Model 2280A
17
3.0 Start Up and Operation
3.1 Types of User Interfaces
User interfaces are provided so that the operator may interpret and direct the Model
2280A in the performance of its various functions. User interfaces consist of a digital
display, status indicators, a mode button, and a reset button.
•
The digital display provides the user with the gas concentration at the sensor
site, fault diagnostic codes, calibration prompts, and setup parameters.
•
The status indicators provide the user with an indication of the current mode of
operation:
HIGH
(High alarm),
LOW
(Low alarm),
FAULT
,
CAL
(Calibration or
Calibration Check modes) and
SETUP
(Setup and Setup Check modes).
•
Mode
button provides the user access to the Calibration, Calibration Check,
Setup, and Setup Check modes. The
Mode
button is accessed using a small
screwdriver in the front of the unit.
•
The
Reset
button allows the user to reset latched alarms.
Figure 7: Front Panel Display