background image

OPERATING DATA

KW RATING (LP/NG)

130

ENGINE SIZE

6.8 Liter V-10

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

LP

AMP

NG

AMP

CB Size

120/240V, 1-phase, 1.0 pf
120/208V, 3-phase, 0.8 pf
120/240V, 3-phase, 0.8 pf
277/480V, 3-phase, 0.8 pf

130
130
130
130

542
451
391
195

117
122
122
122

488
423
367
183

600
500
450
225

GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%

Single phase or 208-240 3-phase
480V 3-phase

270
320

ENGINE FUEL CONSUMPTION 

(Natural Gas) (Propane)

Exercise cycle
25% of rated load
50% of rated load
75% of rated load
100% of rated load

For Btu content, multiply ft

3

/hr x 2520 (LP) or ft

3

/hr x 1000 (NG)

Natural Gas

(ft

3

/hr.)

135
482
927

1292
1786

Propane

 

(gal/hr.)

 (

ft

3

/hr.)

 1.4 

54.5

 5.3 

193

 10.3 

373

 14.3 

520

 19.8 

719

ENGINE COOLING

Air flow 

(inlet air including alternator and combustion air) 

ft

3

/min.

System coolant capacity

 

US gal.

Heat rejection to coolant

 

BTU/hr.

Max. operating air temp. on radiator

 

°C (°F)

Max. ambient temperature

 

°C (°F)

6,450

4.5

496,000

60 (150)
50 (140)

COMBUSTION AIR REQUIREMENTS

Flow at rated power 60 Hz

 

cfm

336

SOUND EMISSIONS IN DBA

Exercising at 7 meters
Normal operation at 7 meters

65
75

EXHAUST

Exhaust flow at rated output 60 Hz

 

cfm

Exhaust temp. at muffler outlet

 

ºC (

°F)

1,119

521 (970)

ENGINE PARAMETERS

Rated synchronous RPM

 

60 Hz

2970

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

Temperature Deration

3% for every 10 °C above - °C

1.65% for every 10 °F above - °F

Altitude Deration

1% for every 100 m above - m

3% for every 1000 ft. above - ft.

25
77

183
600

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a 
reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage.  There is no overload capability for this rating. Ratings are in accordance with 
ISO-3046-1. Design and specifications are subject to change without notice.
kW rating is based on LPG Fuel and may derate with natural gas.

Generac

®

 Standby Generator - 130 kW

®

Содержание QT130

Страница 1: ... the surge loads to the engine An unequalled 1 voltage regulation SINGLE SOURCE SERVICE RESPONSE from Generac s extensive dealer network provides parts and service know how for the entire unit from the engine to the smallest electronic component GENERAC TRANSFER SWITCHES Long life and reliability are synonymous with GENERAC POWER SYSTEMS One reason for this confidence is that the GENERAC product l...

Страница 2: ...available Ensures protection against mother nature Electrostatically applied textured epoxy paint for added durability Enclosed critical grade muffler Quiet critical grade muffler is mounted inside the unit to prevent injuries Small compact attractive Makes for an easy eye appealing installation SAE Sound attenuated enclosure ensures quiet operation ENGINE SPECIFICATIONS MAKE Generac MODEL V type ...

Страница 3: ...x ambient temperature C F 6 450 4 5 496 000 60 150 50 140 COMBUSTION AIR REQUIREMENTS Flow at rated power 60 Hz cfm 336 SOUND EMISSIONS IN DBA Exercising at 7 meters Normal operation at 7 meters 65 75 EXHAUST Exhaust flow at rated output 60 Hz cfm Exhaust temp at muffler outlet ºC F 1 119 521 970 ENGINE PARAMETERS Rated synchronous RPM 60 Hz 2970 POWER ADJUSTMENT FOR AMBIENT CONDITIONS Temperature...

Страница 4: ...Automatic Voltage Regulation with Over and Under Voltage Protection Standard Automatic Low Oil Pressure Shutdown Standard Overspeed Shutdown Standard 72Hz High Temperature Shutdown Standard Overcrank Protection Standard Safety Fused Standard Failure to Transfer Protection Standard Low Battery Protection Standard 50 Event Run Log Standard Future Set Capable Exerciser Standard Incorrect Wiring Prote...

Страница 5: ...c Power Systems Inc S45 W29290 HWY 59 Waukesha WI 53189 generac com 2011 Generac Power Systems Inc All rights reserved All specifications are subject to change without notice Bulletin 0188700SBY C Printed in U S A 02 18 11 QT130 ...

Отзывы: