Operation
Owner’s Manual for 60 Hz Synergy Generator™
17
Manual Transfer Operation
Prior to automatic operation, manually exercise the
transfer switch to verify that there is no interference with
proper operation of the mechanism. Manual operation of
the transfer switch is required if electronic operation
should fail.
Transfer to Generator Power Source
1.
Verify generator is in the OFF mode.
2.
Set the main circuit breaker (Generator
Disconnect) to OFF or OPEN.
3.
Turn off the utility power supply to the transfer
switch using the means provided (such as a utility
main line circuit breaker).
4.
Use the manual transfer handle (A in
)
inside the transfer switch to move the main
contacts to the STANDBY position (loads
connected to the standby power source).
5.
To crank and start the engine, press the control
panel MANUAL button.
6.
Allow the engine to stabilize and warm up for a few
minutes.
7.
Set the main circuit breaker (Generator Disconnect)
to ON or CLOSED. The standby power source now
powers the loads.
Figure 3-8. Manual Transfer Switch Operation
Transfer Back to Utility Power Source
When utility power has been restored, transfer back to
utility source and shut down the generator. To manually
transfer back to utility power and shut down the
generator:
1.
Set the Main Circuit Breaker (Generator
Disconnect) to OFF or OPEN.
2.
Allow the engine to run for two minutes at no-load
to stabilize the internal temperatures.
3.
Press the control panel OFF button. The engine
should shut down.
4.
Verify that utility power supply to the transfer switch
is turned OFF.
(000132)
DANGER
Electrocution. Do not manually transfer under load.
Disconnect transfer switch from all power sources
prior to manual transfer. Failure to do so will result
in death or serious injury, and equipment damage.
000228
A
B
MANUAL
•
Will not transfer to generator if utility is present.
•
Will transfer to generator if utility fails (below 65% of nominal for five consecutive seconds).
•
Will transfer back when utility returns for 15 consecutive seconds. The engine will continue to
run until removed from the MANUAL mode.
AUTO
•
Will start and run if utility fails for five consecutive seconds. (factory default)
•
Will start a 5 second engine warm-up timer (or 30 seconds; refer to
):
–
Will not transfer if utility subsequently returns.
–
Will transfer to generator if utility is not present.
•
Will transfer back to utility once utility returns (above 80% of nominal) for 15 seconds.
•
Will not transfer back to utility unless utility returns. The generator will shut down if the OFF
button is pressed or a shutdown alarm is present.
•
Once utility power is returned, the generator will shut down after 1 minute cool-down time.
EXERCISE
•
Will not exercise if generator is already running in either AUTO or MANUAL mode.
•
During exercise, the controller will only transfer if utility fails during exercise for 10 seconds
(or 30 seconds; refer to
) and will switch to AUTO.
Содержание 0K2502SPFR
Страница 24: ...Operation 20 Owner s Manual for 60 Hz Synergy Generator This page intentionally left blank ...
Страница 34: ...Maintenance 30 Owner s Manual for 60 Hz Synergy Generator This page intentionally left blank ...
Страница 43: ......
Страница 87: ......
Страница 112: ...Fonctionnement 20 Manuel de l utilisateur du générateur SynergyMC de 60 Hz Page laissée en blanc intentionnellement ...
Страница 122: ...Entretien 30 Manuel de l utilisateur du générateur SynergyMC de 60 Hz Page laissée en blanc intentionnellement ...
Страница 131: ......