Generac Power Systems 40-400A Скачать руководство пользователя страница 11

IB01602078E

For more information visit: www.generac.com

Instruction Booklet

Effective: September 2011

Page

 

11

40-400A (480/600Vac) ATC-300+ 3-Postion 

Contactor Based Transfer Switch

23K. Plant Exerciser Selectable – Disabled/1/7/14/28 Day Inter-

val

This feature provides for automatic test operation of the 

generator.  Available test cycles are daily, 7, 14, or 28 

days with duration equal to the programmed engine test 

time.

Programmable setpoints allow for selection of three test 

cycles:

Engine Start/Run Only (No Load);

Exercise with Load Transfer; or

Disabled

This is a “Failsafe” operation.

26.

Source 1 - Monitoring and Protection

This feature provides Source 1 monitoring and protection 

functions.  If the Source 1 power supply fails, then the 

Automatic Transfer Controller will begin the sequence of 

operations necessary to transfer the load circuit to the 

Source 2 power supply.  All Feature 26 monitoring and 

protection functions are Failsafe operations.

26D. Go to Source 2

This feature provides the capability for an external contact 

opening to initiate a load circuit transfer to the Source 2 

power source.  This includes starting the engine/generator, 

performing the programmed time delays, and the transfer 

operation.  Re-transfer will occur when the external con-

tact is closed or under a Failsafe condition.  

26H. Phase Reversal Protection

For a 3-phase wye source, this feature monitors the phase 

sequence of the sources.  If a source does not have the 

same ABC or CBA sequence as the phase reversal set-

point, the source will be considered “Unavailable”.

For a 3-phase delta source, this feature should be turned 

off via the PHASE REV setpoint.

26J. All Phase Undervoltage and Underfrequency Protection

Adjustable Undervoltage:

Dropout: 78 - 97% of nominal

Pickup: (D2%) to 99% of nominal

Adjustable Underfrequency:

Dropout: 90 - 97% of nominal

Pickup: (D1Hz) to 99% of nominal

26K. All Phase Overvoltage/Overfrequency

Adjustable Overvoltage:

Dropout: 105 - 110% of nominal

Pickup:103% to (Dropout –2%) of nominal

Adjustable Overfrequency:

Dropout: 103 - 105% of nominal

Pickup: 101% to (Dropout -1Hz) of nominal

26L. Source 1 3-Phase Voltage Unbalance

.For a 3-phase wye source, this feature monitors phase 

voltage ratios.  Voltage unbalance (%) is calculated as the 

difference between the maximum and minimum phase 

voltage, divided by the minimum phase voltage.  User-

selectable setpoints are available for dropout and pickup 

unbalance settings (minimum 2% differential).  Dropout is 

adjustable from 5 to 20%.  Pickup is adjustable from 3 to 

(Dropout –2%)).  A setpoint for user-selectable time delay 

from 10 to 30 seconds is provided.  The factory default 

setpoints are: 5% dropout, 3% pickup, and 30 seconds 

time delay.  A user-selectable setpoint for enable and dis-

able is also provided.

When an unbalance condition is detected on Source 1, the 

Unbalance Timer (TD UNBAL) starts timing.  After TD 

UNBAL times out, Source 1 is declared “failed”.

For a 3-phase delta source, this feature should be turned 

off via the VOLT UNBAL setpoint.

29.

Alternate Transfer Modes of Operation

Provides standard or optional transfer modes, mode selec-

tion devices, and operational methods for ATSs.

29J. Type of Operation (MANTR) Operation (new feature)

This feature provides for a selection between an automatic 

transfer and re-transfer mode or a manual pushbutton re-

transfer to Normal from the Emergency Source mode. If 

this option is not selected the factory default selection is 

automatic.

32.

Delayed Transition Transfer Modes for Open Transition 

Transfer Switches

This feature provides delayed transition transfer modes 

for an open transition transfer switch.  Often used in sys-

tems with inductive loads, a delayed transition transfer 

switch may prevent or reduce in-rush currents due to out 

of phase switching of inductive loads.

32A. Time Delay Neutral

This feature provides a time delay in the neutral position 

during the transfer and re-transfer operations during 

which both Source 1 and Source 2 are disconnected from 

the load circuit.  The time delay is programmable and is 

the same for both transfer and re-transfer operations.

Adjustable 0 - 120 Seconds

35.

Pre-Transfer Signal

This feature provides a signal to a remote device prior to a 

re-transfer operation.  It provides one Form “C” contact 

(NO/NC) for interface with other equipment (typically ele-

vator controls).  The contacts close/open on a timed basis 

prior to transfer in either direction.  After TDNE/TDEN 

times out, this relay closes and the Pre-transfer Timer 

(TPRE) starts timing.  After the TPRE times out, the trans-

fer proceeds by starting the TDN timer if enabled.  The 

pre-transfer relay opens after the transfer is complete.

Adjustable 0 - 120 Seconds

35A. Pre-Transfer Signal with 1 N.O. and 1 N.C. Contacts

This feature provides pre-transfer signal and includes 1 

N.O. and 1N.C. contacts.

Содержание 40-400A

Страница 1: ...sfer Switch Instruction Booklet Description Page Introduction 2 Receiving Handling and Storage 6 Equipment Description 7 Installation and Wiring 15 Operation 21 Testing and Problem Solving 22 Adjustme...

Страница 2: ...guide for authorized and qualified personnel only Please refer to the specific WARNING and CAUTION in Section 1 1 2 before proceeding If further infor mation is required by the purchaser regarding a...

Страница 3: ...ransfers back and initiates generator shutdown In the event the Source 1 power source fails and the Source 2 power source does not appear the ATS remains connected to the Source 1 power source until t...

Страница 4: ...ber Identification Transfer switch equipment catalog numbers provide a significant amount of relevant information that pertains to a particular piece of equipment The Catalog Number Identification Tab...

Страница 5: ...fined as a change of the load connection from the Source 2 to the Source 1 Source 1 Source 1 is the primary source normal source normal power source or normal Source 2 Source 2 is the secondary source...

Страница 6: ...y for installation Once the top packaging is removed from the shipment the enclosure door can be opened A plastic bag of documents will be found in the enclosure usually attached to the inside of the...

Страница 7: ...corporates a power contactor The main contacts connect and disconnect the load to and from the different power sources The power contactor is mechanically and electrically interlocked to prevent the t...

Страница 8: ...are of the controller contain the intelligence supervisory circuits that constantly moni tor the condition of the power sources It provides the intelli gence necessary for the operation of the ATS Fig...

Страница 9: ...gins when Source 1 becomes available If Source 2 fails during timing then re transfer is immediate overriding the time delay Adjustable 0 1800 Seconds 4 Time Delay for Engine Cool down TDEC This featu...

Страница 10: ...Time Delay Bypass Pushbutton This feature provides a way by pushing the Help and Step pushbutton simultaneously to bypass the TDNE Feature 1 and or TDEN Feature 2 time delays The Time Delay Bypass fun...

Страница 11: ...ge divided by the minimum phase voltage User selectable setpoints are available for dropout and pickup unbalance settings minimum 2 differential Dropout is adjustable from 5 to 20 Pickup is adjustable...

Страница 12: ...ntenance Selector Switch MSS Marked OFF ON This feature provides selector switch disconnection of control to transfer thus allowing testing of the transfer switch control logic circuitry with out init...

Страница 13: ...s fer switch logic controllers and or associated device pan els These covers function with Generac s ATC series logic controllers and device panels The covers are designed for NEMA 1 3R 4X and 12 appl...

Страница 14: ...ted in Table 3 is listed for application by UL and ULC In addition Generac ATSs are listed in File E38116 by Underwriters Labora tories Inc under Standard UL 1008 This standard covers requirements for...

Страница 15: ...ffers optional enclosure designs that can be used in special environments If there are any doubts as to a location s suitability discuss them with your Generac representa tive Check to make certain th...

Страница 16: ...Mounting Surface Step 6 Double check to ensure that all packing and shipping materials have been removed 4 4 Power Cable Connections WARNING POWER CONDUCTORS MAY HAVE VOLTAGE PRESENT THAT CAN CAUSE S...

Страница 17: ...ned in Sec tion 6 to verify that the equipment is installed and operating properly 4 6 Engine Start Connection The engine control contact connections are located on the logic panel of the ATS Connect...

Страница 18: ...VDC Source 2 Closed 32 VDC Lockout 32 VDC Go To Source 2 32 VDC Monitor Mode Control Inputs 8 0 in 6 5 in 3 4 1 2 7 8 5 6 Output Relays Control Inputs J8 K4 NO K4Com K3 NO K3 Com 2 1 Rx Tx Emergency I...

Страница 19: ...E 4 7 1 Standard Voltage Selection Panels 208 240 480 600 V 60 Hz 220 380 415 V 50 Hz The Standard voltage selection panel consists of multi tap trans formers contained in a steel case mounted in the...

Страница 20: ...rminal Blocks Step 2 Begin by inserting a small flathead screwdriver into the square tool hole with the flat surface of the screwdriver against the back wall of the hole With a little bit of force pus...

Страница 21: ...2 Disconnect the J7 connector from the ATC 300 controller 3 Locate the manual lever on the left side of the contactor 4 Locate the handle used to manually transfer the switch 5 Attach the handle to th...

Страница 22: ...Section 6 Testing and Problem Solving 6 1 Testing After the ATS equipment is initially installed or during planned outages the installation should be tested to ensure that all equip ment operates pro...

Страница 23: ...allow the engine to run unloaded for a preset time after transfer to the Source 1 power source is com pleted 6 1 5 Alternate Tests 1 Alternate operational tests may be possible depending upon the opti...

Страница 24: ...the structure area for safety hazards or potential maintenance problems Inspect the area especially where switching device is installed for any safety hazards including personnel safety and fire haza...

Страница 25: ...nsformer Pack 400A 2 Pole 3 Pole 4 Pole Cat 68C8229G02 Contactors 400A 400A 480VAC 2 Pole Cat 69C2990G01 400A 480VAC 3 Pole Cat 69C2990G02 400A 480VAC 4 Pole Cat 69C2990G03 200A 600VAC 2 Pole Cat 69C2...

Страница 26: ...IONS SET UP AND TESTING Step 1 Mount the ATS on a flat rigid surface Figure 20 Shim if necessary ATC 300 Electrical ase ase Source 1 Source 2 Available Available Connected Connected Load Unit Status A...

Страница 27: ...EL VOLTAGE SELECTION AND TRANSFORMER PANEL GROUND CONNECTION IB01602078E For more information visit www generac com Instruction Booklet Effective September 2011 Page 27 40 400A 480 600Vac ATC 300 3 Po...

Страница 28: ...ource 2 S1 Line S1 Neut S2 Line Control Power S2 Neut Clk In Out 5V Gnd Programming Port K1 Com K1 NO K2 Com K2 NO Pretransfer Com Pretransfer NO Pretransfer NC Alarm Com Alarm NO Alarm NC Earth Groun...

Страница 29: ...witch Figure 23 ATC 300 Logic Utility Supplying Load Step 6 To view the setpoints press the Step Enter pushbut ton and enter the Password Note The factory default Password is 0300 Once all installatio...

Страница 30: ...wering the load Is Source 1 Available TDEN timer times out Yes No No Yes Sends pretransfer signal TPRE timer times out If Source 1 is Available Open Source 2 Energize K1 Close Source 1 Energize K1 Sou...

Страница 31: ...load Is Source 1 Available TDEN timer times out Yes No No Yes Open Source 2 Energize K1 Close Source 1 Energize K1 Source 1 is powering the load Sends pretransfer signal TPRE timer times out If Source...

Страница 32: ...inal System Voltage 110 S1 OV PICK Volts Source 1 Overvoltage Pickup Range Contactor Style ATS 2 position 3 position 103 to Dropout 2 of Nominal System Voltage 105 S2 OV PICK Volts Source 2 Overvoltag...

Страница 33: ...Timer 0 sec to 6 sec 6 IN PHASE Hertz In Phase Transition 0 or 1 1 Enabled 1 IP FREQ DIFF Hertz In phase Transition Frequency Difference 0 0 Hz to 3 0 Hz 1 0 SYNC TIME Minutes In phase Transition Sync...

Страница 34: ...anually start the engine generator at the generator con troller Check that the generator is running and the Source 2 Available amber LED is lit Press the Step Enter pushbutton step through the phase v...

Страница 35: ...Failure Test Initiate a Load Test by simulating an actual power failure 1 This should be done by opening the upstream breaker or fused disconnect switch 2 The generator should start and the ATS should...

Страница 36: ...241 278 348 57 68 119 125 137 217 237 274 342 56 67 116 123 134 213 232 269 336 55 66 114 121 132 209 228 264 330 54 65 112 119 130 205 224 259 324 53 64 110 117 127 201 220 254 318 52 62 108 114 125...

Страница 37: ...Effective September 2011 Page 37 40 400A 480 600Vac ATC 300 3 Postion Contactor Based Transfer Switch OVERVOLTAGE PICKUP DROPOUT TABLE PERCENTAGE VOLTAGE 120 208 220 240 380 415 480 600 110 132 229 2...

Страница 38: ...For more information visit www generac com IB01602078E Instruction Booklet Page 38 Effective September 2011 40 400A 480 600Vac ATC 300 3 Postion Contactor Based Transfer Switch Notes...

Страница 39: ...IB01602078E For more information visit www generac com Instruction Booklet Effective September 2011 Page 39 40 400A 480 600Vac ATC 300 3 Postion Contactor Based Transfer Switch Notes...

Страница 40: ...E ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Generac be responsible to the purchaser or user in contract in tort including negligence strict...

Отзывы: