2.10 BATTERY INSTALLATION

Standby generators installed with automatic
transfer switches will crank and start automati-
cally when NORMAL (UTILITY) source voltage is
removed or is below an acceptable preset level.
To prevent such automatic start-up and possible
injury to personnel, do not connect battery
cables until certain that normal source voltage
at the transfer switch is correct and the system
is ready to be placed into operation. Ensure
that the 5A and 15A fuses in the control panel
are removed when connecting or disconnecting
battery cables.

Storage batteries give off explosive hydrogen
gas. This gas can form an explosive mixture
around the battery for several hours after
charging. The slightest spark can ignite the gas
and cause an explosion. Such an explosion can
shatter the battery and cause blindness or
other injury. Any area that houses a storage
battery must be properly ventilated. Do not
allow smoking, open flame, sparks or any spark
producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely corro-
sive sulfuric acid solution that can cause severe
burns. Do not permit fluid to contact eyes, skin,
clothing, painted surfaces, etc. Wear protective
goggles, protective clothing and gloves when
handling a battery. If fluid is spilled, flush the
affected area immediately with clear water.

Do not dispose of the battery in a fire. The bat-
tery is capable of exploding.

Do not open or mutilate the battery. Released
electrolyte can be toxic and harmful to the skin
and eyes.

The battery represents a risk of high short cir-
cuit current. When working on the battery,
always remove watches, rings or other metal
objects, and only use tools that have insulated
handles.

2.10.1 VENTED BATTERIES

The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive. The following proce-
dures are to be observed:

• Wear full eye protection and protective clothing,
• Where electrolyte contacts the skin, wash it off

immediately with water,

• Where electrolyte contacts the eyes, flush thor-

oughly and immediately with water and seek med-
ical attention, and

• Spilled electrolyte is to be washed down with an

acid-neutralizing agent. A common practice is to
use a solution of one pound (500 grams) bicarbon-
ate of soda to one gallon (4 liters) of water. The
bicarbonate of soda solution is to be added until
the evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.

Lead acid batteries present a risk of fire
because they generate hydrogen gas. The fol-
lowing procedure are to be followed:

• DO NOT SMOKE when near batteries,
• DO NOT cause flame or spark in battery area, and
• Discharge static electricity from body before touch-

ing batteries by first touching a grounded metal
surface.

Servicing of batteries is to be performed or super-
vised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized person-
nel away from batteries.

The recommended battery is Group 26, 525 CCA/75
AH minimum at 0° F (-17.8° C). All batteries must be
at 100 percent state-of-charge before they are
installed on the generator.

When using maintenance-free batteries, it is not nec-
essary to check the specific gravity or electrolyte level.
Have these procedures performed at the intervals
specified in Section 4, “Maintenance.” A negative
ground system is used. Battery connections are
shown on the wiring diagrams. Make sure all batter-
ies are correctly connected and terminals are tight.
Observe battery polarity when connecting batteries to
the generator set.

NOTE:

Damage will result if the battery connections are
made in reverse.

2.11 PREPARATION BEFORE START-UP

The instructions in this section assume that the
standby generator has been properly installed, serv-
iced, tested, adjusted and otherwise prepared for use
by a competent, qualified installation contractor. Be
sure to read the “Safety Rules” on pages 2 and 3, as
well as all other safety information in this manual,
before attempting to operate this (and related) equip-
ment.

!

‹

!

!

!

DANGER

Section 2 — Installation

Guardian Liquid-cooled 25 kW Generator

Содержание 005040-2

Страница 1: ...Owner s Manual ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION This manual should remain with the unit Liquid cooled Prepackaged Standby Generators Model Number 005040 2 25kW...

Страница 2: ...tential explosion hazard This symbol points out potential fire hazard This symbol points out potential electrical shock hazard The operator is responsible for proper and safe use of the equipment Gene...

Страница 3: ...od 9 2 6 Total Circuit Isolation Method 10 2 7 Grounding the Generator 10 2 8 Generator AC Neutral Connections 10 2 9 Using an Engineered GTS Transfer Switch 10 2 10 Battery Installation 11 2 11 Prepa...

Страница 4: ...ven death For that reason adequate ventilation must be provided Keep hands feet clothing etc away from drive belts fans and other moving or hot parts Never remove any drive belt or fan guard while the...

Страница 5: ...can conduct electricity resulting in electric shock or may get caught in moving components causing injury FIRE HAZARDS Keep a fire extinguisher near the generator at all times Do NOT use any carbon t...

Страница 6: ...ect the switch at all times against excessive moisture dust dirt lint construction grit and cor rosive vapors If a transfer switch is not included one may be pur chased separately from a Generac Autho...

Страница 7: ...cally shut down under the fol lowing conditions low oil pressure high coolant tem perature engine overspeed low coolant level or over crank Figure 1 3 Figure 1 3 Engine Protective Devices 1 7 1 LOW OI...

Страница 8: ...ck cartons with the proper side up as noted on the shipping carton 1 8 2 INSPECTION Upon delivery carefully inspect the generator for any damage that may have occurred during shipment If loss or damag...

Страница 9: ...2 5 Install brass hose fitting into Port 2 6 Install pipe plug into Port 1 7 Connect carburetor gas hose to brass fitting 8 Tighten all clamps and plugs 9 Make sure fuel supply is of the proper pressu...

Страница 10: ...ll phases of operation including engine start up and load transfer 2 1 STANDBY GENERATOR INSTALLATION Connecting this generator to an electrical sys tem normally supplied by an electric utility shall...

Страница 11: ...enerator as close as possible to the fuel supply to reduce the length of piping HOWEVER REMEMBER THAT LAWS OR CODES MAY REG ULATE THE DISTANCE 2 3 GENERATOR MOUNTING AND SUPPORT Retain the generator c...

Страница 12: ...ng is recommended only at the main service entrance If the neutral wire is grounded and one of the phase loads becomes grounded the excessive current opens the load circuit breaker or collapses the ge...

Страница 13: ...g Where electrolyte contacts the skin wash it off immediately with water Where electrolyte contacts the eyes flush thor oughly and immediately with water and seek med ical attention and Spilled electr...

Страница 14: ...em for leaks and other problems See Specifications and Coolant 2 11 6 BELT TENSION Check the engine fan belt tension and condition prior to placing the unit into service and at recommended intervals B...

Страница 15: ...15 AMP FUSE This fuse protects the control console s DC control circuit against electrical overload and is located inside the control panel If the fuse has melted open because of an overload engine c...

Страница 16: ...the factory during final testing of the generator and should not be adjusted If however adjustments are necessary the following procedure should be followed Figure 3 2 and Section 3 8 1 Move dip swit...

Страница 17: ...sfer switch using whatever means provided such as a utility main line circuit breaker The utility power source now powers the loads 3 6 AUTOMATIC OPERATION To set the system for fully automatic operat...

Страница 18: ...generator alternator output frequency and is factory pre set for 60 Hz Switch Position 2 Selects the type of transfer switch and is factory pre set for an automatic trans fer switch ATS Switch Positio...

Страница 19: ...ts studs to specifications in the tightening sequence shown First pass 7 10 N m 5 7 lb ft Final pass 26 38 N m 19 28 lb ft Figure 4 1 Intake Manifold Installation 4 4 CYLINDER HEAD PROCEDURE 1 Positio...

Страница 20: ...iodically remove radiator pressure cap only when engine has cooled down to make sure the coolant recovery system is functioning properly Coolant should be at bottom of radiator filler neck If coolant...

Страница 21: ...f old filter 5 Apply light coating of new engine oil to seal of new oil filter Install FILTER and tighten by hand only DO NOT OVER TIGHTEN 6 Remove OIL FILL CAP Add recommended oil see SPECIFICATIONS...

Страница 22: ...9 3 BATTERY MAINTENANCE The battery should be inspected per Section 4 7 Scheduled Maintenance The following procedure should be followed for inspection 1 Inspect the battery posts and cables for tight...

Страница 23: ...battery cable The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condi tion from burning out sensitive control panel components and circuits Following...

Страница 24: ...Correct as necessary 5 Check the natural gas delivery system on gas engine driven units Tighten connections as necessary 6 Check the air inlets and outlets for debris Clean as necessary 7 Check the b...

Страница 25: ...d abnormal operating conditions Correct as necessary 14 Start and exercise the unit at full rated load use a load bank if the site load is not enough for at least 2 hours looking for leaks loose conne...

Страница 26: ...gs 3 Clean regap or replace plugs Engine starts then shuts down 1 Engine oil level is low 1 Check oil and add oil as needed 2 Engine is overheated 2 Check cooling system for leaks 3 Defective Low Oil...

Страница 27: ...Generac Power Systems Inc 25 Section 6 Notes Guardian Liquid cooled 25 kW Generator...

Страница 28: ...26 Generac Power Systems Inc Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Wiring Diagram 2 5L Engine 15kW 20kW units Drawing No 0F1411 A...

Страница 29: ...Generac Power Systems Inc 27 Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Wiring Diagram 2 5L Engine 15kW 20kW units Drawing No 0F1411 A...

Страница 30: ...28 Generac Power Systems Inc Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Electrical Schematic 2 5L Engine 15kW 20kW units Drawing No 0F1413 A...

Страница 31: ...Generac Power Systems Inc 29 Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Electrical Schematic 2 5L Engine 15kW 20kW units Drawing No 0F1413 A...

Страница 32: ...30 Generac Power Systems Inc Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Wiring Diagram 2 5L Engine 25kW unit Drawing No 0E9982 C...

Страница 33: ...Generac Power Systems Inc 31 Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Wiring Diagram 2 5L Engine 25kW unit Drawing No 0E9982 C...

Страница 34: ...32 Generac Power Systems Inc Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Electrical Schematic 2 5L 25kW unit Drawing No 0E9983 C...

Страница 35: ...Generac Power Systems Inc 33 Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Electrical Schematic 2 5L 25kW unit Drawing No 0E9983 C...

Страница 36: ...25 kW Generator Mounting Base Drawing No 0E9964 E 28 ENGINE BLOCK 5 CARRIER REAR BEARING 14 15 13 3 BOTTOM PANEL 3 2 12 4 1 11 15 14 13 33 2 3 12 11 36 35 10 10 3 1 6 8 9 3 22 21 27 23 1 25 26 29 34...

Страница 37: ...4 052259 4 WASHER FLAT M12 15 052891 4 SCREW HHC M12 1 75 X 80 G8 8 16 0536210261 1 ASSY WIRE 0 12 00 17 074906 1 SCREW HHTT M6 1 0 X 20 BP 18 077483 REF BATT 12VDC 75 AH 26 NOT SHOWN 19 0E9941 1 HOLD...

Страница 38: ...0E9720 J 35 NUTS ITEM 26 USE LOCTITE ON PANEL FOR ACCESS COVER CABLE WELD STUD UNDER ROOF 17 GROUND WIRE FASTENER TO SECURE USE DOOR LATCH NOTE 6 18 38 11 31 7 9 24 1 4 26 2 18 8 29 2 12 11 14 13 10 5...

Страница 39: ...72J 2 ACSTC INSLTN 1 5L RR CRNR BOTTOM 29 0E0072L 2 ACSTC INSLTN 1 5L SIDE BRC PNL 30 0E0072M 2 ACSTC INSLTN 1 5L SIDE DR PNL 31 0D2023 1 TRIM VINYL SELF GRIPPING 80 LG 33 0E0072Q 2 ACSTC INSLTN 1 5L...

Страница 40: ...4 26 10 14 1 29 24 31 33 52 50 41 33 4 48 13 27 66 36 54 A 23 65 37 35 2 7 3 35 9 34 43 34 21 35 17 30 34 22 3 35 16 36 34 5 56 0 12 14 11 64 54 38 18 39 Section 8 Exploded Views and Parts Guardian Li...

Страница 41: ...13 SCREW PHTT M4 0 7 X 16 ZYC 35 022264 22 WASHER LOCK 8 M4 36 0C2265 7 SCREW PHTT M4 0 7 X 12 ZYC 37 023965 2 SCREW RHM 8 32 X 3 8 38 039782 1 BRKT MTG CB BQ ITEM PART NO QTY DESCRIPTION 39 0A2077 1...

Страница 42: ...40 Generac Power Systems Inc Section 8 Exploded Views and Parts Guardian Liquid cooled 25 kW Generator Control Panel Drawing No 0F1378 F...

Страница 43: ...CONTROL HSB 2 5L FORD 33 022097 3 WASHER LOCK M6 1 4 34 0C2212 9 SCREW PHTT M4 0 7 X 16 ZYC 35 022264 22 WASHER LOCK 8 M4 36 0C2265 13 SCREW PHTT M4 0 7 X 12 ZYC ITEM PART NO QTY DESCRIPTION 37 023965...

Страница 44: ...ND 5 3 22 17 68 15 19 10 38 22 31 0 HSG 20 3 47 45 20 49 1 16 39 50 34 35 65 33 57 18 37 18 20 16 38 RADIATOR CAP 62 TO 58 39 STEPPER MOTOR UNITS ONLY 17 12 A 11 67 24 23 61 Section 8 Exploded Views a...

Страница 45: ...E9680 1 GASKET 2 5L FORD EXHAUST MAN 34 0E9609 1 MANIFOLD EXHAUST MACHINED ITEM PART NO QTY DESCRIPTION 35 0E9930 1 HEAT SHIELD EXHAUST MANIFOLD 36 049821 3 SCREW SHC M8 1 25 X 30 G12 9 37 0E9747 1 ST...

Страница 46: ...LVE 12 13 28 1 8 20 33 31 32 17 34 26 6 38 30 16 25 24 18 4 29 15 9 5 27 6 4 CARBURETOR ASSY 0E1028A I N 19 CONVERSION 35 41 OUT 2 PORT L P VAPOR 3 40 1 11 3 40 7 2 6 11 Section 8 Exploded Views and P...

Страница 47: ...CARBURETOR GASKET 21 091526 4 SCREW PPHM M5 0 8 X 12 ZNC 22 049226 4 WASHER LOCK M5 23 026307 1 ELBOW 90D STREET 3 4 24 062522 1 STUD TH 1 4 20 X 3 G2 ZNC FULL 25 022127 1 NUT HEX 1 4 20 STEEL 26 022...

Страница 48: ...Power Systems Inc 3 LOCKTIGHT LOCKTIGHT 7 15 17 8 7 6 18 4 16 LEADS 5 2 9 13 21 19 20 14 10 11 12 30 1 31 Section 8 Exploded Views and Parts Guardian Liquid cooled 25 kW Generator Alternator Drawing N...

Страница 49: ...1 REVCOR FAN 10 75 X 2 W PRESS DIS 7 046526 8 WASHER LOCK M10 8 051755 4 SCREW HHC M10 1 5 X 16 G8 8 9 04576100BK 4 STUD M14 2 0 X 490 G5 ZINC 3 0L FORD 2 5L FORD 04576100BF 4 STUD M14 2 0 X 540 G5 Z...

Страница 50: ...C M6 1 0 X 16 G8 8 14 022097 4 WASHER LOCK M6 1 4 15 022473 8 WASHER FLAT 1 4 M6 ZINC 16 049813 4 NUT HEX M6 X 1 0 G8 YEL CHR 17 039253 2 SCREW HHC M8 1 25 X 20 G8 8 18 045771 2 NUT HEX M8 1 25 G8 YEL...

Страница 51: ...1 ASSY CARBURETOR LINKAGE ROD 12 0A7106 1 BRACKET STEPPER MOTOR 13 074031 AR LIQUID NEOPRENE 14 029333A 1 TIE WRAP 7 4 X 19 BLK UL 15 022507 2 SCREW HHC 1 4 20 X 1 2 G5 16 022473 2 WASHER FLAT 1 4 ZI...

Страница 52: ...060035 4 SPACER 41 X 75 X 87 ST ZNC ITEM PART NO QTY DESCRIPTION 14 0F0127 1 HOSE UPPER RADIATOR 174MM TAL 15 0E9833 1 HOSE 2 5L FORD LOWER RADIATOR 16 035461 1 BARBED STR 1 4NPT X 3 8 17 069860C 1 HO...

Страница 53: ...Generac Power Systems Inc 51 Section 9 Installation Diagram Guardian Liquid cooled 25 kW Generator Installation Diagram Drawing No 0F1020 A...

Страница 54: ...enerac may deny any and or all warranty coverage or responsibility if your engine or a part component thereof has failed due to abuse neglect improper maintenance or unap proved modifications or the u...

Страница 55: ...to Subsection 4 below Any such emissions related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replaceme...

Страница 56: ...losures that are rusting due to the improper installation location in a harsh or saltwater environment or scratched where integrity of paint applied is compromised Failures caused by any contaminated...

Отзывы: