Troubleshooting
46
Owner’s Manual for Stationary Diesel Generators
6.2 — Controller Troubleshooting
Active Alarm
Problem
Solution
NOT ACTIVATED
Unit will not start in AUTO with utility loss.
Refer to activation section in Owner’s Manual.
NONE
Unit running in AUTO but no power in house.
Check MLCB. Contact servicing dealer if MLCB is in the ON
position.
NONE
Unit will not start in AUTO with utility loss.
Check screen for start delay countdown. If the start up delay is
greater than expected, contact servicing dealer to adjust from 2
to 1500 seconds.
HIGH
TEMPERATURE
Unit shuts down during operation.
Check ventilation around the intake, exhaust and rear of gener-
ator. Contact serving dealer if no obstruction is found.
OVERLOAD
Unit shuts down during operation.
Clear alarm and remove household loads from the generator.
Put back in AUTO and restart.
RPM SENSE LOSS
Unit was running and shuts down, attempts to
restart.
Clear alarm and remove household loads from the generator.
Put back in AUTO and restart. If problem returns, contact servic-
ing dealer to investigate possible fuel issue.
LOW OIL
PRESSURE
Unit will not start in AUTO with utility loss.
Check oil level. Add oil per Owner’s Manual. Contact servicing
dealer if oil level is correct.
RPM SENSE LOSS
Unit will not start in AUTO with utility loss.
Clear alarm. From the MAIN menu on the control panel, navi-
gate to the BATTERY MENU. Contact servicing dealer if battery
is GOOD. Replace battery If CHECK BATTERY is displayed.
OVERCRANK
Unit will not start in AUTO with utility loss.
Clear alarm. Attempt to start the unit in MANUAL. If it does not
start or starts and runs rough, contact servicing dealer.
FUSE PROBLEM
Unit will not start in AUTO with utility loss.
Check ATO 7.5 amp fuse. Replace with same type fuse if bad.
Contact servicing dealer if fuse is good.
OVERSPEED
Unit will not start in AUTO with utility loss.
Contact servicing dealer.
UNDER
VOLTAGE
Unit will not start in AUTO with utility loss.
Contact servicing dealer.
UNDERSPEED
Unit will not start in AUTO with utility loss.
Contact servicing dealer.
MISWIRE
Unit will not start in AUTO with utility loss.
Contact servicing dealer.
OVERVOLTAGE
Unit will not start in AUTO with utility loss.
Contact servicing dealer.
LOW BATTERY
Warning active.
Clear alarm. From the MAIN menu on the control panel, navi-
gate to the BATTERY MENU. Contact servicing dealer if battery
is GOOD. Replace battery If CHECK BATTERY is displayed.
BATTERY PROBLEM
Warning active.
Contact servicing dealer.
CHARGER WARNING
Warning active.
Contact servicing dealer
SERVICE SCHEDULE A
Warning active.
Perform SERVICE SCHEDULE A maintenance; press ENTER
to clear.
SERVICE SCHEDULE B
Warning active.
Perform SERVICE SCHEDULE B maintenance; press ENTER
to clear.
SERVICE SCHEDULE C
Warning active.
Perform SERVICE SCHEDULE C maintenance; press ENTER
to clear.
Содержание 66781
Страница 10: ...Safety 4 Owner s Manual for Stationary Diesel Generators This page intentionally left blank ...
Страница 16: ...Specifications 10 Owner s Manual for Stationary Diesel Generators This page intentionally left blank ...
Страница 24: ...Activation and Startup 18 Owner s Manual for Stationary Diesel Generators This page intentionally left blank ...
Страница 32: ...Operation 26 Owner s Manual for Stationary Diesel Generators This page intentionally left blank ...
Страница 50: ...Maintenance 44 Owner s Manual for Stationary Diesel Generators This page intentionally left blank ...
Страница 56: ...Troubleshooting 50 Owner s Manual for Stationary Diesel Generators This page intentionally left blank ...
Страница 57: ...Troubleshooting Owner s Manual for Stationary Diesel Generators 51 NOTES ...
Страница 58: ...Troubleshooting 52 Owner s Manual for Stationary Diesel Generators NOTES ...
Страница 59: ......