1.9 LIFTING THE GENERATOR
When lifting or hoisting equipment is used, be
careful not to touch overhead power lines. The
generators weight of more than 900 pounds
requires proper tools, equipment, and qualified
personnel to be used in all phases of handling
and unpacking.
1.10 SPECIFICATIONS
1.10.1 GENERATOR SPECIFICATIONS
1.10.2 ENGINE SPECIFICATIONS
M
a
ke ................................................................................ Chry
s
ler
Di
s
pl
a
cement ...................................................................3.9 liter
s
Cylinder Arr
a
ngement ............................................................. V-6
V
a
lve Arr
a
ngement .............................................. Overhe
a
d V
a
lve
Firing Order .................................................................1-6-5-4-3-2
N
u
mber of M
a
in Be
a
ring
s
...........................................................4
Compre
ss
ion R
a
tio ........................................................... 9.1 to 1
No. of Teeth on Flywheel .........................................................164
Ignition Timing
a
t 1800 rpm ..............................30 degree
s
BTDC
S
p
a
rk Pl
u
g G
a
p .............................................. 1.01mm (0.040 in.)
Recommended
S
p
a
rk Pl
u
g
s
Ch
a
mpion ....................................................................RC12LC4
Oil Pre
ssu
re ....................................................................30-80 p
s
i
Cr
a
nkc
as
e Oil C
a
p
a
city ........................4.0 U.
S
. q
ua
rt
s
(3.8 liter
s
)
Recommended Engine Oil .......................................
S
AE 15W-40
Type of Cooling
S
y
s
tem ................. Pre
ssu
rized, clo
s
ed recovery
Cooling F
a
n ...............................................................P
us
her Type
Cooling
S
y
s
tem C
a
p
a
city ................. 5.0 U.
S
. g
a
llon
s
(19.3 liter
s
)
Recommended Cool
a
nt ............................ U
s
e
a
50-50 mixt
u
re of
ethylene glycol b
as
e
a
nd de-ionized w
a
ter.
1.11 FUEL CONSUMPTION
N
a
t
u
r
a
l G
as
% of Lo
a
d 25% 50% 75% 100%
m
3
/hr 4.1
7.7
11.0
14.2
ft
3
/hr 143.1
271.1
388.5
502.0
LP V
a
por
% of Lo
a
d 25% 50% 75% 100%
m
3
/hr
1.7 3.3 4.7 6.0
ft
3
/hr 60.7
115.0
164.9
213.0
NOTE:
Fuel consumption is given at rated maximum
continuous power output when using natural gas
rated at 1000 Btu per cubic foot. LP gas is rated at
2520 Btu per cubic foot. Actual fuel consumption
obtained may vary depending on such variables as
applied load, ambient temperature, engine condi-
tions and other environmental factors.
Fuel pressure for a natural gas set up should be
five
inches to 14 inches of water column (0.18 to 0.5
psi)
at all load ranges.
Fuel pressure for an LP vapor set up should be
11
inches to 14 inches of water column (0.4 to 0.5
psi)
at all load ranges.
1.12
RECONFIGURING THE FUEL
SYSTEM
NOTE:
All models are configured for natural gas from the
factory.
To reconfigure the fuel system from NG to LP vapor,
follow these steps:
1. Turn the main gas supply off.
2. Remove the carburetor fuel hose from the outlet
port (Port 1) of the demand regulator (Figure
1.8).
Figure 1.8 — Reconfigure the Fuel System
NG FUEL SYSTEM
LP FUEL SYSTEM
Port 1
Port 2
FUEL HOSE
BRASS HOSE
FITTING
HOUSING
PORTS
OUT
PORT 2
PLUG
FUEL HOSE
BRASS HOSE
FITTING
HOUSING
PORTS
PLUG
OUT
PORT 1
Section 1 — General Information
40kW Liquid-cooled Generators
7
Single-phase
Model
005012-1
Rated Max. Cont.
37 (NG), 40 (LP)
AC Power Output (kW)
Rated voltage (volts)
120/240
No. of Rotor Poles
4
Driven Speed of Rotor
1800
Rotor Excitation System Direct excited brush type
Type of Stator
4 Wire
Rotor/Stator Insulation
Class F/H
Содержание Quietsource 005012-1
Страница 26: ...24 Section 6 Electrical Data 40kW Liquid cooled Generators Wiring Diagram Engine Drawing No 0E8115 A ...
Страница 27: ...25 Section 6 Electrical Data 40kW Liquid cooled Generators Wiring Diagram Engine Drawing No 0E8115 A ...
Страница 28: ...26 Section 6 Electrical Data 40kW Liquid cooled Generators Electrical Schematic Engine Drawing No 0E8116 A ...
Страница 29: ...27 Section 6 Electrical Data 40kW Liquid cooled Generators Electrical Schematic Engine Drawing No 0E8116 A ...
Страница 34: ...32 Section 7 Exploded Views and Parts 40kW Liquid cooled Generators Control Panel Drawing No 0E7118 K ...
Страница 45: ...43 Section 8 Installation Diagram 40kW Liquid cooled Generators Installation Diagram Drawing No 0E8797 ...
Страница 46: ...44 Section 9 Notes 40kW Liquid cooled Generators ...