![Generac Power Systems 66781 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/generac-power-systems/66781/66781_owners-manual_2209488041.webp)
Maintenance
Owner’s Manual for Stationary Diesel Generators
35
5.7.7— Check Battery Condition/Fluid Level
5.7.7.1— Check Condition and Clean
NOTE: On 2.3L models, remove ten screws to release louvered air intake panel on left side of enclosure.
1.
Verify that top of battery is clean and dry. Dirt and electro-
lyte on top of the battery can cause battery to self-dis-
charge. Clean battery top with a solution of baking soda
(sodium bicarbonate) and water (5 teaspoons baking
soda per quart or liter of water). When solution stops bub-
bling, rinse off the battery with clean water.
2.
Clean cable clamps and battery terminals using a wire
brush or sandpaper to remove any oxidation.
3.
Inspect battery screws, clamps and cables for breakage,
loose connections and corrosion. Tighten and clean as
necessary.
4.
Check the battery posts for melting or damage caused by
over tightening.
5.
Inspect battery for discoloration, raised top or a warped
or distorted case, which might indicate that the battery
has been frozen, overheated or overcharged.
6.
Inspect the battery case for cracks or leaks.
7.
Check the battery fluid level of unsealed batteries. See
Subsection 5.7.7.2—Check Fluid Level.
8.
Check the battery state of charge. See Subsection
5.7.7.3—Check State of Charge.
9.
Replace battery if necessary. See Subsection 5.7.7.4—
Battery Replacement.
NOTE: On 2.3L models, start ten screws to install louvered
air intake panel. Alternately tighten screws to 90 in-lbs (10
N-m) using a crosswise pattern.
5.7.7.2— Check Fluid Level
Check the fluid level of unsealed batteries. If necessary, fill with
distilled water only. DO NOT use tap water.
5.7.7.3— Check State of Charge
Check the state of charge using a Digital Multimeter. Recharge and retest if state of charge is below manufacturer's
recommendations. Replace battery if necessary.
5.7.7.4— Battery Replacement
Removal
Always disconnect the negative battery cable first. If the positive cable should contact ground with the
negative cable installed, the resulting sparks may cause a battery explosion which could result in seri-
ous injury.
1.
Remove battery negative cable (black) from battery negative (-) terminal.
2.
Remove battery positive cable (red) from battery positive (+) terminal.
3.
Install rubber protective cover over battery positive (+) terminal.
4.
Loosen two screws with nylon washers to release battery hold-down clamp from battery tray.
5.
Grasp battery strap next to battery positive (+) terminal, and lift battery.
6.
When battery tilts sideways, remove from opening.
7.
Remove rubber protective cover from battery positive (+) terminal.
Figure 5-11. Battery Cable Connections
Battery
Red Lead
From Starter
Black Lead
To Frame
$
Содержание 66781
Страница 10: ...Safety 4 Owner s Manual for Stationary Diesel Generators This page intentionally left blank ...
Страница 16: ...Specifications 10 Owner s Manual for Stationary Diesel Generators This page intentionally left blank ...
Страница 24: ...Activation and Startup 18 Owner s Manual for Stationary Diesel Generators This page intentionally left blank ...
Страница 32: ...Operation 26 Owner s Manual for Stationary Diesel Generators This page intentionally left blank ...
Страница 50: ...Maintenance 44 Owner s Manual for Stationary Diesel Generators This page intentionally left blank ...
Страница 56: ...Troubleshooting 50 Owner s Manual for Stationary Diesel Generators This page intentionally left blank ...
Страница 57: ...Troubleshooting Owner s Manual for Stationary Diesel Generators 51 NOTES ...
Страница 58: ...Troubleshooting 52 Owner s Manual for Stationary Diesel Generators NOTES ...
Страница 59: ......