BNC2 - BACnet Gateway for UPS Systems and BACS
®
systems
Copyright of the European Union is effective (Copyright EU) (c) 2016 GENEREX GmbH, Hamburg, Germany, All rights reserved
TEL +49(40)22692910 - EMAIL [email protected] - WEB www.generex.de (This and all other product datasheets are available for download.)
Restoring a Configuration
First switch to the configuration mode [1]
From the drop-down menu "Other" and then "Export / Import Config". Choose [2]
Select the file that contains the desired configuration. [3]
Load the configuration by clicking the button "Load Configuration" [4] high. This process can
also take some time Anpruch. The progress bar of the browser in this case indicates the
current status. When the upload is complete, restart the gateway by clicking on the button
"Restart now". The desired configuration is after the restart.