40-400A (480/600Vac) ATC-300+ 3-Postion
Contactor Based Transfer Switch
Table 6. Setpoint Possibilities
SETPOINT
SETPOINT UNITS
DESCRIPTION
RANGE
FACTORY
DEFAULT
New Password
Four Digits
Set New Password
0000 to 9999
0300
TDES
Minutes: Seconds
Time Delay Engine Start
0 to 120 seconds
0:03
TDNE
Minutes: Seconds
Time Delay Normal to Emergency
0 to 1800 seconds
0:00
TDEN
Minutes: Seconds
Time Delay Emergency to Normal
0 to 1800 seconds
5:00
TDEC
Minutes: Seconds
Time Delay Engine Cool-off
0 to 1800 seconds
5:00
NOM FREQ
Hertz
Nominal Frequency
50 or 60 Hz
As ordered
NOM VOLTS
Volts
Nominal Voltage
120 to 600 volts
As ordered
S1 UV DROP
Volts
Source 1 Undervoltage Dropout Range:
Contactor Style ATS (2-position/3-position)
78 to 97% of Nominal System Voltage
85%
S2 UV DROP
Volts
Source 2 Undervoltage Dropout Range:
Contactor Style ATS (2-position/3-position)
78 to 97% of Nominal System Voltage
85%
S1 UV PICK
Volts
Source 1 Undervoltage Pickup Range:
Contactor Style ATS (2-position/3-position)
(D2%) to 99% of Nominal System Voltage
90%
S2 UV PICK
Volts
Source 2 Undervoltage Pickup Range:
Contactor Style ATS (2-position/3-position)
(D2%) to 99% of Nominal System Voltage
90%
S1 OV DROP
Volts
Source 1 Overvoltage Dropout Range:
Contactor Style ATS (2-position/3-position)
105 to 110% of Nominal System Voltage
110%
S2 OV DROP
Volts
Source 2 Overvoltage Dropout Range:
Contactor Style ATS (2-position/3-position)
105 to 110% of Nominal System Voltage
110%
S1 OV PICK
Volts
Source 1 Overvoltage Pickup Range:
Contactor Style ATS (2-position/3-position)
103% to (Dropout -2%) of Nominal System Voltage
105%
S2 OV PICK
Volts
Source 2 Overvoltage Pickup Range:
Contactor Style ATS (2-position/3-position)
103% to (Dropout -2%) of Nominal System Voltage
105%
S1 UF DROP
Hertz
Source 1 Underfrequency Dropout Range:
Contactor Style ATS (2-position/3-position)
90 to 97% of Nominal System Frequency
90%
S2 UF DROP
Hertz
Source 2 Underfrequency Dropout Range:
Contactor Style ATS (2-position/3-position)
90 to 97% of Nominal System Frequency
90%
S1 UF PICK
Hertz
Source 1 Underfrequency Pickup Range:
Contactor Style ATS (2-position/3-position)
(D1 Hz) to 99% of Nominal System Frequency
95%
S2 UF PICK
Hertz
Source 2 Underfrequency Pickup Range:
Contactor Style ATS (2-position/3-position)
(D1 Hz) to 99% of Nominal System Frequency
95%
S1 OF DROP
Hertz
Source 1 Overfrequency Dropout Range:
Contactor Style ATS (2-position/3-position)
103 to 105% of Nominal System Frequency
105%
S2 OF DROP
Hertz
Source 2 Overfrequency Dropout Range:
Contactor Style ATS (2-position/3-position)
103 to 105% of Nominal System Frequency
105%
S1 OF PICK
Hertz
Source 1 Overfrequency Pickup Range:
Contactor Style ATS (2-position/3-position)
101% to (Dropout -1 Hz) of Nominal System Frequency
102%
S2 OF PICK
Hertz
Source 2 Overfrequency Pickup Range:
Contactor Style ATS (2-position/3-position)
101% to (Dropout -1 Hz) of Nominal System Frequency
102%
TDN
Minutes: Seconds
Time Delay Neutral
0 to 120 seconds
0:00
BAUD RATE
Modbus Baud Rate
9600 or 19200
9600
ADDRESS
Modbus Address
1 to 247
1
PLANT EXER
Days
Plant Exerciser Programming
OFF, DAILY, 7-DAY, 14-DAY or 28 DAY
OFF
PE LOAD XFR
Plant Exerciser Load Transfer
0 or 1 (1 = yes)
0