BNC2 - BACnet Gateway for UPS Systems and BACS
®
systems
Copyright of the European Union is effective (Copyright EU) (c) 2016 GENEREX GmbH, Hamburg, Germany, All rights reserved
TEL +49(40)22692910 - EMAIL [email protected] - WEB www.generex.de (This and all other product datasheets are available for download.)
Configuration of the Modbus TCP/IP Client
If you are not already in the configuration mode, switch into it by pressing the button
"Configuration Mode" there.
Click the left button on the Modbus TCP / IP Client
Please ask first at the top of the following values:
Delay Between Messages: 10ms
Response Timeout: 20000ms
Delay Between Attempts Connect: 1000ms
Dependency Protocol: None
Close the entry by clicking
“Save Parameters” button.
I
Set in the "IP Address", the IP address of the CS121 / CS141 a. In this example it is the
192.168.222.91.
The TCP Port 502 (default).
Make sure that the checkbox "Enable 0-Base Addressing" is activated safely.
Should not the CS121 are the default subnet and you are connected via the default IP is an
error message, which can ignore
Please scroll down and close the input by clicking Save Parameters from.
Configuration of the BACnet IP Server
Please adjust these settings according to the specifications of the BACnet infrastructure.
If the BACnet / IP client in a Andren subnet there is the possibility the BACnet IP Server in the
other subnet involve:
Foreign Device Registration (recommended). As time To_Live time time specifies how often
data should have been sent to the client.
Static Device Binding: Only if supported by the client).