Lynx No-Idle Split AC User Manual
WARNING
Compressor is pre-charged with the right amounts of oil
and refrigerant. Do not overfill.
When adding refrigerant to the system, do not open the
high-pressure manual valve, otherwise, the AC system
would force the refrigerant into refrigerant container, and
push the lubricating oil out, which will damage the system.
When adding the lubrication oil to the compressor, only
350ml of POE RB68EP oil should be used. Please use only
designated oil type. Mixture of different brands of
lubrication oil will form precipitates, which will affect
compressor lubrication.
3.2.4
Wiring
Install and connect signal wiring between indoor and
outdoor unit before connecting the power. Connect positive and
negative supply conductors to the APU. Total length of supply
conductors should not exceed 5 meters (15 feet). Adequate
support, mechanical and thermal protection should be provided
to prevent friction and consequent insulation damage. Supply
conductors should be protected with properly sized fuse or
circuit breaker.
Содержание 2600A
Страница 1: ......
Страница 7: ...info generalcomponents ca 1 800 517 7740 2 PRINCIPLE OF OPERATION 2 1 Electrical Diagram...
Страница 8: ...7 Lynx No Idle Split AC User Manual 2 2 Plumbing Diagram...
Страница 12: ...11 Lynx No Idle Split AC User Manual...
Страница 20: ...19 Lynx No Idle Split AC User Manual The unit should not be used at temperatures below 5 41 or above 43 110...
Страница 22: ...21 Lynx No Idle Split AC User Manual 7 PARTS LIST...
Страница 23: ...info generalcomponents ca 1 800 517 7740...
Страница 24: ...23 Lynx No Idle Split AC User Manual...
Страница 25: ...info generalcomponents ca 1 800 517 7740...
Страница 26: ...25 Lynx No Idle Split AC User Manual...
Страница 27: ...info generalcomponents ca 1 800 517 7740...