ENGINE PROTECTIVE DEVICES

The standby generator may be required to operate for 
long periods of time without an operator on hand to 
monitor such engine conditions as coolant tempera-
ture, oil pressure or rpm. For that reason, the engine 
has several devices designed to protect it against 
potentially damaging conditions by automatically 
shutting down the unit when the oil pressure is too 
low, the coolant temperature is too high, the coolant 
level is too low, or the engine is running too fast.

NOTE:

Engine protective switches and sensors are men-
tioned here for the reader’s convenience. Also 
refer to the applicable control panel manual for 
additional automatic engine shutdown informa-
tion.

HIGH COOLANT TEMPERATURE SWITCH

This switches contacts close if the temperature should 
exceed approximately 140° C (284° F), initiating an 
engine shutdown. The generator will automatically 
restart and the LED will reset once the temperature 
has returned to a safe operating level.

LOW COOLANT LEVEL SENSOR

Should the engine coolant level drop below the level 
of the high coolant temperature switch, it is possible 
for the engine to overheat without automatic shut-
down. To prevent such overheating, the engine has a 
low coolant level sensor. If the level of engine coolant 
drops below the level of the low coolant level sensor, 
the engine automatically shuts down.

LOW OIL PRESSURE SWITCH

This switch has normally closed contacts that are 
held open by engine oil pressure during cranking and 
operating. Should oil pressure drop below the 8 psi 
range, switch contacts close, and the engine shuts 
down. The unit should not be restarted until oil is 
added, and the AUTO/OFF/MANUAL switch must be 
turned to OFF and then back to AUTO.

‹

‹

‹

OVERCRANK SHUTDOWN

After a prespecified duration of cranking, this func-
tion ends the cranking if the engine has failed to 
start. The overcrank LED will turn ON. Turn OFF the 
AUTO/OFF/MANUAL switch, then turn switch back to 
AUTO to reset the generator control board.

NOTE:

If the fault is not corrected, the overcrank feature 
will continue to activate.

Approximate Crank Cycle Times

• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
• 7 seconds OFF
•  Repeat for 45 seconds
  Approximately 90 seconds total.

OVERSPEED SHUTDOWN

A speed circuit controls engine cranking, start-up, 
operation and shutdown. Engine speed signals are 
delivered to the circuit board whenever the unit is 
running. Should the engine overspeed above a safe, 
preset value, the circuit board initiates an automatic 
engine shutdown. Contact the nearest Authorized 
Dealer if this failure occurs.

RPM SENSOR LOSS SHUTDOWN

If the speed signal to the control panel is lost, engine 
shutdown will occur.

DC FUSE

This fuse is located inside of the control panel. It 
protects the panel wiring and components from 
damaging overload. 

Always remove this fuse before 

commencing work on the generator.

 The unit will 

not start or crank if the fuse is blown. Replace the 
fuse with one of the same size, type, and rating. (See 
the exploded views and parts lists at the end of this 
manual for replacement part number.)

‹

‹

‹

‹

4-1

Standby Generator Sets

Engine Protective Devices

EngProt001  Rev.

 0  08/05

Содержание Guardian 005324-1

Страница 1: ...of reliability Serial Number 1 6L 25kW Models 005324 1 005325 1 CAUTION ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION DEADLY EXHAUST FUMES OUTDOOR INSTALLATION ONLY Not inten...

Страница 2: ...Start up Checklist 8 2 Preparation for Start up 8 2 Start up Inspection 8 2 OPERATION 9 1 Generator Control and Operation 9 1 Operating Unit with Manual Transfer Switch 9 1 Engine Start up and Transfe...

Страница 3: ...e with the manufacturer s instructions and recommendations Following installation do nothing that might render the unit unsafe or in noncompliance with the aforementioned codes standards laws and regu...

Страница 4: ...will result in damage to the generator and may also result in injury or death to utility power workers due to backfeed of electrical energy Generators installed with an automatic transfer switch will...

Страница 5: ...tial fire hazard This symbol points out potential electrical shock hazard The operator is responsible for proper and safe use of the equipment The manufacturer strongly recom mends that the operator r...

Страница 6: ...is manual or to the data label affixed to the unit Generator Model and Serial Number This number is the key to numerous engineering and manufacturing details pertaining to your unit Always supply this...

Страница 7: ...result in an engine failure NOTE For temperatures below 32 F it is strongly recom mended to use the optional Cold Weather Start Kit part number listed in the Specification Section The oil grade for t...

Страница 8: ...g cranking and operating Should oil pressure drop below the 8 psi range switch contacts close and the engine shuts down The unit should not be restarted until oil is added and the AUTO OFF MANUAL swit...

Страница 9: ...sure sufficient gas pressure is available to operate the primary regulator Gas pressure at the inlet to the fuel shutoff sole noid should not exceed approximately 14 inches water column 0 5 psi Optim...

Страница 10: ...s Steady State Regulation 25 Adjustments Speed Selectable Engine Lubrication System Type of Oil Pump Gear Oil Filter Full Flow Cartridge Crankcase Oil Capacity 4 U S qts COOLING SYSTEM Type Closed Wat...

Страница 11: ...switch inside the control panel must be in the LP or NG position when switching to differ ent fuels Figure 6 2 Reconfigure the Fuel System NG FUEL SYSTEM LP FUEL SYSTEM Port 1 Port 2 FUEL HOSE BRASS H...

Страница 12: ...reaker ter minal is 240V The rated voltage between each circuit breaker terminal and the neutral point 00 is 120V Figure 7 1 Four lead Single phase Stator ALTERNATOR POWER WINDING CONNECTIONS 3 PHASE...

Страница 13: ...hours of operation Check the oil level in the generator gearbox if so equipped prior to initial use and at the intervals indicated by the Service Schedule The recom mended oil is SAE 90 gear lubricant...

Страница 14: ...control panel Move the AUTO OFF MANUAL switch to the MAN UAL position The engine should now crank and start Check voltage at the generator terminals For 3 phase units check phase rotation at the tran...

Страница 15: ...ansfer handle to its UTILITY NORMAL position with load circuits connected to the utility power supply Set the standby generator s main line circuit break er to its OFF or OPEN position Start the gener...

Страница 16: ...bstructed for contin ued proper operation This includes such obstruc tions as high grass weeds brush leaves and snow Without sufficient cooling and ventilating air flow the engine generator quickly ov...

Страница 17: ...cooling system See Maintenance Schedule Check hoses for damage deterioration leaks etc Correct any discrepancies found Check hose clamps for tightness CHECK ENGINE COOLANT LEVEL See Checking Fluid Le...

Страница 18: ...ngine and check for oil leaks CHANGING THE ENGINE AIR CLEANER To replace the engine air cleaner simply remove the air cleaner cover and replace the air filter making sure it is positioned properly bef...

Страница 19: ...hould be followed for inspection 1 Inspect the battery posts and cables for tightness and corrosion Tighten and clean as necessary 2 Check the battery fluid level of unsealed batteries and if necessar...

Страница 20: ...tery cable to prevent an over current condition from burning out sensitive control panel components and circuits Following all maintenance reverse these steps to insure the unit is returned to standby...

Страница 21: ...gas engine driven units Tighten connections as necessary 6 Check the air inlets and outlets for debris Clean as necessary 7 Check the battery electrolyte level if accessible Adjust as necessary 8 Chec...

Страница 22: ...d exercise the unit at full rated load use a load bank if the site load is not enough for at least 2 hours looking for leaks loose connections or components and abnormal operating conditions Correct a...

Страница 23: ...ded in SPECIFICATIONS Engine starts then shuts down 1 Engine oil level is low 1 Check oil and add oil as needed 2 Engine is overheated 2 Check cooling system for leaks 3 Defective Low Oil Pressure Swi...

Страница 24: ...Standby Generator Sets Notes...

Страница 25: ...Standby Generator Sets Notes...

Страница 26: ...Standby Generator Sets Notes...

Страница 27: ...Standby Generator Sets Notes...

Страница 28: ......

Страница 29: ...022237 1 WASHER LOCK 3 8 21 057329 1 LUG SLDLSS 350 6 X 13 32 AL CU 22 057073 1 JUNCTION BLOCK 3 8 16 23 023484J 1 BUSHING SNAP SB 2000 26 24 0E3257 15 SCREW HWHTF M6 1 0 X 16 25 0E7890 REF BRKT CB M...

Страница 30: ......

Страница 31: ...E FEBRUARY 2007 0G2926 1 STR 102 20 0AD1 CPL 2006 FOR UNITS BUILT AFTER FEBRUARY 2007 0G3682 1 STR 102 20 0GD1 CPL 2006 FOR UNITS BUILT AFTER FEBRUARY 2007 0G2826 1 ASSY STR 102 25AD1 2006 FOR UNITS B...

Страница 32: ......

Страница 33: ...4 0E4494 1 SWITCH RKR DPDT ON OFF ON 25 0F3215 1 DECAL CONTROL HSB 26 0F6305 2 SEAL COVER 3 18 X 12 7 X 382 27 0F6305A 1 SEAL COVER 3 18 X 12 7 X 283 28 0F5886 3 SCREW HHPM M5 0 8 X 12 29 051713 14 WA...

Страница 34: ......

Страница 35: ...RD FAN RH C1 23 0F7320 1 BLOCK OFF UPPER 24 0F1433 1 BRACKET 2 5L FORD WATER BOTTLE 25 076749 1 TANK COOLANT RECOVERY 26 048031C 2 CLAMP HOSE BAND 1 4 27 029032 1 HOSE 9 32 ID 43 LG 28 050275 3 DECAL...

Страница 36: ......

Страница 37: ...VDC 75 AH 26 7 050331A 1 BATTERY POST COVER RED 8 050331 1 BATTERY POST COVER BLK 9 038805J 1 CABLE BATTERY BLACK 1 X 30 00 10 038804N 1 CABLE BATTERY RED 1 X15 00 11 045771 REF NUT HEX M8 1 25 G8 YEL...

Страница 38: ......

Страница 39: ...5 16 ZINC 7 022129 12 WASHER LOCK M8 5 16 8 045771 4 NUT HEX M8 1 25 G8 YEL CHR 9 071956 4 WASHER FLAT M8 10 051730 4 SCREW HHC M8 1 25 X 60 G8 8 11 021991 1 EARTH STRAP 13 026850 1 WASHER SHAKEPROOF...

Страница 40: ......

Страница 41: ...0 X 10 G8 8 7 022097 5 WASHER LOCK M6 1 4 8 084543A 1 SCREW PHM M3 0 5 X 12MM 9 098783 1 LEVER STEPPER MOTOR 10 037398 2 NUT LOCK HEX 10 32 NYL INS 11 0E1326 1 ASSY CARBURETOR LINKAGE ROD 12 0A7106 1...

Страница 42: ......

Страница 43: ...EW HHC M8 1 25 X 35 G8 8 31 022129 4 WASHER LOCK M8 5 16 32 022145 3 WASHER FLAT 5 16 M8 ZINC 33 029333A 1 TIE WRAP UL 7 4 X 19 BLK 34 057821 3 SCREW HHC M8 1 25 X 40 G8 8 35 045771 3 NUT HEX M8 1 25...

Страница 44: ......

Страница 45: ...REW THROTTLE PIN STOP 1 35 0E1108 1 THROTTLE ARM REWORK 1 36 033138 1 SCREW HHM 10 32 X 5 8 1 37 022152 1 WASHER LOCK 10 1 38 0E0645 1 LEVER THROTTLE STOP 1 39 034339 1 BARBED EL 90 3 8 NPT X 5 8 40 0...

Страница 46: ......

Страница 47: ...JS 19 078115 20 WASHER SELF LOCKING DOME 20 0F3890B 2 RETAINER INSULATION 820 21 0F3890 4 RETAINER INSULATION 450 22 0F7365 2 INSULATION SIDE DOOR C1 23 0F7365B 1 INSULATION REAR DOOR C1 CPL 24 0F736...

Страница 48: ......

Страница 49: ...RAP 7 0C6119 1 BOLT U 5 16 18 X 2 1 4 8 036434 3 BOLT U 5 16 18 X 2 09 9 036449 3 SADDLE 2 INCH 10 022129 6 WASHER LOCK M8 5 16 11 022259 6 NUT HEX 5 16 18 STEEL 12 038750 1 SCREW HHC M6 1 0 X 30 G8 8...

Страница 50: ......

Страница 51: ......

Страница 52: ......

Страница 53: ......

Страница 54: ......

Страница 55: ......

Страница 56: ......

Страница 57: ......

Страница 58: ......

Страница 59: ......

Страница 60: ......

Страница 61: ......

Страница 62: ......

Страница 63: ......

Страница 64: ...aminated fuels oils coolants antifreeze or lack of proper fuels oils or coolants antifreeze 4 Units sold rated or used for Prime Power Trailer Mounted or Rental Unit applications as Generac Power Syst...

Отзывы: