Pos2 OFF — Standard Prepackaged ATS

Application

• The control board will perform all of the automat-

ic features listed in this document.

• The two-wire start connections, wires 178-183,

should NOT be connected.

NOTE:

If the generator is installed in conjunction with an
engineered GTS type transfer switch, refer to the
applicable transfer switch manual for exact oper-
ating parameters and timing sequences.

2.10 BATTERY INSTALLATION

Standby generators installed with automatic
transfer switches will crank and start automati-
cally when NORMAL (UTILITY) source voltage is
removed or is below an acceptable preset level.
To prevent such automatic start-up and possible
injury to personnel, do not connect battery
cables until certain that normal source voltage
at the transfer switch is correct and the system
is ready to be placed into operation. Ensure
that the 5A and 15A fuses in the control panel
are removed when connecting or disconnecting
battery cables.

Storage batteries give off explosive hydrogen
gas. This gas can form an explosive mixture
around the battery for several hours after
charging. The slightest spark can ignite the gas
and cause an explosion. Such an explosion can
shatter the battery and cause blindness or
other injury. Any area that houses a storage
battery must be properly ventilated. Do not
allow smoking, open flame, sparks or any spark
producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely corro-
sive sulfuric acid solution that can cause severe
burns. Do not permit fluid to contact eyes, skin,
clothing, painted surfaces, etc. Wear protective
goggles, protective clothing and gloves when
handling a battery. If fluid is spilled, flush the
affected area immediately with clear water.

Do not dispose of the battery in a fire. The bat-
tery is capable of exploding.

Do not open or mutilate the battery. Released
electrolyte can be toxic and harmful to the skin
and eyes.

The battery represents a risk of high short cir-
cuit current. When working on the battery,
always remove watches, rings or other metal
objects, and only use tools that have insulated
handles.

2.10.1 VENTED BATTERIES

The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive. The following proce-
dures are to be observed:

• Wear full eye protection and protective clothing,
• Where electrolyte contacts the skin, wash it off

immediately with water,

• Where electrolyte contacts the eyes, flush thor-

oughly and immediately with water and seek med-
ical attention, and

• Spilled electrolyte is to be washed down with an

acid-neutralizing agent. A common practice is to
use a solution of one pound (500 grams) bicarbon-
ate of soda to one gallon (4 liters) of water. The
bicarbonate of soda solution is to be added until
the evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.

Lead acid batteries present a risk of fire
because they generate hydrogen gas. The fol-
lowing procedure are to be followed:

• DO NOT SMOKE when near batteries,
• DO NOT cause flame or spark in battery area, and
• Discharge static electricity from body before touch-

ing batteries by first touching a grounded metal
surface.

Servicing of batteries is to be performed or super-
vised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized person-
nel away from batteries.

The recommended battery is Group 26, 525 CCA/75
AH minimum at 0° F (-17.8° C). All batteries must be
at 100 percent state-of-charge before they are
installed on the generator.

When using maintenance-free batteries, it is not nec-
essary to check the specific gravity or electrolyte level.
Have these procedures performed at the intervals
specified in Section 4, “Maintenance.” A negative
ground system is used. Battery connections are
shown on the wiring diagrams. Make sure all batter-
ies are correctly connected and terminals are tight.
Observe battery polarity when connecting batteries to
the generator set.

NOTE:

Damage will result if the battery connections are
made in reverse.

!

‹

!

!

!

DANGER

Section 2 — Installation

Guardian Liquid-cooled 25 kW Generator

Содержание 005040-0, 005040-1, 005053-0, 005053-1, 005054-0, 005054-1

Страница 1: ...FIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION This manual should remain with the unit Liquid cooled Prepackaged Standby Generators Model Nos 005040 0 005040 1 25kW 005053 0 005053 1 20k...

Страница 2: ...tential explosion hazard This symbol points out potential fire hazard This symbol points out potential electrical shock hazard The operator is responsible for proper and safe use of the equipment Gene...

Страница 3: ...d 10 2 6 Total Circuit Isolation Method 10 2 7 Grounding the Generator 10 2 8 Generator AC Neutral Connections 10 2 9 Using an Engineered GTS Transfer Switch 10 2 10 Battery Installation 11 2 11 Prepa...

Страница 4: ...ng that might render the unit unsafe or in noncompliance with the aforementioned codes standards laws and regula tions The engine exhaust fumes contain carbon monoxide gas which can be DEADLY This dan...

Страница 5: ...not pos sible attempt to free the victim from the live conductor AVOID DIRECT CONTACT WITH THE VICTIM Use a nonconducting implement such as a dry rope or board to free the victim from the live conduct...

Страница 6: ...urface Never install the switch where water or any corro sive substance might drip onto the enclosure Protect the switch at all times against excessive moisture dust dirt lint construction grit and co...

Страница 7: ...VE DEVICES The engine has several safety switches which cause the engine to automatically shut down under the fol lowing conditions low oil pressure high coolant tem perature engine overspeed low cool...

Страница 8: ...ck cartons with the proper side up as noted on the shipping carton 1 8 2 INSPECTION Upon delivery carefully inspect the generator for any damage that may have occurred during shipment If loss or damag...

Страница 9: ...re and type for configuration 10 Move dip switch position 4 on the control board to the off position LP vapor see Figure 3 2 and Section 3 8 11 Reverse the procedure to convert back to natural gas Fig...

Страница 10: ...witch if necessary The standard prepackaged transfer switch does not have sensing or controlling circuit boards Instead the generator control console houses a Printed Circuit Board Assembly which cont...

Страница 11: ...for maintenance and servicing A required mini mum allowance of space to any solid structure is three feet Five feet allowance of space is recom mended Where strong prevailing winds blow from one dire...

Страница 12: ...in the area Grounding procedures must meet local regulations Do not connect the ground wire to any pipe that carries a flammable or explosive substance FIRE or an EXPLOSION may result Proper groundin...

Страница 13: ...of high short cir cuit current When working on the battery always remove watches rings or other metal objects and only use tools that have insulated handles 2 10 1 VENTED BATTERIES The electrolyte is...

Страница 14: ...ine Oil Recommendations NOTE This engine is shipped from the manufacturer with 15W 40 oil This oil should be changed after 30 hours of operation 2 11 5 ENGINE COOLANT Have the engine cooling system pr...

Страница 15: ...1 7 for further explanation of engine pro tection functions 3 2 3 15 AMP FUSE This fuse protects the control console s DC control circuit against electrical overload and is located inside the control...

Страница 16: ...the factory during final testing of the generator and should not be adjusted If however adjustments are necessary the following procedure should be followed Figure 3 2 and Section 3 8 1 Move dip swit...

Страница 17: ...sfer switch using whatever means provided such as a utility main line circuit breaker The utility power source now powers the loads 3 6 AUTOMATIC OPERATION To set the system for fully automatic operat...

Страница 18: ...generator alternator output frequency and is factory pre set for 60 Hz Switch Position 2 Selects the type of transfer switch and is factory pre set for an automatic trans fer switch ATS Switch Positio...

Страница 19: ...ts studs to specifications in the tightening sequence shown First pass 7 10 N m 5 7 lb ft Final pass 26 38 N m 19 28 lb ft Figure 4 1 Intake Manifold Installation 4 4 CYLINDER HEAD PROCEDURE 1 Positio...

Страница 20: ...iodically remove radiator pressure cap only when engine has cooled down to make sure the coolant recovery system is functioning properly Coolant should be at bottom of radiator filler neck If coolant...

Страница 21: ...f old filter 5 Apply light coating of new engine oil to seal of new oil filter Install FILTER and tighten by hand only DO NOT OVER TIGHTEN 6 Remove OIL FILL CAP Add recommended oil see SPECIFICATIONS...

Страница 22: ...9 3 BATTERY MAINTENANCE The battery should be inspected per Section 4 7 Scheduled Maintenance The following procedure should be followed for inspection 1 Inspect the battery posts and cables for tight...

Страница 23: ...battery cable The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condi tion from burning out sensitive control panel components and circuits Following...

Страница 24: ...Correct as necessary 5 Check the natural gas delivery system on gas engine driven units Tighten connections as necessary 6 Check the air inlets and outlets for debris Clean as necessary 7 Check the b...

Страница 25: ...d abnormal operating conditions Correct as necessary 14 Start and exercise the unit at full rated load use a load bank if the site load is not enough for at least 2 hours looking for leaks loose conne...

Страница 26: ...gs 3 Clean regap or replace plugs Engine starts then shuts down 1 Engine oil level is low 1 Check oil and add oil as needed 2 Engine is overheated 2 Check cooling system for leaks 3 Defective Low Oil...

Страница 27: ...Generac Power Systems Inc 25 Section 6 Notes Guardian Liquid cooled 25 kW Generator...

Страница 28: ...26 Generac Power Systems Inc Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Wiring Diagram 2 5L Engine 15kW 20kW units Drawing No 0F1411...

Страница 29: ...Generac Power Systems Inc 27 Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Wiring Diagram 2 5L Engine 15kW 20kW units Drawing No 0F1411...

Страница 30: ...28 Generac Power Systems Inc Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Electrical Schematic 2 5L Engine 15kW 20kW units Drawing No 0F1413...

Страница 31: ...Generac Power Systems Inc 29 Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Electrical Schematic 2 5L Engine 15kW 20kW units Drawing No 0F1413...

Страница 32: ...30 Generac Power Systems Inc Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Wiring Diagram 2 5L Engine 25kW unit Drawing No 0E9982 B...

Страница 33: ...Generac Power Systems Inc 31 Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Wiring Diagram 2 5L Engine 25kW unit Drawing No 0E9982 B...

Страница 34: ...32 Generac Power Systems Inc Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Electrical Schematic 2 5L 25kW unit Drawing No 0E9983 B...

Страница 35: ...Generac Power Systems Inc 33 Section 7 Electrical Data Guardian Liquid cooled 25 kW Generator Electrical Schematic 2 5L 25kW unit Drawing No 0E9983 B...

Страница 36: ...25 kW Generator Mounting Base Drawing No 0E9964 E 28 ENGINE BLOCK 5 CARRIER REAR BEARING 14 15 13 3 BOTTOM PANEL 3 2 12 4 1 11 15 14 13 33 2 3 12 11 36 35 10 10 3 1 6 8 9 3 22 21 27 23 1 25 26 29 34...

Страница 37: ...4 052259 4 WASHER FLAT M12 15 052891 4 SCREW HHC M12 1 75 X 80 G8 8 16 0536210261 1 ASSY WIRE 0 12 00 17 074906 1 SCREW HHTT M6 1 0 X 20 BP 18 077483 REF BATT 12VDC 75 AH 26 NOT SHOWN 19 0E9941 1 HOLD...

Страница 38: ...9720 D 35 NUTS ITEM 26 USE LOCTITE ON PANEL FOR ACCESS COVER CABLE WELD STUD UNDER ROOF 17 GROUND WIRE FASTENER TO SECURE USE DOOR LATCH NOTE 26 38 11 25 31 7 9 24 10 4 2 15 26 25 19 8 29 2 11 16 14 1...

Страница 39: ...4 20 STEEL 21 0C2634A 1 ASSEMBLY COVER ACCESS 22 022473 1 WASHER FLAT 1 4 ZINC 23 022097 1 WASHER LOCK M6 1 4 24 0D2023 2 GASKET CLIP ON SELF GRIPPING 89 LG 25 0C2164 1 LATCH AND CAM 26 037337 6 NUT...

Страница 40: ...14 26 10 14 1 24 29 33 31 50 52 41 33 4 48 13 27 36 54 A 23 65 37 35 2 7 3 35 9 34 43 34 21 35 17 30 34 22 3 35 16 36 34 0 56 5 12 14 11 64 54 38 18 39 Section 8 Exploded Views and Parts Guardian Liqu...

Страница 41: ...CAL CONTROL HSB 2 5L FORD 33 022097 3 WASHER LOCK M6 1 4 34 0C2212 13 SCREW PHTT M4 0 7 X 16 ZYC 35 022264 20 WASHER LOCK 8 M4 36 0C2265 5 SCREW PHTT M4 0 7 X 12 ZYC ITEM PART NO QTY DESCRIPTION 37 02...

Страница 42: ...40 Generac Power Systems Inc Section 8 Exploded Views and Parts Guardian Liquid cooled 25 kW Generator Control Panel Drawing No 0F1378 D...

Страница 43: ...EX M6 X 1 0 G8 YEL CHR 32 0F0653 1 DECAL CONTROL HSB 2 5L FORD 33 022097 3 WASHER LOCK M6 1 4 34 0C2212 9 SCREW PHTT M4 0 7 X 16 ZYC ITEM PART NO QTY DESCRIPTION 35 022264 22 WASHER LOCK 8 M4 36 0C226...

Страница 44: ...9 5 3 22 17 68 15 19 10 38 22 20 HSG 20 3 47 46 4 45 19 0 3 49 48 1 16 39 50 34 35 65 33 18 18 CAP RADIATOR 38 TO 62 58 39 STEPPER MOTOR 17 A A 67 UNITS ONLY 18 23 20 61 Section 8 Exploded Views and P...

Страница 45: ...8940 1 SPACER FLEXPLATE HSB ITEM PART NO QTY DESCRIPTION 33 0E9680 1 GASKET 2 5L FORD EXHAUST MAN 34 0E9609 1 MANIFOLD EXHAUST MACHINED 35 0E9930 1 HEAT SHIELD EXHAUST MANIFOLD 36 049821 3 SCREW SHC M...

Страница 46: ...LVE 12 13 28 1 8 20 33 31 32 17 34 26 6 38 30 16 25 24 18 4 29 15 9 5 27 6 4 CARBURETOR ASSY 0E1028A I N 19 CONVERSION 35 41 OUT 2 PORT L P VAPOR 3 40 1 11 3 40 7 2 6 11 Section 8 Exploded Views and P...

Страница 47: ...CARBURETOR GASKET 21 091526 4 SCREW PPHM M5 0 8 X 12 ZNC 22 049226 4 WASHER LOCK M5 23 026307 1 ELBOW 90D STREET 3 4 24 062522 1 STUD TH 1 4 20 X 3 G2 ZNC FULL 25 022127 1 NUT HEX 1 4 20 STEEL 26 022...

Страница 48: ...Power Systems Inc 3 LOCKTIGHT LOCKTIGHT 7 15 17 8 7 6 18 4 16 LEADS 5 2 9 13 21 19 20 14 10 11 12 30 1 31 Section 8 Exploded Views and Parts Guardian Liquid cooled 25 kW Generator Alternator Drawing N...

Страница 49: ...Y 3 0L HSB LG GEAR 6 0E6076 1 REVCOR FAN 10 75 X 2 W PRESS DIS 7 046526 8 WASHER LOCK M10 8 051755 4 SCREW HHC M10 1 5 X 16 G8 8 9 04576100BK 4 STUD M14 2 0 X 490 G5 ZINC 3 0L FORD 2 5L FORD 04576100B...

Страница 50: ...C M6 1 0 X 16 G8 8 14 022097 4 WASHER LOCK M6 1 4 15 022473 8 WASHER FLAT 1 4 M6 ZINC 16 049813 4 NUT HEX M6 X 1 0 G8 YEL CHR 17 039253 2 SCREW HHC M8 1 25 X 20 G8 8 18 045771 2 NUT HEX M8 1 25 G8 YEL...

Страница 51: ...1 ASSY CARBURETOR LINKAGE ROD 12 0A7106 1 BRACKET STEPPER MOTOR 13 074031 AR LIQUID NEOPRENE 14 029333A 1 TIE WRAP 7 4 X 19 BLK UL 15 022507 2 SCREW HHC 1 4 20 X 1 2 G5 16 022473 2 WASHER FLAT 1 4 ZI...

Страница 52: ...060035 4 SPACER 41 X 75 X 87 ST ZNC ITEM PART NO QTY DESCRIPTION 14 0F0127 1 HOSE UPPER RADIATOR 174MM TAL 15 0E9833 1 HOSE 2 5L FORD LOWER RADIATOR 16 035461 1 BARBED STR 1 4NPT X 3 8 17 069860C 1 HO...

Страница 53: ...Generac Power Systems Inc 51 Section 9 Installation Diagram Guardian Liquid cooled 25 kW Generator Installation Diagram Drawing No 0F1020 A...

Страница 54: ...enerac may deny any and or all warranty coverage or responsibility if your engine or a part component thereof has failed due to abuse neglect improper maintenance or unap proved modifications or the u...

Страница 55: ...to Subsection 4 below Any such emissions related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replaceme...

Страница 56: ...e to the improper installation location in a harsh or saltwater environment or scratched where integrity of paint applied is compromised Failures caused by any contaminated fuels oils coolants or lack...

Отзывы: