36
Figure 32:
HTTP
– Threshold event
The CS121 firmware version 4.27.x or higher provides the option to configure pre-threshold
events for the analog sensor inputs (temperature, humidity etc.) additionally. In this example a
pre-threshold alarm for a SM_T_COM temperature sensor for the value temperature low of
13°C and temperature high of 37°C were defined. The analog values for external sensors are
configurable through the variable SM_analogue 1-8. The proper threshold events for
temperature low of 10°C and temperature high of 40°C were defined into the menu “COM2 &
AUX” for the SM_T_COM.
Figure 33:
HTTP
– COM2 Threshold events SM_T_COM
4.2.13.2
Logfile Entries
For a numerous of events logfile entries are already pre-configured as default. To configure a
new logfile
entry, type in the field “Text” the desired message you wish to enter in the logfile
and choose the option on the right side, when/how often the message should appear in the
logfile.