INTERCONNECTIONS
NEXUS™ CONTROL FEATURES
2-Line Plain Text LCD Display
Simple user interface for ease of operation
Mode Switch
-Auto
Automatic Start on Utility failure. 7 day exerciser
-Off
Stops unit. Power is removed. Control and charger still operate.
-Manual/Test (start)
Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Programmable start delay between 10-30 seconds
Standard
Engine Start Sequence
Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration)
Engine Warm-up
5 seconds
Engine Cool-Down
1 minute
Starter Lock-out
Starter cannot re-engage until 5 sec. after engine has stopped.
Smart Battery Charger
Standard
Automatic Voltage Regulation with Over and Under Voltage Protection
Standard
Automatic Low Oil Pressure Shutdown
Standard
Overspeed Shutdown
Standard, 72Hz
High Temperature Shutdown
Standard
Overcrank Protection
Standard
Safety Fused
Standard
Failure to Transfer Protection
Standard
Low Battery Protection
Standard
50 Event Run Log
Standard
Future Set Capable Exerciser
Standard
Incorrect Wiring Protection
Standard
Internal Fault Protection
Standard
Common External Fault Capability
Standard
Governor Failure Protection
Standard
QT130
*Single and three phase connections may vary , refer to the owner’s manual for specific connection information.
CIRCUIT BREAKER WIRE AND CONDUIT SIZE
kW
VOLTS
CB AMPS
LUG SIZE
130
240 1 Ø
600
(3) 2/0 to 400 mcm
130
240 3 Ø
450
(3) 2/0 to 400 mcm
130
208 3 Ø
500
(3) 2/0 to 400 mcm
130
480 3 Ø
225
(1) 600 mcm or (2) 1/0 to 250 mcm