Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage.  No overload capability is available for this rating.  (All ratings in accordance with BS5514, 
ISO3046 and DIN6271).  * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.  Maximum power 
decreases about 3.5 percent for each 1,000 feet above sea level. Sound output ratings from certain points on the generator subject to change based on installation parameters.

SPECIFICATIONS

GENERATOR

Model 005873-1 (17 kW)

Rated Maximum Continuous Power Capacity (LP)

17,000 Watts* 

Rated Maximum Continuous Power Capacity (NG) 

16,000 Watts*

Rated Voltage

240 

Rated Maximum Continuous Load Current – 240 Volts

70.8 LP/66.6 NG

Total Harmonic Distortion

Less than 5%

Main Line Circuit Breaker

65 Amp

Phase

1

Number of Rotor Poles

2

Rated AC Frequency

60Hz

Power Factor

1

Battery Requirement (not included) 

Group 26R 12 Volts and 525 Cold-cranking Amperes Minimum

Unit Weight

455/210.9

Dimensions (L” x W” x H”)

48 x 25 x 29 (1218 x 638 x 732)

Sound output in dB(A) at 23 ft.  with generator operating at normal load

66

Sound output in dB(A) at 23 ft. with generator in Quiet-Test™ low speed exercise mode 

60

ENGINE

Model 005873-1 (17 kW)

Type of Engine

GENERAC OHVI V-TWIN

Number of Cylinders

2

Displacement

992cc

Cylinder Block

Aluminum w/Cast Iron Sleeve

Valve Arrangement

Overhead Valve

Ignition System

Solid-state w/Magneto

Governor System

Electronic

Compression Ratio

9.5:1

Starter

12 Vdc

Oil Capacity Including Filter

Approx. 1.9 Qts./1.8L

Operating RPM

3,600

Fuel Consumption
Natural Gas 

 

cu.ft./hr.

 

1/2 Load

 

Full Load

Liquid Propane

 

ft3/hr (gal/hr)

 

1/2 Load

 

Full Load

183
261

59 (1.61) [6.09]
94 (2.57) [9.73]

Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas
For Btu content, multiply ft

3

/hr x 2520 (LP) or ft

3

/hr x 1000 (NG)

CONTROLS

2-Line Plain Text LCD Display

Simple user interface for ease of operation.

Mode Switch

-Auto 

Automatic Start on Utility failure. 7 day exerciser.

-Off

Stops unit. Power is removed. Control and charger still operate.

-Manual/Test (start)

Start with starter control, unit stays on. If utility fails, transfer to load takes place.

Programmable start delay between 10-30 seconds

Standard

Engine Start Sequence

Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration).

Engine Warm-up

5 seconds

Engine Cool-Down

1 minute

Starter Lock-out

Starter cannot re-engage until 5 sec. after engine has stopped.

Smart Battery Charger

Standard

Automatic Voltage Regulation with Over and Under Voltage Protection

Standard

Automatic Low Oil Pressure Shutdown

Standard

Overspeed Shutdown

Standard, 72Hz

High Temperature Shutdown

Standard

Overcrank Protection

Standard

Safety Fuse

Standard

Failure to Transfer Protection

Standard

Low Battery Protection

Standard

50 Event Run Log

Standard

Future Set Capable Exerciser

Standard

Incorrect Wiring Protection

Standard

Internal Fault Protection

Standard

Common External Fault Capability

Standard

®

Содержание GUARDIAN SERIES

Страница 1: ... models It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque matching the surge loads to the engine Digital voltage regulation at 1 SINGLE SOURCE SERVICE RESPONSE from Generac s extensive dealer network provides parts and service know how for the entire unit from the engine to the smallest electronic component GENERAC TRANSF...

Страница 2: ...l Auto Off switch Utility voltage sensing Generator voltage sensing Utility interrupt delay Engine warm up Engine cool down Programmable seven day exerciser Smart battery charger Main Line Circuit Breaker Electronic governor Selects the operating mode Constantly monitors utility voltage setpoints 60 dropout 80 pick up of standard voltage Constantly monitors generator voltage to ensure the cleanest...

Страница 3: ...lve Ignition System Solid state w Magneto Governor System Electronic Compression Ratio 9 5 1 Starter 12 Vdc Oil Capacity Including Filter Approx 1 9 Qts 1 8L Operating RPM 3 600 Fuel Consumption Natural Gas cu ft hr 1 2 Load Full Load Liquid Propane ft3 hr gal hr 1 2 Load Full Load 183 261 59 1 61 6 09 94 2 57 9 73 Required fuel pressure to generator fuel inlet at all load ranges 5 to 7 inches of ...

Страница 4: ... 5 x 7 658 x 308 x 172 Total of Pre wired Circuits No 15A 120V No 20A 120V No 20A 240V No 40A 240V No 50A 240V 16 5 5 1 1 1 Circuit Breaker Protected Available RMS Symmetrical Fault Current 250 Volts 10 000 731 9 28 8 637 6 25 1 LEFT SIDE VIEW 642 25 3 76 2 3 0 PEA GRAVEL MINIMUM TRANSFER SWITCH 8KW 17KW IF SUPPLIED TRANSFER SWITCH 20KW IF SUPPLIED 1218 47 9 FRONT VIEW 1226 48 3 H2 H1 W1 W2 H2 H1 ...

Страница 5: ...he bottom the new air cooled generators This offers a sleek contoured appearance as well as offering protection from rodents and insects by covering the lifting holes located in the base 5703 Paint Kit Bisque Kit 5664 Scheduled Maintenance Kit Generac s scheduled maintenance kits provide all the hardware necessary to perform complete routine maintenance on a Generac automatic standby generator 592...

Отзывы: