En-15

TROUBLESHOOTING

In the event of a malfunction (burning smell, etc.), immediately stop operation, turn off the cir-
cuit breaker, and consult authorized service personnel.
Merely turning off the unit’s power switch will not completely disconnect the unit from the power
source. Always be sure to turn off your circuit breaker to ensure that power is completely off.

Before requesting service, perform the following checks:

WARNING!

Symptom

Doesn’t operate immedi-
ately:

Noise is heard:

Smells:

Mist or steam are
emitted:

Airflow is weak or stops:

Water is produced from
the outdoor unit:

The indoor unit is warm
when stopped (heating
mode):

Problem

If the unit is stopped and then immediately started again, the com-
pressor will not operate for about 3 minutes, in order to prevent
fuse blowouts.

Whenever the power supply plug is disconnected and then recon-
nected to a power outlet, the protection circuit will operate for about
3 minutes, preventing unit operation during that period.

During operation and immediately after stopping the unit, the
sound of water flowing in the air conditioner’s piping may be
heard. Also, noise may be particularly noticeable for about 2 to 3
minutes after starting operation (sound of coolant flowing).

During operation, a slight squeaking sound may be heard. This is
the result of minute expansion and contraction of the front cover
due to temperature changes.

During Heating operation, a sizzling sound may be heard occa-
sional. This sound is produced by the Automatic Defrosting op-
eration.

Some smell may be emitted from the indoor unit. This smell is
the result of room smells (furniture, tobacco, etc.) which have
been taken into the air conditioner.

During Cooling or Dry operation, a thin mist may be seen emitted
from the indoor unit. This results from the sudden Cooling of
room air by the air emitted from the air conditioner, resulting in
condensation and misting.

During Heating operation, the outdoor unit’s fan may stop, and
steam may be seen rising from the unit. This is due to Automatic
Defrosting operation.

When Heating operation is started, fan speed is temporarily very
low, to allow internal parts to warm up.

During Heating operation, if the room temperature rises above
the thermostat setting, the outdoor unit will stop, and the indoor
unit will operate at very low fan speed. If you wish to warm the
room further, set the thermostat for a higher setting.

During Heating operation, the unit will temporarily stop opera-
tion (between 7 and 15 minutes) as the Automatic Defrosting mode
operates. During Automatic Defrosting operation, the OPERATION
indicator lamp will flash.

The fan may operate at very low speed during Dry operation or
when the unit is monitoring the room’s temperature.

During SUPER QUIET operation, the fan will operate at very low speed.

In the monitor AUTO operation, the fan will operate at very low speed.

During Heating operation, water may be produced from the out-
door unit due to Automatic Defrosting operation.

When the indoor unit is operating in the heating mode, a small
amount of the refrigerant is allowed to flow to the indoor unit in
order to prevent too much of the refrigerant from accumulating
in the outdoor unit. This causes the indoor unit to become warm
when stopped. This condition is normal.

See Page

16

16

16

7

7

7

16

NORMAL

FUNCTION

Содержание INVERTER AOH34PEAM4

Страница 1: ...URE REFERENCE FUJITSU GENERAL LIMITED E nglis h OPE R ATING MANUAL P N9367998012 HEAT COOL MODEL REV ERS E CYCLE INDOOR UNIT AS H9PMACW AS H12PMACW OUTDOOR UNIT AOH34PEAM4 OPERATING MANUAL ROOM AIR CONDITIONER MULTI S PLIT TYPE 4 ROOMS ...

Страница 2: ...nditioner directly to water Do not operate the air conditioner with wet hands Do not pull power supply cord Turn off power source when not using the unit for extended periods Check the condition of the installation stand for damage Do not place animals or plants in the direct path of the air flow Do not drink the water drained from the air conditioner Do not use in applications involving the stora...

Страница 3: ...NIT The WIRELESS REMOTE CONTROL UNIT allows convenient control of air conditioner operation SWING OPERATION The Air Flow Direction Louvers swings automatically up and down so that the air speeds to every nook and corner of your room REMOVABLE INTAKE GRILLE The indoor unit s INTAKE GRILLE can be removed for easy cleaning and maintenance MILDEW RESISTANT FILTER The AIR FILTER has been treated to res...

Страница 4: ...g 2 Fig 3 Fig 4 Fig 8 To facilitate explanation the accompanying illustra tion has been drawn to show all possible indicators in actual operation however the display will only show those indicators appropriate to the current op eration Fig 7 ...

Страница 5: ... Remote Control Unit Display Fig 8 U Transmit Indicator V Clock Display W Operating Mode Display X Timer Mode Display Y Fan Speed Display Z Temperature Set Display Timer Set Indicator Temperature Set Indicator Fig 1 Indoor Unit 1 Operating Control Panel Fig 2 2 POWER Switch 3 MANUAL AUTO button 4 Remote Control Signal Receiver 5 Indicator Lamps Fig 3 6 OPERATION Indicator Lamp red Lights when unit...

Страница 6: ...perating range About 7 meters When a signal is properly received by the air conditioner a beeping sound will be heard If no beep is heard press the remote control unit button again Remote Control Unit Holder PREPARATION CAUTION Take care to prevent infants from accidentally swallowing batteries When not using the remote control unit for an extended period remove the batteries to avoid possible lea...

Страница 7: ... setting range AUTO Standard temperature setting 2 C Heating 16 to 30 C Cooling Dry 18 to 30 C The thermostat cannot be used to set room temperature during the FAN mode the temperature will not appear on the remote control unit s display About three seconds later the entire display will reappear The thermostat setting should be considered a standard value and may differ somewhat from the actual ro...

Страница 8: ... accompanying table Also depending on the operating mode the room temperature setting will cause the standard temperature to be set as shown Actual Room Operating Mode Thermostat Setting Temperature standard setting 30 C or above Cooling 27 C 27 to 30 C Cooling 26 C 24 to 27 C Dry 24 C 22 to 24 C Monitor Below 22 C Heating 23 C The operating mode and standard thermostat settings are selected autom...

Страница 9: ...itioner will operate at very low fan speed for about 3 to 5 minutes after which it will switch to the selected fan set ting This period of time is provided to allow the indoor unit to warm up before begin full operation When the room temperature is very low frost may form on the outside unit and its performance may be reduced In order to remove such frost the unit will automatically enter the defr...

Страница 10: ...imer and ON timer operations in a single sequence The sequence can involve one transition from OFF timer to ON timer or from ON timer to OFF timer within a twenty four hour period The first timer function to operate will be the one set nearest to the current time The order of operation is indicated by the arrow in the Remote Control Unit s display OFF ON or OFF ON One example of PROGRAM timer use ...

Страница 11: ...uring Timer Operation Press the START STOP button About the SLEEP timer To prevent excessive warming or cooling during sleep the SLEEP timer function automatically modifies the thermostat set ting in accordance with the time setting When the set time has elapsed the air conditioner completely stops During Heating operation When the SLEEP timer is set the thermostat setting is automatically lowered...

Страница 12: ... from the air conditioner During the Cooling and Dry modes if the Air Flow Direction Louvers are left in the range 5 to 7 for more than 30 minutes they will au tomatically return to position 4 When used in a room with infants chil dren elderly or sick persons the air direction and room temperature should be considered carefully when making settings Vertical Air Direction Adjustment Press the AIR F...

Страница 13: ...eration is con tinued at the lowest downward range for more than 30 minutes the unit will automatically switch the swing range to the horizontal flow range to prevent the condensation of moisture on the outlet The SWING operation may stop temporarily when the air conditioner s fan is not operating or when operating at very low speeds MANUAL AUTO OPERATION Use the MANUAL AUTO operation in the event...

Страница 14: ...turned properly to their holes in the panel 2 Close the intake grille For purposes of example the illustration shows the unit without intake grille installed Dust can be cleaned from the air filter either with a vacuum cleaner or by washing the filter in a solution of mild de tergent and warm water If you wash the filter be sure to allow it to dry thoroughly in a shady place before rein stalling I...

Страница 15: ...rately sold replacement air clean ing filters type APS 02F and install them 1 Open the intake grille and remove the air filters 2 Replace them by two new air cleaning filters 1 Remove the old air cleaning filters in reverse order of their installation 2 Install in the same way as for installation of the air cleaning filter set 3 Install the two air filters and close the intake grille In regard to ...

Страница 16: ...from the indoor unit This smell is the result of room smells furniture tobacco etc which have been taken into the air conditioner During Cooling or Dry operation a thin mist may be seen emitted from the indoor unit This results from the sudden Cooling of room air by the air emitted from the air conditioner resulting in condensation and misting During Heating operation the outdoor unit s fan may st...

Страница 17: ...tely stop operation turn off the circuit breaker and consult authorized service personnel OPERATING TIPS Heating Performance This air conditioner operates on the heat pump principle absorbing heat from outdoor air and transferring that heat indoors As a result the operating performance is reduced as outdoor air temperature drops If you feel that insuffi cient heating performance is being produced ...

Страница 18: ...se of other electrical appliances electric shaver etc or nearby use of a wireless radio transmitter may cause the air conditioner to malfunction In this event temporarily disconnect the Power Supply Plug reconnect it and then use the remote control unit to resume operation The air conditioner power has been interrupted by a power failure The air conditioner will then restart automatically in its p...

Страница 19: ... the indoor unit is instructed to do an operating mode that it cannot perform the OPERATION indicator lamp red on the indoor unit will flash 1 second on 1 second off and the unit will go into the standby mode Heating mode and cooling mode or dry mode Heating mode and fan mode Operation can be done in the following different operat ing modes Cooling mode and dry mode Cooling mode and fan mode Dry m...

Страница 20: ...DOOR UNIT 4 UNITS 4 UNITS COOLING CAPACITY kW 10 2 10 2 9 8 9 8 POWER INPUT kW 3 90 3 96 3 84 3 88 CURRENT A 17 8 16 5 17 5 16 2 ENERGY EFFICIENCY RATIO 2 62 2 58 2 55 2 53 HEATING CAPACITY kW 11 7 12 0 11 3 11 6 POWER INPUT kW 4 00 4 27 4 00 4 27 CURRENT A 18 2 17 8 18 2 17 8 MAX PRESSURE kPa 3 000 REFRIGERANT R407C g 3 600 DIMENSIONS WEIGHT NET INDOOR UNIT HEIGHT 260 mm 260 mm WIDTH 815 mm 815 m...

Отзывы: