![Generac Power Systems PWRmanager Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/generac-power-systems/pwrmanager/pwrmanager_owners-manual_2208973015.webp)
Specifications
Owner’s Manual for Generac PWRmanager 12 Relay Load Controller
11
Section 4: Specifications
Environmental Specifications
Physical Specifications
Performance Specifications
Connectivity, Security
Compliance
Description
Value
Mounting Options
Indoor, Outdoor, Flush Mount, and Surface Wall
Mount.
Operating Temperature Range
-40°F to 122°F (-40°C to 50°C)
IP Rating
3R Outdoor Mounting
Description
Value
Dimensions (excluding flange)
Width 14 in x Height 9 in x Depth 5 in
(35.56 cm x 22.86 cm x 12.7 cm)
Weight
14.3 lb (6.5 kg)
Wire Sizes
14 through 6 AWG
Description
Value
Per-circuit Current Capacity
60 A resistive 120 / 240 VAC
2 HP motor load 120 VAC
4 HP motor load 240 VAC
Number of Controllable Relays
12
Number of HVAC-control Relays (no metering)
2
Power Consumption
<20 W
Maximum Total Current
450 A
Warranty
10 years
Description
Value
WiFi Frequency Band
2.4 GHz
IP Addressing
DHCP, Static
Encryption
TLSv1.2
Description
Value
UL
UL916
Содержание PWRmanager