FUEL SYSTEM

FUEL REQUIREMENTS

The standby generator may be equipped with one of 
the following fuel systems:

•  Natural gas fuel system
•  Propane vapor (PV) fuel system
The Manual Drawing Listing that is affixed to the 
unit includes the “Identification Code,” which may be 
used to identify the type of fuel system installed on 
the unit.

Recommended fuels should have a Btu content of at 
least 1,000 Btus per cubic foot for natural gas; or at 
least 2,520 Btus per cubic foot for LP gas. Ask the 
fuel supplier for the Btu content of the fuel.

Required fuel pressure for 

natural gas is 5 inches 

to 14 inches water column (0.18 to 0.5 psi); and 
for liquid propane, 5 inches to 14 inches of water 
column (0.18 to 0.5 psi).

NOTE:

Any piping used to connect the generator to the 
fuel supply should be of adequate size to ensure 
the fuel pressure NEVER drops below five inches 
water column for natural gas or 5 inches water 
column for propane vapor for all load ranges.

NOTE:

It is the responsibility of the installer to make sure 
that only the correct recommended fuel is sup-
plied to the generator fuel system. Thereafter, the 
owner/operator must make certain that only the 
proper fuel is supplied.

NATURAL GAS FUEL SYSTEM

Natural gas is supplied in its vapor state. In most 
cases, the gas distribution company provides piping 
from the main gas distribution line to the standby 
generator site. The following information applies to 
natural gas fuel systems.

•  Gas pressure in a building is usually regulated by 

national, state and local codes.

• To reduce gas pressure to a safe level before 

the gas enters a building, a primary regulator is 
needed. The natural gas supplier may or may not 
supply such a regulator.

•  It is the responsibility of the gas supplier to make 

sure sufficient gas pressure is available to operate 
the primary regulator.

• Gas pressure at the inlet to the fuel shutoff sole-

noid should not exceed approximately 14 inches 
water column (0.5 psi). Optimum pressure at the 
fuel shutoff solenoid is 11 inches water column 
(0.4 psi).

‹

‹

 PROPANE VAPOR WITHDRAWAL FUEL SYSTEM

This type of system utilizes the vapors formed above 
the liquid fuel in the supply tank. Approximately 10 
to 20 percent of the tank capacity is needed for fuel 
expansion from the liquid to the vapor state. The 
vapor withdrawal system is generally best suited for 
smaller engines that require less fuel. The installer 
should be aware of the following:

• The natural gas and LP gas systems are similar. 

However, the natural gas system delivers gas at a 
pressure of approximately five inches water col-
umn to the carburetor.

• When ambient temperatures are low and engine 

fuel consumption is high, the vapor withdrawal 
system may not function efficiently.

• Ambient temperatures around the supply tank 

must be high enough to sustain adequate vaporiza-
tion, or the system will not deliver the needed fuel 
volume.

•  In addition to the cooling effects of ambient air, the 

vaporization process itself provides an additional 
cooling effect.

LP FUEL SYSTEM

LP is supplied as a liquid in pressure tanks. It is 
usually made up of propane, butane, or a mixture of 
the two gases. Propane tends to vaporize readily even 
at temperatures as low as -20° F (-29° C). However, 
butane reverts to its liquid state when temperatures 
drop below 32° F (0° C).

LP in a liquid withdrawal system must be converted 
to its gaseous state before it is introduced into the 
engine carburetor. A vaporizer-converter is generally 
used to accomplish this. In such a converter, heated 
engine coolant is ported through the converter to 
provide the necessary heat for conversion of the fuel 
from a liquid to a gaseous state.

‹

‹

5-1

Standby Generator Sets

Fuel Systems

FuelSys001  Rev.

 0  08/05

Содержание Guardian 005324-1

Страница 1: ...of reliability Serial Number 1 6L 25kW Models 005324 1 005325 1 CAUTION ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION DEADLY EXHAUST FUMES OUTDOOR INSTALLATION ONLY Not inten...

Страница 2: ...Start up Checklist 8 2 Preparation for Start up 8 2 Start up Inspection 8 2 OPERATION 9 1 Generator Control and Operation 9 1 Operating Unit with Manual Transfer Switch 9 1 Engine Start up and Transfe...

Страница 3: ...e with the manufacturer s instructions and recommendations Following installation do nothing that might render the unit unsafe or in noncompliance with the aforementioned codes standards laws and regu...

Страница 4: ...will result in damage to the generator and may also result in injury or death to utility power workers due to backfeed of electrical energy Generators installed with an automatic transfer switch will...

Страница 5: ...tial fire hazard This symbol points out potential electrical shock hazard The operator is responsible for proper and safe use of the equipment The manufacturer strongly recom mends that the operator r...

Страница 6: ...is manual or to the data label affixed to the unit Generator Model and Serial Number This number is the key to numerous engineering and manufacturing details pertaining to your unit Always supply this...

Страница 7: ...result in an engine failure NOTE For temperatures below 32 F it is strongly recom mended to use the optional Cold Weather Start Kit part number listed in the Specification Section The oil grade for t...

Страница 8: ...g cranking and operating Should oil pressure drop below the 8 psi range switch contacts close and the engine shuts down The unit should not be restarted until oil is added and the AUTO OFF MANUAL swit...

Страница 9: ...sure sufficient gas pressure is available to operate the primary regulator Gas pressure at the inlet to the fuel shutoff sole noid should not exceed approximately 14 inches water column 0 5 psi Optim...

Страница 10: ...s Steady State Regulation 25 Adjustments Speed Selectable Engine Lubrication System Type of Oil Pump Gear Oil Filter Full Flow Cartridge Crankcase Oil Capacity 4 U S qts COOLING SYSTEM Type Closed Wat...

Страница 11: ...switch inside the control panel must be in the LP or NG position when switching to differ ent fuels Figure 6 2 Reconfigure the Fuel System NG FUEL SYSTEM LP FUEL SYSTEM Port 1 Port 2 FUEL HOSE BRASS H...

Страница 12: ...reaker ter minal is 240V The rated voltage between each circuit breaker terminal and the neutral point 00 is 120V Figure 7 1 Four lead Single phase Stator ALTERNATOR POWER WINDING CONNECTIONS 3 PHASE...

Страница 13: ...hours of operation Check the oil level in the generator gearbox if so equipped prior to initial use and at the intervals indicated by the Service Schedule The recom mended oil is SAE 90 gear lubricant...

Страница 14: ...control panel Move the AUTO OFF MANUAL switch to the MAN UAL position The engine should now crank and start Check voltage at the generator terminals For 3 phase units check phase rotation at the tran...

Страница 15: ...ansfer handle to its UTILITY NORMAL position with load circuits connected to the utility power supply Set the standby generator s main line circuit break er to its OFF or OPEN position Start the gener...

Страница 16: ...bstructed for contin ued proper operation This includes such obstruc tions as high grass weeds brush leaves and snow Without sufficient cooling and ventilating air flow the engine generator quickly ov...

Страница 17: ...cooling system See Maintenance Schedule Check hoses for damage deterioration leaks etc Correct any discrepancies found Check hose clamps for tightness CHECK ENGINE COOLANT LEVEL See Checking Fluid Le...

Страница 18: ...ngine and check for oil leaks CHANGING THE ENGINE AIR CLEANER To replace the engine air cleaner simply remove the air cleaner cover and replace the air filter making sure it is positioned properly bef...

Страница 19: ...hould be followed for inspection 1 Inspect the battery posts and cables for tightness and corrosion Tighten and clean as necessary 2 Check the battery fluid level of unsealed batteries and if necessar...

Страница 20: ...tery cable to prevent an over current condition from burning out sensitive control panel components and circuits Following all maintenance reverse these steps to insure the unit is returned to standby...

Страница 21: ...gas engine driven units Tighten connections as necessary 6 Check the air inlets and outlets for debris Clean as necessary 7 Check the battery electrolyte level if accessible Adjust as necessary 8 Chec...

Страница 22: ...d exercise the unit at full rated load use a load bank if the site load is not enough for at least 2 hours looking for leaks loose connections or components and abnormal operating conditions Correct a...

Страница 23: ...ded in SPECIFICATIONS Engine starts then shuts down 1 Engine oil level is low 1 Check oil and add oil as needed 2 Engine is overheated 2 Check cooling system for leaks 3 Defective Low Oil Pressure Swi...

Страница 24: ...Standby Generator Sets Notes...

Страница 25: ...Standby Generator Sets Notes...

Страница 26: ...Standby Generator Sets Notes...

Страница 27: ...Standby Generator Sets Notes...

Страница 28: ......

Страница 29: ...022237 1 WASHER LOCK 3 8 21 057329 1 LUG SLDLSS 350 6 X 13 32 AL CU 22 057073 1 JUNCTION BLOCK 3 8 16 23 023484J 1 BUSHING SNAP SB 2000 26 24 0E3257 15 SCREW HWHTF M6 1 0 X 16 25 0E7890 REF BRKT CB M...

Страница 30: ......

Страница 31: ...E FEBRUARY 2007 0G2926 1 STR 102 20 0AD1 CPL 2006 FOR UNITS BUILT AFTER FEBRUARY 2007 0G3682 1 STR 102 20 0GD1 CPL 2006 FOR UNITS BUILT AFTER FEBRUARY 2007 0G2826 1 ASSY STR 102 25AD1 2006 FOR UNITS B...

Страница 32: ......

Страница 33: ...4 0E4494 1 SWITCH RKR DPDT ON OFF ON 25 0F3215 1 DECAL CONTROL HSB 26 0F6305 2 SEAL COVER 3 18 X 12 7 X 382 27 0F6305A 1 SEAL COVER 3 18 X 12 7 X 283 28 0F5886 3 SCREW HHPM M5 0 8 X 12 29 051713 14 WA...

Страница 34: ......

Страница 35: ...RD FAN RH C1 23 0F7320 1 BLOCK OFF UPPER 24 0F1433 1 BRACKET 2 5L FORD WATER BOTTLE 25 076749 1 TANK COOLANT RECOVERY 26 048031C 2 CLAMP HOSE BAND 1 4 27 029032 1 HOSE 9 32 ID 43 LG 28 050275 3 DECAL...

Страница 36: ......

Страница 37: ...VDC 75 AH 26 7 050331A 1 BATTERY POST COVER RED 8 050331 1 BATTERY POST COVER BLK 9 038805J 1 CABLE BATTERY BLACK 1 X 30 00 10 038804N 1 CABLE BATTERY RED 1 X15 00 11 045771 REF NUT HEX M8 1 25 G8 YEL...

Страница 38: ......

Страница 39: ...5 16 ZINC 7 022129 12 WASHER LOCK M8 5 16 8 045771 4 NUT HEX M8 1 25 G8 YEL CHR 9 071956 4 WASHER FLAT M8 10 051730 4 SCREW HHC M8 1 25 X 60 G8 8 11 021991 1 EARTH STRAP 13 026850 1 WASHER SHAKEPROOF...

Страница 40: ......

Страница 41: ...0 X 10 G8 8 7 022097 5 WASHER LOCK M6 1 4 8 084543A 1 SCREW PHM M3 0 5 X 12MM 9 098783 1 LEVER STEPPER MOTOR 10 037398 2 NUT LOCK HEX 10 32 NYL INS 11 0E1326 1 ASSY CARBURETOR LINKAGE ROD 12 0A7106 1...

Страница 42: ......

Страница 43: ...EW HHC M8 1 25 X 35 G8 8 31 022129 4 WASHER LOCK M8 5 16 32 022145 3 WASHER FLAT 5 16 M8 ZINC 33 029333A 1 TIE WRAP UL 7 4 X 19 BLK 34 057821 3 SCREW HHC M8 1 25 X 40 G8 8 35 045771 3 NUT HEX M8 1 25...

Страница 44: ......

Страница 45: ...REW THROTTLE PIN STOP 1 35 0E1108 1 THROTTLE ARM REWORK 1 36 033138 1 SCREW HHM 10 32 X 5 8 1 37 022152 1 WASHER LOCK 10 1 38 0E0645 1 LEVER THROTTLE STOP 1 39 034339 1 BARBED EL 90 3 8 NPT X 5 8 40 0...

Страница 46: ......

Страница 47: ...JS 19 078115 20 WASHER SELF LOCKING DOME 20 0F3890B 2 RETAINER INSULATION 820 21 0F3890 4 RETAINER INSULATION 450 22 0F7365 2 INSULATION SIDE DOOR C1 23 0F7365B 1 INSULATION REAR DOOR C1 CPL 24 0F736...

Страница 48: ......

Страница 49: ...RAP 7 0C6119 1 BOLT U 5 16 18 X 2 1 4 8 036434 3 BOLT U 5 16 18 X 2 09 9 036449 3 SADDLE 2 INCH 10 022129 6 WASHER LOCK M8 5 16 11 022259 6 NUT HEX 5 16 18 STEEL 12 038750 1 SCREW HHC M6 1 0 X 30 G8 8...

Страница 50: ......

Страница 51: ......

Страница 52: ......

Страница 53: ......

Страница 54: ......

Страница 55: ......

Страница 56: ......

Страница 57: ......

Страница 58: ......

Страница 59: ......

Страница 60: ......

Страница 61: ......

Страница 62: ......

Страница 63: ......

Страница 64: ...aminated fuels oils coolants antifreeze or lack of proper fuels oils or coolants antifreeze 4 Units sold rated or used for Prime Power Trailer Mounted or Rental Unit applications as Generac Power Syst...

Отзывы: