manualshive.com logo in svg
background image

1

GEH

6280

 I

 

NSTRUCTIONS

Power Break® II Circuit Breaker Accessories

  

Mechanical Counter 

Introduction 

The Mechanical Counter, shown in Figure 1, can be installed 
in 800-4000 ampere frame Power Break II circuit breakers. 
Its function is to count the number of times the breaker is 
closed.  The  catalog  number  when  ordered  with  a  circuit 
breaker for factory installation is SPCOUNTER. The catalog 
number  of  the  field  installable  Mechanical  Counter  kit  is 
SPCOUNTER

R

control power to the accessories and motor operator (if
present). If it is a draw-out breaker, rack it out.
Loosen the four #8-32 screws on the trim-plate assembly
and remove the trim plate.

Loosen the four screws at the corners of the breaker 
cover. Remove the cover from the breaker face.
On the breaker cover, use a screwdriver to punch out 
the  knockout  above  the  CHARGE-DISCHARGE  flag 
opening.
Hold the ON-OFF flag towards the ON position, then 
carefully insert the flag lockout plate to retain the flag 
in  this  position.  The  flag  lockout  plate  should  be 
installed close to the side frame on which the ON-OFF 
flag  pivots  and  over  the    larger  diameter  portion  of  
the    mechanism  cross  pin.  The  installed  flag  lockout 
plate is  shown in  Figure 2.

and  over the  larger

 

diameter  portion 

mechanism  cross  pin.

 

The installed  flag  lockout 

plate  is  shown  in  Figure 

2.

Locate  the  two  mounting  holes  through  the  side

 

frame, behind the CHARGE  DISCHARGE flag. Place

 

the

 

spring-loaded Mechanical Counter arm above the

 

tab

 

on the ON-OFF flag, while simultaneously

 

inserting the

 

two pins on the Mechanical Counter

 

through the holes

 

in the side frame.
Slide the straight legs of the provided clip over the pin

 

on the Mechanical Counter furthest from the ON-OFF

 

flag.  Rotate  the  clip  counterclockwise  until  the  cir-
cular part of the clip snaps over the second pin on the

 

Mechanical Counter.
Carefully  remove  the  flag  lockout  plate,  allowing  the

 

ON-OFF flag to return to the OFF position. The instal-
led Mechanical Counter 

is 

shown in Figure 3.

LOCKOUT

 

 

PLATE 

Figure  1.  Mechanical Counter. 

Operation 

The  count displayed by the Mechanical Counter  is increme- 
nted each time the circuit breaker is closed. 

Figure 2.  Flag  lockout plate  installed in breaker. 

Installation

WARNING: 

Before  installing  any  accessories,

 

turn 

the breaker  OFF,  disconnect  it  from  all  voltage  sources, 

and discharge the closing springs.

AVERTISSEMENT:

 Avant d'installer tout accessoire, mettre le 

disjoncteur en position OFF, le d

é

connecter de toute tension 

d'alimentation, et d

é

charge  les ressorts d'armement 

Install the Mechanical Counter with the following procedure. 

1.

Turn off the breaker, discharge the springs,and turn off

2

.

3

.

4

.

4

.

6

.

7

.

8

.

Отзывы: