Generac Power Systems 004945-1 Скачать руководство пользователя страница 6

 4 

Section 3 — Operation

ATS “HS” Type Transfer Switch

Conductor sizes must be adequate to handle the 
maximum current to which they will be subjected to, 
based on the 75°C column of tables, charts, etc. used 
to size conductors. The installation must comply fully 
with all applicable codes, standards and regulations.

Before connecting wiring cables to terminals, remove 
any surface oxides from the cable ends with a wire 
brush. All power cables must enter the enclosure 
through the knockouts. If not using the knockouts, 
entry must be at or below knockouts. If ALUMINUM 
conductors are used, apply corrosion inhibitor to 
conductors. Tighten terminal lugs to the torque 
values as noted in Section 1.2.2, and on the decal 
located on the inside of the door. After tightening ter-
minal lugs, carefully wipe away any excess corrosion 
inhibitor.

  Use a torque wrench to tighten the conduc-

tors, being sure not to overtighten, or damage 
to the switch base could occur. If not tightened 
enough, a loose connection would result, caus-
ing excess heat which could damage the switch 
base.

Connect power source load conductors to clearly 
marked transfer mechanism terminal lugs as fol-
lows

1.  Connect UTILITY (NORMAL) power source cables 

to circuit breaker.

2.  Connect EMERGENCY (STANDBY) source power 

cables to transfer switch terminals E1, E2.

3.  Connect customer LOAD leads to switch termi-

nals T1, T2.

Conductors must be properly supported, of approved 
insulative qualities, protected by approved conduit, 
and of the correct wire gauge size in accordance with 
applicable codes.

Be sure to maintain proper electrical clearance 
between live metal parts and grounded metal. Allow 
at least 1/2 inch for 100-400 amp circuits.

2.5  

CONNECTING START CIRCUIT
WIRES

Control system interconnections consist of N1 and 
N2, T1 and T2, and leads 23 and 194. Control system 
interconnection leads must be run in a conduit that 
is separate from the AC power lead. Recommended 
wire gauge sizes for this wiring depends on the length 
of the wire, as recommended below:

MAXIMUM WIRE LENGTH 

RECOMMENDED WIRE

  

SIZE

 

460 feet (140m) 

No. 18 AWG.

 

461 to 730 feet (223m) 

No. 16 AWG.

  731 to 1,160 feet (354m) 

No. 14 AWG.

  1,160 to 1,850 feet (565m) 

No. 12 AWG.

NOTE:

When this ATS is used with an air-cooled genera-
tor, the LOAD 1 and LOAD 2 wires are not used.

3.1  

FUNCTIONAL TESTS AND
ADJUSTMENTS

Following transfer switch installation and inter-
connection, inspect the entire installation care-
fully. A competent, qualified electrician should 
inspect it. The installation should comply strictly 
with all applicable codes, standards, and regula-
tions. When absolutely certain the installation is 
proper and correct, complete a functional test of 
the system.

  Perform functional tests in the exact order pre-

sented in this manual, or damage could be done 
to the switch.

IMPORTANT: Before proceeding with functional tests, 
read and make sure all instructions and information 
in this section are understood. Also read the infor-
mation and instructions of labels and decals affixed 
to the switch. Note any options or accessories that 
might be installed and review their operation.

3.2   MANUAL OPERATION

DANGER

  Do NOT manually transfer under load. 

Disconnect transfer switch from all power sourc-
es by approved means, such as the main circuit 
breaker(s).

A manual HANDLE is shipped with the transfer 
switch. Manual operation must be checked BEFORE 
the transfer switch is operated electrically. To check 
manual operation, proceed as follows:

1.  Turn the generator’s AUTO/OFF/MANUAL switch 

to OFF.

2.  Turn OFF both UTILITY (service disconnect cir-

cuit breaker) and EMERGENCY (generator main 
line to circuit breaker) power supplies to the 
transfer switch.

3.  Turn the GENERATOR DISCONNECT SWITCH 

to the OFF position.

4.  Note position of transfer mechanism main con-

tacts by observing the moveable contact carrier 
arm. This can be viewed through the long narrow 
slot in the inside cover of the ATS. The top of the 
moveable contact carrier arm is yellow to be eas-
ily identified.

• Manual operation handle in the UP position - 

LOAD terminals (T1, T2) are connected to UTIL-
ITY terminals (N1, N2).

Содержание 004945-1

Страница 1: ...Automatic Transfer Switch Owner s Manual ATS Service Entrance HS Type Transfer Switch Models 005036 0 100 Amp 250 Volts and 004945 1 200 Amp 250 Volts This manual should remain with the unit...

Страница 2: ...ymbol points out potential fire hazard This symbol points out potential electrical shock hazard GENERAL HAZARDS Any AC generator that is used for backup power if a NORMAL UTILITY power source failure...

Страница 3: ...t may cause dangerous electrical shock Remove all jew elry such as rings watches bracelets etc before working on this equipment If work must be done on this equipment while standing on metal or concre...

Страница 4: ...ches Figure 1 1 are used with a single phase system when the single phase NEUTRAL line is to be connected to a Neutral Lug and is not to be switched Solderless screw type terminal lugs are standard Sw...

Страница 5: ...rom the switch prior to installation 2 3 MOUNTING Mounting dimensions for the transfer switch enclo sure are in this manual Enclosures are typically wall mounted See Installation Diagram Section 5 Han...

Страница 6: ...s for this wiring depends on the length of the wire as recommended below MAXIMUM WIRE LENGTH RECOMMENDED WIRE SIZE 460 feet 140m No 18 AWG 461 to 730 feet 223m No 16 AWG 731 to 1 160 feet 354m No 14 A...

Страница 7: ...osition of the switch by observing the position of the manual operation handle in Figure 3 1 If the handle is DOWN the contacts are closed in the EMERGENCY STANDBY position No further action is requir...

Страница 8: ...governed speed may require adjustment If no load frequency is correct but voltage is not the voltage regulator may require adjustment 3 4 GENERATOR TESTS UNDER LOAD 1 Set the generator s main circuit...

Страница 9: ...79 5mm 7 07 0A 0A6599tv 561mm 22 09 34mm 1 34 KNOCKOUT SUITABLE FOR 1 1 1 4 1 1 2 CONDUIT SIZE KNOCKOUT SUITABLE FOR 3 4 1 CONDUIT SIZE MOUNTING HOLES 6 3mm 0 25 PADLOCK CUSTOMER SUPPLIED LOCATION 0A6...

Страница 10: ...N1 DISCONNECT CONNECTION IN PANELBOARD OR RETROFIT NEW INSTALLATION NEUTRAL BAR GROUND BAR BONDING SOCKET METER UTILITY ALTERNATOR FROM 44 11 STATOR 33 22 GROUND BAR E1 T2 LOCAL ELECTRICAL CODES MEET...

Страница 11: ...TIONAL LOCAL CODES EXISTING WIRES TO PANELBOARD SEE ABOVE NOTE E1 INSULATED SPLICING CONNECTOR OR NEW WIRES CAN BE PULLED FROM ATS PANELBOARD UTILITY METER SOCKET LICENSED ELECTRICIAN AND MUST STATOR...

Страница 12: ...10 Section 5 Electrical Data ATS HS Type Transfer Switch Wiring Diagram Schematic Drawing No 0F0015 A...

Страница 13: ...11 Section 5 Electrical Data ATS HS Type Transfer Switch Wiring Diagram Schematic Drawing No 0F0015 A...

Страница 14: ...B E1 B A 30A 600V D2806 T A 63378 T 63378 T A 63378 T INSIDE LEFT SIDE INSIDE RIGHT SIDE 19 22 50 26 17 16 0A6599tv 0A6599tv 0A6599tv 0A9457 15 43 31 POWER TERMINAL LUG ASSY TIGHTEN ITEM 43 24 30 IN...

Страница 15: ...UTRAL 27 0D3587 1 DECAL FUSE REPLACEMENT 28 0A2595 1 DECAL TERMINAL STRIP 29 0F0776 1 DECAL TEST SEQ 2P TS HS 3R 30 081221 1 DECAL UL LIST HSB 31 045764 6 SCREW HHTT M4 0 7 X 8 BP 32 074908 2 SCREW HH...

Страница 16: ...G ASSEMBLY 35 34 9 28 14 11 31 12 47 1 0A6599tv 0A6599tv 0A6599tv 30A 600V D2806 T 63378 T B B INSIDE RIGHT SIDE INSIDE LEFT SIDE 22 18 4 55 19 46 27 31 11 12 26 17 0C4449A T Replace with UL listed fu...

Страница 17: ...PER HANDLE 24 0E3485 1 DECAL SERVICE DISCONNECT 25 067210A 1 DECAL GROUND LUG NOT SHOWN 26 0A9457 1 DECAL NEUTRAL 27 0D3587 1 DECAL FUSE REPLACEMENT 28 0A2595 1 DECAL TERMINAL STRIP 29 0E7109 1 DECAL...

Страница 18: ...16 Generac Power Systems Inc Section 7 Notes ATS HS Type Transfer Switch...

Страница 19: ...Generac Power Systems Inc 17 Section 7 Notes ATS HS Type Transfer Switch...

Страница 20: ...the prompt that describes the brand name of the generator THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED SPECIFICALLY GENERAC MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILI...

Отзывы: