background image

Generac

®

Power Systems, Inc.

33

3.1

POST INSTALLATION TESTS

The air cooled Impact-36 plus II generator set was
factory tested and adjusted using gasoline as fuel.The
air cooled Impact-34 plus II generator set was factory
tested and adjusted using LP gas as fuel. It is not
required to adjust the unit any further except under
special circumstances.

Do not make any unnecessary adjustments.
Factory settings are correct for most applica-
tions. When making adjustments, however, be
careful to avoid overspeeding the engine.

3.2

BEFORE INITIAL START UP

Before starting, complete the following:

1. Check engine crankcase oil level and, if neces-

sary, fill to dipstick FULL mark with the recom-
mended oil. Do not fill above FULL mark.

2. Check the fuel supply. Gas fuel lines must have

been properly purged and leak tested in accor-
dance with applicable fuel codes. All fuel shutoff
valves in the fuel supply lines must be open.

If an LP (propane) gas fuel system has been
installed, it must have been properly tested
for leaks before operating the system in com-
pliance with ANSI A119.2/NFPA 501C. No leak-
age is permitted. Be sure no gaseous fuel
vapors enter the vehicle interior.

3.3

INITIAL START

When absolutely certain that the unit has been prop-
erly installed and prepared for use, start the engine
as follows:

1. Turn off all electrical loads. Do this by setting the

generator main circuit breaker to its “OFF” or
“OPEN” position.

2. Refer to the Owner's Manual shipped with unit for

cranking and starting instructions. The engine
may require more cranking for initial starting
since the fuel lines have to be primed (Use of the
Primer Switch on gasoline units will shorten this
time).

3. Let the engine warm up for about five minutes to

allow internal temperatures to stabilize.

4. Carefully inspect the engine-generator for fuel, oil

and exhaust system leaks. Before proceeding to
the next step, correct any leakage immediately.

5. When all tests and adjustments at no-load are

completed, apply electrical loads and check for
proper operation under load. See “Testing Under
Load”, Section 3.4. Run the unit at least 30 min-
utes with loads applied.

6. Turn off all electrical loads by setting the genera-

tor main circuit breaker to “OFF” or “OPEN.”

7. Let the unit run at no-load for a few minutes to

stabilize internal engine-generator temperatures.
Then, shut down the engine.

IMPORTANT: THE GENERATOR SET WAS THOR-
OUGHLY TESTED AND ADJUSTED AT THE FAC-
TORY BEFORE SHIPPING. NO ADDITIONAL
ADJUSTMENT SHOULD BE NECESSARY. ONLY
QUALIFIED SERVICE TECHNICIANS WHO HAVE
BEEN TRAINED SHOULD PERFORM ADJUST-
MENTS OUTLINED IN THIS MANUAL.

3.4

TESTING UNDER LOAD

Apply electrical loads equal to about 75-100% of the
unit's rated wattage/amperage capacity.

Let the unit run at least 30 minutes with load
applied. During this part of the test, check that the
unit is not running excessively hot and that adequate
cooling air flow is available. Do not allow the unit to
overheat during prolonged operation.

NOTE:

The generator engine is equipped with a high tem-
perature switch. The switch has normally-open
(N.O.) contacts. When the temperature is too high,
switch contacts close, and engine shuts down
automatically.

IMPORTANT: GENERAC RECOMMENDS THAT
THE GENERATOR IS TESTED FOR ADEQUATE
COOLING.

DANGER

!

Section 3 – Post-installation Start-up Checks

IMPACT-36 plus II Recreational Vehicle Generator

CHECKS

Содержание 00941-4

Страница 1: ...Owner s Manual and Installation Instructions Air cooled Recreational Vehicle Generator Model No 00941 4 IMPACT 36 plus II with Inverter This manual should remain with the unit...

Страница 2: ...f the vehicle and its equipment and for the safety of all vehicle occupants Before using this equipment we strongly recommend that the operator read this manual and thoroughly under stand all instruct...

Страница 3: ...Air Intake Screen 11 3 7 Engine Spark Plug 11 3 8 Inverter 11 3 9 Cleaning the Generator 11 3 10 Battery 12 3 11 Service and Adjustments 12 3 12 Adjusting the Carburetor 12 3 13 Adjusting Valve Clear...

Страница 4: ...MS MOVE INTO FRESH AIR IMMEDIATELY IF SYMPTOMS PERSIST GET MEDICAL HELP Shut down the generator and do not operate it until it has been inspected and repaired Never sleep in the vehicle while the gens...

Страница 5: ...the victim from the live conductor AVOID DIRECT CONTACT WITH THE VICTIM Use a nonconduct ing implement such as a dry rope or board to free the victim from the live conductor If the victim is unconscio...

Страница 6: ...Rating__________________________ 4 Rated Voltage __________________ 5 Phase ______________________________ 6 Hertz __________________________ 1 1 1 IMPACT 36LPG PLUS II FEATURES 1 Generator Air Intake...

Страница 7: ...ion 1 General Information IMPACT 36 plus II Recreational Vehicle Generator 1 1 2 INVERTER FEATURES PART NO 0D4885 1 Inverter 2 12 Pin Connection 3 Customer AC Output 4 DC Input 5 Cooling Fan REFERENCE...

Страница 8: ...y shorten its life Add up the rated watts of all electrical lighting appliance tool and motor loads the generator will power at one time This total should not be greater than the wattage capacity of t...

Страница 9: ...ter control system the computer disables the load capability of the gen erator and shuts down the engine Do not attempt to physically adjust or control the engine speed Equipment damage or per sonal i...

Страница 10: ...ENCES EXIST BETWEEN VEHICLES FOR EXAMPLE SOME VEHICLES MAY USE A TRANS FER SWITCH TO ISOLATE DOCKSIDE POWER FROM THE GENERATOR WHILE OTHER VEHI CLES MAY USE AN ISOLATING RECEPTACLE SOME VEHICLES MAY B...

Страница 11: ...P UNITS These generators are equipped with a liquefied petro leum LP gas fuel system LP gas is usually supplied as a liquid in pressure tanks These generators require a vapor withdrawal type fuel syst...

Страница 12: ...ne oil after the first 25 hours of opera tion Thereafter change oil every 100 operating hours Change oil more frequently if operating con sistently under heavy load or at high ambient tem peratures Wa...

Страница 13: ...7 ENGINE SPARK PLUG Clean engine spark plug and set gap to 0 030 inch 0 76mm every 100 hours of operation Figure 3 5 Clean by scraping or wire brushing and washing with commercial solvent DO NOT BLAS...

Страница 14: ...area immediately with clear water Do not use any jumper cables or booster bat tery to crank and start the generator engine If any battery has discharged remove it from the vehicle for recharging 3 11...

Страница 15: ...unning drain the oil completely Refill crankcase with recom mended oil See Specifications Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase Remove spar...

Страница 16: ...14 Generac Power Systems Inc Section 4 Notes IMPACT 36 plus II Recreational Vehicle Generator...

Страница 17: ...PART II INSTALLATION INSTRUCTIONS ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION DANGER...

Страница 18: ...nds that the installation initial startup and maintenance of this equipment is carried out by a Generac Authorized Service Dealer The engine exhaust fumes contain carbon monox ide which can be DEADLY...

Страница 19: ...conductor If the vic tim is unconscious apply first aid and get immediate medical help Never wear jewelry when working on this equip ment Jewelry can conduct electricity resulting in electric shock or...

Страница 20: ...ed standards as well as the manufacturer s recommendations The following standards booklets latest revision are available from the sources indicated 1 NFPA 1192 Standard for Recreational Vehicles repl...

Страница 21: ...ich will restrain the generator set should consist of at least two horizontal beams These beams should consist of a 1 1 2 inch square 11 gauge steel tubing OR b 1 1 2 inch 11 gauge angle iron A typica...

Страница 22: ...STEEL DUE TO ALUMINUM S LOW MELTING POINT If the compartment is lined with galvanized steel it may be constructed of any material Generac rec ommends that the compartment be constructed of 1 2 inch t...

Страница 23: ...ing the vehicle interior Refer to the sealant information as noted previously NOTE Silicone rubber base sealant is an acceptable caulking material Pressing putty tape onto com partment joints and seam...

Страница 24: ...is used its coated side should face toward the compartment interior Using a combination of sound insulating materials can often reduce noise more effectively than a single material For example a sheet...

Страница 25: ...e the compartment door interior except for air openings with suitable fire proof sound insula tion such as 1 inch thick fiberglass with a 2 pound density It is absolutely essential that an adequate fl...

Страница 26: ...F PLANNING TO INSTALL THE GEN ERATOR IN A COMPARTMENT BE SURE TO LEAVE AT LEAST ONE INCH 2 recommended OF CLEAR ANCE BETWEEN THE GENERATOR AND COM PARTMENT WALLS AND CEILING INCLUDE 26 GAUGE GALVANIZE...

Страница 27: ...AS THE GENERATOR The sensing harnesses supplied with the inverter have a maximum length of 12 feet If the cables are longer than needed coil the excess near the inverter unit If a greater length is n...

Страница 28: ...o the secondary regulator at 11 inch es water column Do NOT exceed 14 inches water column The installer must be sure the primary regulator is rated at sufficient gas flow to operate the generator plus...

Страница 29: ...be tested under gas or air pressure of not less than 90 psi 620kPa while using soap and water or equiva lent solution to check for leaks Other approved methods of testing for leaks may be used if app...

Страница 30: ...vehicle Terminate the exhaust tailpipe such that exhaust gases will not be drawn back into the generator compartment and recirculated If there is any possibility of the tailpipe or muffler being damag...

Страница 31: ...om being connected to two different power sup plies at the same time such as generator and dockside power Conductors must be rated 221 F 105 C or must be of a larger conductor size 2 6 2 GENERATOR AC...

Страница 32: ...gure 2 20 Transfer Switch Isolation Method Figure 2 21 Installation with Isolation Receptacle INVERTER INVERTER POWER CORD FOR DOCKSIDE POWER POWER SUPPLY CORD Section 2 Installation IMPACT 36 plus II...

Страница 33: ...y rated 70 amp hours and capa ble of delivering 400 cold cranking amperes For prevailing ambient temperatures below 32 F 0 C use a battery rated 95 amp hours and capa ble of delivering 450 cold cranki...

Страница 34: ...PLUG IN RECEPTACLE A plug in receptacle Figure 2 24 is provided on the generator set near the DC power wires Use this receptacle to connect an optional remote mounted start stop panel to the generator...

Страница 35: ...l lines have to be primed Use of the Primer Switch on gasoline units will shorten this time 3 Let the engine warm up for about five minutes to allow internal temperatures to stabilize 4 Carefully insp...

Страница 36: ...s properly and safely installed ELECTRICAL CONNECTIONS Connections comply with local code requirements and all National Electrical Codes Junction box is properly installed Wiring meets all standards A...

Страница 37: ...ugh 1 Air cleaner plugged or damaged 1 Clean or replace as needed 2 Defective spark plug 2 Clean regap or replace plug Engine starts shuts down 1 Engine oil is low 1 Check oil add as needed when Start...

Страница 38: ...36 Generac Power Systems Inc Section 5 Electrical Data IMPACT 36 plus II Recreational Vehicle Generator Wiring Diagram and Schematic Drawing No 0D4947 B...

Страница 39: ...Generac Power Systems Inc 37 Section 5 Electrical Data IMPACT 36 plus II Recreational Vehicle Generator Wiring Diagram and Schematic Drawing No 0D4947 B...

Страница 40: ...22 2 9 13 2 11 21 14 40 9 15 1 19 19 17 14 16 46 23 8 9 5 41 9 20 41 31 38 25 43 27 26 7 12 31 42 22 37 22 10 30 20 48 33 34 45 24 51 50 Section 6 Exploded Views and Parts Lists IMPACT 36 plus II Rec...

Страница 41: ...089744 1 RESISTOR POWER 1 OHM 29 0A6423A 2 BUS BAR OUTER 30 045756 4 TAPTITE M6 1 0 X 10MM 31 086722 1 BRACKET HEAT SINK PCB 32 075210A 1 TERMINAL BLOCK 33 0A6423B 4 BUS BAR INNER 34 0912970025 1 GROU...

Страница 42: ...52 9 56 49 50 48 9 54 51 44 42 2 62 61 47 11 9 16 49 9 45 46 1 11 18 9 3 19 4 4 3 5 12 21 22 6 2 7 5 13 14 13 58 5 15 16 7 8 5 63 Section 6 Exploded Views and Parts Lists IMPACT 36 plus II Recreationa...

Страница 43: ...X 35mm 33 020668 2 EARTHING STRAP ITEM PART NO QTY DESCRIPTION 34 092000 1 BRACKET MUFFLER HANGER 35 079246 2 SCREW HHC M6 1 0 X 16mm W LOCK WASHER 36 086731A 1 ASSEMBLY MUFFLER 37 094670 1 CLAMP EXH...

Страница 44: ...49 50 34 28 13 52 8 1 18 17 51 25 22 33 32 58 42 19 59 23 24 11 13 37 17 4 39 40 38 21 26 30 53 31 48 43 45 46 44 47 36 Section 6 Exploded Views and Parts Lists IMPACT 36 plus II Recreational Vehicle...

Страница 45: ...HHFC M8 1 25 X 35 30 0C3733 2 RETAINER VALVE 31 0C4390 2 SPRING VALVE 32 088590 1 DOWEL DIA 12 X 18L 33 083152 1 GEROTER INNER 6 5 34 076381 2 BOLT CON ROD 36 021705B 1 ASSY CYL HD GDS STS 37 0C3590 1...

Страница 46: ...68 60 4 73 67 72 42 41 45 44 66 65 57 75 7 58 56 63 64 32 43 48 49 38 37 35 47 60 51 53 54 52 62 61 59 59 31 34 36 50 16 13 30 32 85 84 66 89 87 88 86 66 83 Section 6 Exploded Views and Parts Lists IM...

Страница 47: ...3 8 16 X 1 1 4 ITEM PART NO QTY DESCRIPTION 46 086705 1 PLATE DIVIDER 47 090192 1 WASHER CARBURETOR 48 089477 1 CLIP ADJUSTMENT 49 086706 1 ROD THROTTLE CONTROL 50 089478 1 SNAP RETAINING 51 078609 2...

Страница 48: ...SPRING REGULATOR 45N M 29MM 16 0C4643A 1 INLET TWIN REG 11 11 DIA 17 0C6066 1 SEAL INLET REGULATOR 18 0C5968 1 SUPPORT INLET SEAL 19 0C5759 1 PIN PIVOT ARM 20 0C5761 1 LEVER REGULATOR 21 0C6069 1 GAS...

Страница 49: ...Section 7 Installation Diagram IMPACT 36 plus II Recreational Vehicle Generator Major Features and Dimensions Drawing No 0F1119 Generac Power Systems Inc 47...

Страница 50: ...your engine or a part component thereof has failed due to abuse neglect improper maintenance or unap proved modifications or the use of counterfeit and or grey market parts not made supplied or appro...

Страница 51: ...Any such emissions related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emi...

Страница 52: ...anty expense allowances are subject to the conditions defined in Guardian s Warranty Policies and Procedures Guide THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING Generac Guardian generators that utili...

Отзывы: