C 55 C 20 C 55 C 20 C 55 C 20 C 55 C Type of use Residential Condominium Residential Condominium Resident...

Страница 8: ...are accessories 3 Electric motor 4 Magnetic limit stop sensor 5 Electronic board 6 Magnetic limit switches 7 Release device 8 Start up capacitor 9 Earth connection 10 Power cable clamp 11 Z16 Module 4 pinion 7 Installation Accessories 1 Base plate with mounting hardware 2 Steel rack 3 Spacers for steel rack to be screwed or welded 4 Nylon rack 5 Mounting hardware for nylon rack INSTALLATION ACCESS...

Страница 9: ...ructure columns guides mechanical strikers sliding gate section must be solid and there must be no risk of detachment or collapse taking into consideration the weight of the sliding gate section force appliedbywindandtheforcesgeneratedbythegearmotor Perform structural calculations where necessary No signs of corrosion or cracking in the structure Sliding gate section perfectly vertical in all move...

Страница 10: ... Nm ELECTRICIAN S SCISSORS 6 5 5 5 3 6 HSS DRILL BIT of specified sizes M8 THREAD CUTTER of specified sizes for steel rack to be screwed on SPIRIT LEVEL 4 3 EXAMPLE SYSTEM The example system is a purely illustrative and not exhaustive representation of BLIZZARD 500 900 C TAPE MEASURE SCREW CLAMP WELDING EQUIPMENT for steel rack to be welded on ANGLE GRINDER 0 1 2 3 4 5 6 CALLIPER WIRE STRIPPER TER...

Страница 11: ...88 132 50 6 288 132 Translation of the original instructions ENGLISH Translation of the original instructions ENGLISH POSITIONING THE RACK 5 2 INSTALLATION DIMENSIONS POSITIONING THE BASE PLATE CENTRELINE DISTANCES Opening to the left Opening to the right Nylon rack Foundation https smartel ua ...

Страница 12: ... Take the cable conduits out from the hole 12 1 and install the base plate Do not bury the base plate in the concrete 4 Use a spirit level to check that the slab is horizontal making any corrections before the concrete goes off 12 5 4 FASTENING THE GEAR MOTOR RISKS PERSONAL PROTECTIVE EQUIPMENT Wait for the concrete to cure fully before proceeding Lift the gear motor holding it by the base 1 Passt...

Страница 13: ...ith personalised key is available as an optional accessory MANUAL RELEASE 1 Open the plastic cap on the release device 15 1 2 Turn the lock clockwise using a coin or your personalised key 15 1 3 Turn the knob clockwise 15 2 RESTORING AUTOMATIC OPERATION 1 Turn the knob anticlockwise 2 Turn the lock anticlockwise 3 Manually move the gate until the mechanical system engages 5 6 INSTALLING THE RACK R...

Страница 14: ... weld the other two spacers repeating the operations in steps 5 and 6 7 If necessary install another rack section as in step 1 8 Rest the section on the pinion bringing it up to the previous one use a third section screw clamps and a spirit level to line up the teeth and check it is level 18 9 Weld the spacers repeating the operations in points 5 6 and 7 10 Add other rack sections until the entire...

Страница 15: ... use a third section screw clamps and a spirit level to line up the teeth and check it is level 21 8 Install the section repeating the operations in points 5 6 and 7 9 Add other rack sections until the entire length of the sliding gate section is covered 10 If the final section is too long cut it with an angle grinder near one of the three slots 22 NYLON RACK AND MOUNTING HARDWARE 1 Rest a rack se...

Страница 16: ...ear one of the three slots 25 5 7 ADJUSTMENTS AND CHECKS RISKS PERSONAL PROTECTIVE EQUIPMENT The operations described in this section are fundamentally important to the integrity and operation of the gear motor 1 When you have installed the rack lower the gear mo tor by 1 5mm 2 6 1 using the four support nuts 27 1 2 Check that the gear motor is level using a spirit level 27 3 Tighten the four uppe...

Страница 17: ...tart up capacitor J5 Rapid connector for the magnetic limit switch sensor J6 Terminal board for motor and flashing light J7 Terminal board for main power supply F1 Fuse for main power supply F2 Fuse for accessories power supply LED FCA Limit switch 1 FCC Limit switch 2 OPEN B Partial opening command OPEN A Total opening command FSW OP Opening photocells FSW CL Closing photocells STOP Automation st...

Страница 18: ...gativepoleforaccessoriessupply 100 mA max It can be used to carry out a functional test of the safetydevicesconnectedtotheinputsFSWOP FSWCLandEDGE If the test fails the gear motor does control the movement Please refer to 6 2 e 7 4 15 12 W L Programmable output 100 mA max When active it provides a negativeforaccessories Default indicatorlamp 7 4 15 SP J2 RapidconnectorforinsertingtheGENIUS5 pinrad...

Страница 19: ... and 7 8 EDGE 33 If active reverses the movement for 2 seconds and stops the gear motor It is usually used for connecting sensitive edges If multiplecontactsareused theymustbeconnectedinseries 30 If no contact is used bridge terminals 6 and 11 PHOTOCELLS DURING OPENING FSW OP 34 If active they trip during the opening movement of the gate the outcome depends on a function in Advanced Programming 7 ...

Страница 20: ...arthing wire that is connected to terminal PE of J7 40 1 1 Crimp the electric motor and system earth wires together using the supplied terminal 40 2 2 Install the M5 nut washer and terminal supplied onto the gear motor earth connection 40 3 Tighten the nut 3 Connect the phase wires and neutral to terminals L and N respec tively of J7 40 4 13 LEDs Check STATUS MEANING FCA 7 3 FCC 7 3 OPEN B Partial...

Страница 21: ... by 1m 4 Drill a 3 6mm diameter hole corresponding to the central points of the slots Fasten the limit switch using two 3 9x16 self tapping screws and two washers supplied 45 2 5 Manually move the gate back into its stop position when closed and check that the FCC LED turns off Otherwise adjust the posi tion of the limit switch using the slots 6 Move the gate to the open position by hand 7 Positio...

Страница 22: ... F to go to the next function 14 Basic Programming BASIC PROGRAMMING Default LO Operating logics 9 A Automatic AP Automatic Step by Step S Automatic Safety E Semi automatic EP Semi automatic Step by Step C Dead Man b Semi automatic B bC Mixed b during opening C during closing EP PA Pause time Thishasaneffectonlyifanautomaticlogichasbeenselected Ad justablefrom0 to59 in1secondsteps Thedisplaysubseq...

Страница 23: ...minimum sensitivity 00 Encoder not installed or disabled 01 99 Encoder active and sensitivity adjustment The encoder also controls decelerations and partial opening 00 ADVANCED PROGRAMMING Default rP Pre limit switch deceleration Thissetsthedecelerationofthegatebeforetheopeningandclosing limit switches are tripped The time can be regulated from 00 to 99 in 0 1 second steps If an encoder is install...

Страница 24: ... are tripped In particular the display must indicate status 03 or 04in correspondence with the opening limit switch the display must indicate status 00in correspondence with the closing limit switch 7 6 FINAL OPERATIONS RISKS PERSONAL PROTECTIVE EQUIPMENT 1 Ensure that the forces generated by the leaf are within the limits allowed by the standard Use an impact curve gauge in ac cordance with stand...

Страница 25: ...t the power supply and connecting cables and the cable glands are intact 12 Check that the connectors and wiring are intact Check that there are no signs of overheating burning etc of electronic com ponents 12 Check that the earth connections are intact 12 Check the operation of the circuit breaker and RCD 12 Check that the limit switch is intact and that it operates correctly 12 Control Devices C...

Страница 26: ...ivated it must only be possible to move the gate manually 6 Check that the caps on the locks are present Check that the maximum force required for manual movement of the gate is below 225 N in residential areas and 390 N in industrial or commercial settings 6 Check that the safety edges operate correctly when faced with an obstacle 6 Check that the encoder where present functions correctly when an...

Страница 27: ...ps Stops 7 4 15 oP No effect Stops Opens when disengaged Reverses to closing for 2 seconds OPEN IN PAUSE Stops Stops Stops No effect Resets pause time OPEN disabled Resets pause time OPEN disabled No effect OPEN disabled WHEN CLOSING Opens Opens Stops No effect memo rizes OPEN 7 4 15 Ph Stops Opens when disengaged Reversestoopening for 2 seconds STOPPED Closes Closes Noeffect OPENdisa bled No effe...

Страница 28: ...a bled WHEN OPENING Stops Stops Stops 7 4 15 oP No effect Stops Opens when disengaged Reverses to closing for 2 seconds OPEN Closes Closes Stops No effect Noeffect OPENdisa bled Noeffect OPENdisa bled Noeffect OPENdisa bled WHEN CLOSING Stops Stops Stops Noeffect memorizes OPEN 7 4 15 Ph Stops Opens when disengaged Reverses to opening for 2 seconds STOPPED Restartsintheoppo sitedirection Always cl...

Страница 29: ...ed No effect OPEN B disabled Noeffect OPENdisa bled Noeffect OPENdisa bled LOGIC BC MIXED GATE STATUS PULSES MAINTAINED COMMANDS SAFETY DEVICES OPEN A OPEN B CLOSE STOP FSW OP FSW CL FSW CL OP EDGE CLOSED Opens No effect No effect OPEN A disabled No effect OPEN A disabled No effect No effect OPEN A disabled No effect OPEN A disabled WHEN OPENING No effect No effect Stops Noeffect memorizes OPEN A ...

Страница 30: ...ole way Do not push it and let it slide freely Do not leave the gate with the release engaged after moving it manu ally restore automatic operation RELEASE OPERATION 1 Open the plastic cap on the release device 48 1 2 Turn the lock clockwise using a coin or your personalised key 48 1 3 Turn the knob clockwise 48 2 RESTORING AUTOMATIC OPERATION 1 Turn the knob anticlockwise 2 Turn the lock anticloc...

Страница 31: ...https smartel ua ...

Страница 32: ...BLIZZARD 500 900 C 32 532103 Rev B https smartel ua ООО Компания Строймир г Киев ул Борщаговская 154А оф 435 38 044 331 15 43 info smartel ua www smartel ua ...

Отзывы: