 4 

8.   From inside the building, feed the end of the 30-foot 

conduit (INCLUDED and pre-wired from transfer switch) 

through the wall to the outside.

9.  Remove the threaded lock nut from the conduit coupling.

10.  Lift cover. Remove internal 

cover plate screw and internal 

cover. Remove the knock out 

in the lower right corner of 

the external connection box. 

From the rear of the connec-

tion box, feed wires, 4-pin and 

2-pin plugs into box. Slip the 

lock nut over wires and plugs 

and tighten securely onto con-

duit coupling. Using appropri-

ate fasteners, mount external 

connection box over pre-drilled 

hole to fully conceal the hole. Seal around the hole and 

conduit with silicone caulk from both the inside and out-

side of the building. Also, caulk around the sides and top 

of the box to seal the edges to the siding or wall. Connect 

wires to lugs; black to black, white to white, and red to red. 

Torque nuts to 20 in/lbs. Snap together the 4-pin and 2-pin 

plug connector. Loosen nut from grounding lug and attach 

ground wire (green) from conduit. Reinstall nut and tighten 

to 45 in/lbs. Reinstall internal cover plate and screw. Close 

cover and install lock. This wiring is complete.

  The outdoor connection box must be locked to 

ensure safety and to discourage tampering.

11.  Locate automatic transfer switch with built-in emer-

gency load center in close proximity to the main 

distribution panel. The transfer switch can be located 

to the left or right of the main distribution panel. Two 

(2) feet is the suggested distance (see Figure 11). The 

transfer switch may be located a different distance 

from the main panel depending on available mounting 

area. Using the two (2) foot conduit connected straight 

across to the main panel is another option. Always 

adhere to local electrical codes during installation. Hold 

transfer switch against the mounting surface. Level the 

transfer switch and mark the mounting holes. Drill the 

appropriate size pilot holes. Mount transfer switch with 

built-in load center to mounting surface with appropri-

ate fasteners.

  The manufacturer recommends that a licensed elec-

trician or an individual with complete knowledge of 

electricity perform the procedures in Sections 12 

and 13.

  Switch service main circuit breaker to 

the OFF (OPEN) position prior to removal 

of cover or removal of any wiring of the 

main electrical distribution panel. The 

wires connected to the service main cir-

cuit breaker remain LIVE or HOT. Avoid contact with 

these wires and the service main circuit breaker con-

nection lugs.

10

Feed Conduit and Wires

8

Silicone

Caulk

The outer diameter of the conduit 

connector is 1-11/16”

Threaded Lock Nut

9

The outer diameter of the threaded 

end is 15/16 inches.

Mounting Automatic Transfer Switch

11

Two (2)

Feet 

Suggested 

Distance

OFF

Residential Transfer Switch Installation Guide

Содержание RTSF100A1

Страница 1: ...4 16 and 17kW Generators This Automatic Transfer Switch with built in Load Center includes an Express Install Kit Saves on installation time and cost in many cases up to 50 compared to traditional tra...

Страница 2: ......

Страница 3: ...INSTRUCTIONS The manufacturer suggests that these rules for safe operation be copied and posted near the unit s installation site Safety should be stressed to all operators and potential operators of...

Страница 4: ...th will be deter mined by the materials to be drilled and cut open end wrenches or adjustable wrenches socket wrenches or nut drivers standard and Phillips screwdrivers sledge hammer level pencil chan...

Страница 5: ...mounting pad 49 L x 25 W 3 Lay black poly film to cover the area 4 Fill the area to ground level with pea gravel or crushed stone 5 Drive an eight foot grounding rod into the ground to grade Make sure...

Страница 6: ...in emer gency load center in close proximity to the main distribution panel The transfer switch can be located to the left or right of the main distribution panel Two 2 feet is the suggested distance...

Страница 7: ...nuts are included in installation kit Trace each black hot wire connected and wire nut the white neutral wire from the same Romex cable circuit to the matching circuit number on the white neutral wire...

Страница 8: ...g strap will also be installed with the generator Save this guide for reference at time of generator installa tion DANGER Be sure the service main circuit breaker is switched OFF at time of generator...

Страница 9: ...ing the supplied threaded flexible fuel line Use a pipe sealant suitable for gaseous fuel connections Check connections for leaks by opening manual fuel shut off valve and swab or spray con nections w...

Страница 10: ...8 Residential Transfer Switch Installation Guide Installation Drawing 0H0258 A...

Страница 11: ...9 Residential Transfer Switch Installation Guide Installation Drawing 0H0258 A...

Страница 12: ...Residential Transfer Switch Installation Guide Installation Drawing 0G8573 A 10 10...

Страница 13: ...11 Residential Transfer Switch Installation Guide Electrical Schematic Drawing 0G7959 A...

Страница 14: ...12 Residential Transfer Switch Installation Guide Wiring Diagram Drawing 0G7958 A...

Страница 15: ...13 Residential Transfer Switch Installation Guide Wiring Diagram Drawing 0G7958 A...

Страница 16: ...14 Residential Transfer Switch Installation Guide Load Center Exploded View Drawing 0G8786 D...

Страница 17: ...1 HARN GTS MAIN PNL 8CIR W NEUT 0G8139 1 HARN GTS MAIN PNL 10CIR W NEUT 0G8140 1 HARN GTS MAIN PNL 12CIR W NEUT 0G7955 1 HARN GTS MAIN PNL 14CIR W NEUT 0G8141 1 HARN GTS MAIN PNL 16CIR W NEUT ITEM PAR...

Страница 18: ...16 Residential Transfer Switch Installation Guide Notes...

Страница 19: ...17 Residential Transfer Switch Installation Guide Notes...

Страница 20: ...Part No 0G8571 Revision E 08 10 09 Catalog No KGATX100 1SI Printed in U S A...

Отзывы: