background image

 

Model

 

ITE-100  

Description 

Generator interlock kit fits Gould or ITE 100 Amp Panels with 1 ¼ 
spacing 

Main Breaker

 

100 amp single handle Vertical throw up (on) down (off)  

Generator Breaker

 

Top left side 2 positions 

 

     

 

WARNING 

Only qualified personnel should be working on the panel box 

An amateur should 

NEVER

 open the panel box 

Please follow all rules and regulations of the National Electric Code

 

 

Step 1:  Disassemble the interlock. Place the bottom plate (holes only) above the top left breaker and mark holes. 

 

 
Step 2:  Turn off main breaker and remove panel cover.  
 
Step 3:  Drill holes as marked on panel cover with supplied 3/16 drill bit and remove all burs from drilling cover. 
 
Step 4:   Insert screws from rear of cover, install bottom plate, and install top plate (slotted) install thread lock to screws and install 

retaining nuts. Ensure proper movement. 

 
Step 5:  Install 2 pole Generator breaker on top left side and place Generator Warning Sticker on Generator breaker. 
 
Step 6:   Combine the zip ties to make a loop and install zip ties around top set of breakers in panel as shown in picture below. Pull on 

ends to make tight around breakers.  Install Warning label next to release tab on zip tie at generator breaker. 