Installation, Tests, and Troubleshooting
12
Owner’s/Installation Manual for SMM
Troubleshooting
See
for troubleshooting problems, causes, and corrections.
Table 3-2. Troubleshooting
Problem
Cause
Correction
Load not powered; LED is OFF
Circuit breaker disabled.
Enable circuit breaker.
Load not powered; LED is OFF
MLCB disabled and generator OFF.
Enable MLCB if utility is present or verify generator
operation if outage.
Load not powered; LED flashing
1 second interval
Generator power just applied to unit.
Utility power just applied to unit.
Generator was overloaded and shed
occurred.
Wait five minutes plus the priority time delay (see
Load not powered; LED flashing
3 second interval
This load overloaded the generator
while attempting recovery from a shed.
It is in a 30 minute lockout wait period.
Wait 30 minutes from lockout for unit to attempt to re-
apply load.
Review all loads enabled in household. The genera-
tor may experience another overload condition when
this load is enabled. Disable some loads to prevent
generator overload from recurring.
Load not powered; LED flashing
6 second interval
The lockout switch is enabled and the
unit is on generator power.
During installation, it was determined that this load
will be disabled during generator operation to prevent
generator overload. Contact IASD for details.
Содержание G007006-0
Страница 4: ...iv Owner s Installation Manual for SMM This page intentionally left blank ...
Страница 6: ...Introduction and Safety 2 Owner s Installation Manual for SMM This page intentionally left blank ...
Страница 12: ...General Information and Setup 8 Owner s Installation Manual for SMM This page intentionally left blank ...
Страница 19: ......