Installation

10

Automatic Transfer Switch Owner’s Manual

Connecting Power Source and 

Generator Power Supply

Installation and interconnection diagrams are provided in
this manual. 

NOTE: 

All installations must comply with national, state

and local codes. It is the responsibility of the installer to
perform an installation that will pass the final electrical
inspection.

1.

Connect utility supply at the utility service
disconnect circuit breaker terminals N1 and N2.
Follow torque specifications listed on the circuit
breaker.

2.

See 

Figure 3-2

. Connect utility neutral and ground

to the Upper Neutral and Ground terminals. Neutral
and Ground terminals are bonded to each other
with a jumper wire (A).

NOTE: 

Neutral to Ground jumper wire (A) is

provided for use if required by local codes.

3.

Connect generator to the generator terminals (E1
and E2) on the transfer mechanism.

4.

Connect the generator neutral wire to the lower
neutral lug.

IMPORTANT NOTE: A jumper wire (B) bonds
the upper and lower Neutral lugs. NEVER
remove this wire.

5.

Connect a subpanel supply to lower T1 and T2
Terminals. Connect subpanel Neutral and Ground
to lower Neutral and Ground bars. 

Conductor sizes must be adequate to handle the
maximum current to which they will be subjected, based
on the 75°C column of tables, charts, etc. used to size
conductors. The installation must comply fully with all
applicable codes, standards and regulations.
Knockouts into the transfer switch can be made in the
field as needed for entry of power cables and conduit.
Conduit entry shall maintain the proper wire bending
spaces required by Tables 312.6 (A) and (B) in the NEC.
Conduits should be arranged to provide separation
between the Utility and Generator supply conductors
inside the enclosure. 

For transfer switches installed in wet locations, power
cables or conduits entering above the level of
uninsulated live parts shall use fittings listed for use in
wet locations as required by 312.2 in the NEC.

NOTE: 

If aluminum conductors are used, apply corrosion

inhibitor to conductors. After tightening terminal lugs,
carefully wipe away any excess corrosion inhibitor.

Figure 3-2. Wiring Connections

Tighten terminal lugs to the torque values as noted on the
decal located on the inside of the door. After tightening
terminal lugs, carefully wipe away any excess corrosion
inhibitor. 

Electrocution. Turn utility and emergency
power supplies to OFF before connecting 
power source and load lines. Failure to do so 
will result in death or serious injury.

 

(000116)

DANGER

004398

N2

E2

T2

A

T1

N1

E1

(000120)

CAUTION

Equipment damage. Verify all conductors are tightened 
to the factory specified torque value. Failure to do so 
could result in damage to the switch base.

 

Содержание RXSC100A3

Страница 1: ...Utility Service Circuit Breaker RXSW200A3 Service Entrance Rated with Utility Service Circuit Breaker RXSC200A3 SERIAL NUMBER _________________________ DATE PURCHASED ________________________ WWW GEN...

Страница 2: ...alates and lead which are known to the State of California to cause cancer and birth defects or other reproductive harm To minimize exposure avoid breathing exhaust do not idle the engine except as ne...

Страница 3: ...ault Current Label 13 Section 4 Operation Functional Tests and Adjustments 15 Manual Operation 15 Close to Utility Source Side 15 Close to Generator Source Side 16 Return to Utility Source Side 16 Vol...

Страница 4: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 5: ...that might involve a hazard The warnings in this manual and on tags and decals affixed to the unit are therefore not all inclusive If using a procedure work method or operating technique that the man...

Страница 6: ...the transfer switch Failure to do so will result in death or serious injury 000157 DANGER Electrocution Do not disable or modify the connection box door safety switch Doing so will result in death or...

Страница 7: ...efore working on utility connections of the transfer switch Failure to do so will result in death or serious injury 000104 DANGER Electrocution Water contact with a power source if not avoided will re...

Страница 8: ...Safety 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 9: ...a single phase system when the single phase neutral line is to be connected to a neutral lug and is not to be switched Solderless screw type terminal lugs are standard The conductor size range is as...

Страница 10: ...ion against falling rain and sleet are undamaged by the formation of ice on the enclosure Safe Use of Transfer Switch Before installing operating or servicing this equipment read the Safety Rules care...

Страница 11: ...al of eight loads Use Priorities A C 1 4 on the SACM as the top priorities then up to four SMMs as Priorities 5 8 Use only select A C priorities on the SACM as the top priorities then use additional S...

Страница 12: ...General Information 8 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 13: ...he transfer switch as close as possible to the electrical loads that are to be connected to it Mount the switch vertically to a rigid supporting structure To prevent switch distortion level all mounti...

Страница 14: ...on the 75 C column of tables charts etc used to size conductors The installation must comply fully with all applicable codes standards and regulations Knockouts into the transfer switch can be made i...

Страница 15: ...insulation rating equal to at least the maximum circuit voltage applied to any conductor within the equipment cable or conduit See NEC 300 3 C 1 Connecting SACM See Figure 3 3 The SACM can control an...

Страница 16: ...2 D Air Conditioner 2 E Thermostat 3 F Air Conditioner 3 G Thermostat 4 H Air Conditioner 4 T1 fused Battery Charge N1 fused Utility Sense N2 fused Utility Sense 0 DC Ground 194 12 VDC 23 Transfer Co...

Страница 17: ...ining the unit Owner s Manual and transfer switch manual operating handle The 2017 NEC requires that the short circuit current rating of the transfer equipment based on the type of overcurrent protect...

Страница 18: ...Installation 14 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 19: ...can be viewed through the long narrow slot in the inside cover The top of the movable contact carrier arm is yellow to be easily identified Manual operation handle in the UP position LOAD terminals T...

Страница 20: ...1 to its ON or CLOSED position 4 With an accurate AC voltmeter and frequency meter check the no load voltage and frequency Measure across ATS terminal lugs E1 to E2 E1 to NEUTRAL and E2 to NEUTRAL 5 W...

Страница 21: ...nd start when the utility source power is turned OFF after a five second delay factory default setting After starting the transfer switch should connect load circuits to the standby side after a five...

Страница 22: ...tility supply to the ATS 2 Verify managed loads are powered and all LEDs illuminate on SACM 3 Press the TEST button on the SACM 4 Verify that all of the connected loads to be shed become disabled 5 Af...

Страница 23: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 19 Section 5 Drawings and Diagrams Installation Drawings No 0G6832 A 100A SE non SE 150 200A non SE...

Страница 24: ...Drawings and Diagrams 20 Automatic Transfer Switch Owner s Manual No 10000012171 A 150 200A SE...

Страница 25: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 21 Interconnection Drawings No 10000009574 Part 1 of 2 Liquid Cooled Generator...

Страница 26: ...Drawings and Diagrams 22 Automatic Transfer Switch Owner s Manual No 10000009574 Part 2 of 2 Liquid Cooled Generator...

Страница 27: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 23 No 10000009620 SE and non SE Rated ATS 1 of 2 Air Cooled Generator...

Страница 28: ...Drawings and Diagrams 24 Automatic Transfer Switch Owner s Manual No 10000009620 SE and non SE Rated ATS 2 of 2 Air Cooled Generator...

Страница 29: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 25 This page intentionally left blank...

Страница 30: ...Drawings and Diagrams 26 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 31: ......

Страница 32: ...rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W2929...

Отзывы: