background image

Owner’s Manual for 5.6 kVA PowerPact™

19

Changing the Oil

1.

Start the engine by pressing the MANUAL button
on the control panel and allow the engine to run
until it is thoroughly warmed up. Then, press the
Control Panel OFF button to shut down the engine.

2.

A few minutes after the engine shuts OFF, when it
has cooled slightly, remove the enclosure top lid by
unscrewing the fasteners, and lift the front panel off.

3.

Remove the battery access panel (A) by loosening
the two hex head screws. See 

Figure 4-3

.

4.

Disconnect the battery and remove the fuse.

5.

Pull the oil drain hose (B) free of its retaining clip
(C). See 

Figure 4-3

.

6.

Remove the cap from the hose and direct the hose
into a suitable container.

7.

Unscrew the drain hose cap and allow engine oil to
drain. Remove dipstick/ fill plug to permit oil to
drain faster. For proper drainage, drain the oil into
a pan placed at a lower level than the engine.

Figure 4-3.  Oil Drain Location

8.

After the oil has drained, replace the cap onto the
end of the oil drain hose. Reposition and secure
the hose with the retaining clip.

9.

Refill the engine with the proper recommended oil.
For recommended oil, see 

Figure 4-2

.

10.

Connect the battery, secure the battery access
panel, insert the fuse, and switch the unit to
MANUAL.

11.

Start the engine, run for one minute, and check for
leaks.

12.

Shutdown the engine and check the oil level. Add
oil as needed. DO NOT OVERFILL.

13.

Insert dipstick/fill cap.

14.

Press the Control Panel AUTO button.

15.

Dispose of the used oil and filter at a proper
collection center.

Changing the Engine Air Cleaner

1.

With the generator shut down, remove the top lid.

2.

See 

Figure 4-4

. Disengage the wire clip (A) and

remove the air cleaner access cover (B).

Figure 4-4.  Air Filter Location

3.

Remove the old air filter (C) and discard.

4.

Thoroughly clean the air cleaner enclosure of any
dust or debris while ensuring that none of the
debris falls in to the engine intake.

5.

Install a new air filter.

6.

Install the air cleaner cover and engage the wire
clip.

7.

Install the enclosure top lid. Tighten fasteners
securely.

8.

Place generator in AUTO.

Spark Plug

Check the spark plug gap and replace the spark plug as
necessary:

1.

With the generator shut down, remove the top lid.

2.

Clean the area around the base of the spark plug
to keep dirt and debris out of the engine.

3.

Gently pull the spark plug boot off of the spark
plug.

4.

Remove the spark plug and check the condition.
Install a new plug if the old plug is worn or if reuse
is questionable.

5.

Clean the plug by scraping or washing with a wire
brush and commercial solvent. Do not blast the
plug to clean.

6.

See

 

Figure 4-5

. Check the spark plug gap using a

wire feeler gauge. The gap should measure 0.030
in (0.76 mm). If the gap is out of specification,
replace the spark plug. See Section 2—

Replacement Parts

.

001115

B

A

C

001070

A

B

C

Содержание 5.6 kVA PowerPact

Страница 1: ...ur le fran ais visiter http www generac com service support product support lookup http www generac com service support product support lookup Register your Generac product at WWW GENERAC COM 1 888 GE...

Страница 2: ...iodically by an Independent Authorized Service Dealer Normal maintenance service and replacement of parts are the responsibility of the owner operator and as such are not considered defects in materia...

Страница 3: ...fer to Generator Power Source 11 Transfer Back to Utility Power Source 12 Automatic Transfer Operation 12 Automatic Sequence of Operation 13 Utility Failure 13 Cranking 13 Cold Smart Start 13 Load Tra...

Страница 4: ...Table of Contents 2 Owner s Manual for 5 6 kVA PowerPact This page intentionally left blank...

Страница 5: ...ner s Manual and thoroughly understand all instructions before using this equipment The manufacturer also strongly recommends instructing other users to properly start and operate the unit This prepar...

Страница 6: ...death or serious injury 000182 WARNING 000155 WARNING Only a trained and licensed electrician should perform wiring and connections to unit Failure to follow proper installation requirements could res...

Страница 7: ...rocution Verify electrical system is properly grounded before applying power Failure to do so will result in death or serious injury 000188 DANGER Electrocution Do not wear jewelry while working on th...

Страница 8: ...equipment required when working with with a live electrical system Failure to use 000147 WARNING Risk of Fire Unit must be positioned in a manner that prevents combustible material accumulation undern...

Страница 9: ...ngine 5 6 kVA Unit A Controller Lid F Control Panel K Air Box B Top Lid G Data Label L Spark Plug C Customer Connection Box H Battery Access Panel M Exhaust Enclosure D Front Panel I Oil Drain Hose N...

Страница 10: ...e engine specifications section These generators are rated in accordance with UL 2200 Safety Standard for Stationary Engine Generator Assemblies and CSA C22 2 No 100 04 Standard for Motors and Generat...

Страница 11: ...able fuel source during installation Recommended fuels should have a BTU content of at least 1000 Btus per cubic foot 37 26 megajoules per cubic meter for natural gas or at least 2500 BTUs per cubic f...

Страница 12: ...ecommended in areas where temperatures fall below 32 F 0 C Scheduled Maintenance Kit Includes all pieces necessary to perform maintenance on the generator along with oil recommendations Touch Up Paint...

Страница 13: ...IVE cable last Controller Lid To open or close the controller lid 1 See view A in Figure 3 1 Lift lid from bottom to open Lid will lock in place when raised 2 See view B in Figure 3 1 Pull raised lid...

Страница 14: ...AUTO LED will flash 001052 A B C Button Description of Operation AUTO GREEN Selecting this button activates fully automatic system operation It also allows the unit to automatically start and exercis...

Страница 15: ...w exercise time to take place The exercise timer does not correct for daylight savings time NOTE The exerciser will only work in the AUTO mode and will default to exercise weekly at the time the Contr...

Страница 16: ...ILITY power source voltage is available to transfer switch terminal lugs N1 and N2 3 Press the AUTO button on the control panel interface 4 Set the main circuit breaker Generator Disconnect to the ON...

Страница 17: ...rests Cold Smart Start The Cold Smart Start feature enables the generator to monitor ambient temperature The warm up delay will be adjusted based on prevailing conditions On a startup in AUTO mode if...

Страница 18: ...14 Owner s Manual for 5 6 kVA PowerPact This page intentionally left blank...

Страница 19: ...ons critical maintenance must be performed as scheduled in order for the Emissions Warranty to be valid Emissions critical maintenance consists of servicing the air filter and spark plugs in accordanc...

Страница 20: ...X 6 M or 100 hours inspect 1 Y or 300 hours change Valve clearance X 1 Y or 300 hours General condition Vibration noise leakage X M Contact the nearest Independent Authorized Service Dealer for assis...

Страница 21: ...Manual for 5 6 kVA PowerPact 17 Maintenance Log Battery inspection and charge check Dates Performed Oil oil filter air filter and spark plug replacement Dates Performed Valve Adjustment Dates Performe...

Страница 22: ...esidence Engine Oil Recommendations To maintain the product warranty the engine oil should be serviced in accordance with the recommendations of this manual For your convenience Generac Maintenance Ki...

Страница 23: ...leaks 12 Shutdown the engine and check the oil level Add oil as needed DO NOT OVERFILL 13 Insert dipstick fill cap 14 Press the Control Panel AUTO button 15 Dispose of the used oil and filter at a pro...

Страница 24: ...alve stem D with a feeler gauge E 8 If valve clearance is 0 002 0 004 in 0 05 0 1 mm adjustment is not needed Adjust Valve Clearance See Figure 4 6 1 The engine should be cool before adjustment 2 Remo...

Страница 25: ...area Discharge static electricity from the body before touching the battery by first touching a grounded metal surface Always recycle batteries in accordance with local laws and regulations Contact yo...

Страница 26: ...dry room on a wooden board 12 Clean and wipe down the entire generator Return to Service To return the unit to service after storage 1 Verify utility power is OFF 2 Check the tag on the engine for oil...

Страница 27: ...re gap or replace plug s 3 Confirm fuel pressure to regulator is 10 12 in water column 19 22 mm mercury for LP and 5 7 in water column 9 13 mm mercury for natural gas 4 Turn fuel conversion valve to...

Страница 28: ...24 Owner s Manual for 5 6 kVA PowerPact This page intentionally left blank...