2.4.1 FUEL 

TANK

Either the generator must share the vehicle engine's fuel tank, 

or install a separate fuel tank for the generator set. All fuel tanks 

installed on the vehicle must be constructed, installed and 

restrained so they comply with applicable codes, standards and 

regulations.
If the generator is to share the vehicle engine's tank, separate 

fuel pickup tubes are required for the engine and the generator. 

The manufacturer recommends that the fuel pickup tube be 2 to 

3 inches (51 to 76 mm) shorter than the vehicle engine's pickup 

tube. This prevents the generator from depleting the entire fuel 

supply during prolonged generator operating periods.

n

 

 Do NOT tee the generator fuel supply line 

into the vehicle engine fuel supply line. If 

this is done, the generator will be starved of 

fuel when both engines are operating at the 

same time. Also, while the vehicle engine is 

not running, generator operation may drain 

the vehicle engine supply line, making it dif-

ficult to start the vehicle engine.

2.4.2  GENERATOR FUEL SUPPLY LINE

2.4.2.1   Rigid Fuel Lines

Those lines used to supply fuel from a tank to the generator must 

comply with applicable codes, standards and regulations. The fol-

lowing general rules apply to rigid fuel lines:

Rigid lines should be of annealed, seamless, drawn aluminum 

• 

or steel.

Lines and fittings must comply with SAE J512F, “Standard 

• 

Automotive Fittings,” or with ANSI B126.26 (latest edition).

Route the fuel line so that at least 2 inches (51 mm) of clear-

• 

ance is maintained between the line and any exhaust system 

parts.

Do not attach electrical wiring to fuel lines. Route the wiring so 

• 

it cannot come into contact with any fuel line.

Route fuel lines so if they leak, fuel does not drip onto any 

• 

electrical or exhaust system parts.

Use nonferrous metal straps without sharp edges to secure 

• 

fuel lines.

2.4.2.2   Flexible Fuel Line

Use an approved flexible length of fuel hose between the generator 

fuel inlet connection and rigid fuel lines. This prevents breaking of 

the line caused by vibration, shifting, settling or movement. The 

following rules apply:

The flexible hose must comply with SAE J30R7, “Standard for 

• 

Fuel and Oil Hose.” It must be approved for use with gasoline 

and low permeability.

The hose should be at least 6 inches (152 mm) longer than 

• 

is needed to prevent the hose from rupturing if the generator 

shifts or settles.

 2.5   EXHAUST SYSTEM

The generator exhaust system must be safely and properly 

installed. Only approved mufflers and other exhaust system parts 

must be used. A properly installed exhaust system must be vapor 

tight, quiet and completely safe.

n

 

 The generator engine gives off DEADLY 

carbon monoxide gas through its exhaust 

system. This dangerous gas, if breathed in 

sufficient concentrations, can cause uncon-

sciousness or even death. Never operate 

the generator set with the vehicle inside 

any garage or other enclosed area. DO 

NOT OPERATE THE GENERATOR IF THE 

EXHAUST SYSTEM IS LEAKING OR HAS 

BEEN DAMAGED. SYMPTOMS OF CARBON 

MONOXIDE POISONING ARE (a) inability to 

think coherently; (b) vomiting; (c) twitch-

ing muscles; (d) throbbing temples; (e) 

dizziness; (f) headaches; (g) weakness; 

and (h) sleepiness. IF FEELING ANY OF 

THESE SYMPTOMS, MOVE INTO FRESH 

AIR IMMEDIATELY. IF SYMPTOMS PERSIST, 

GET MEDICAL HELP. Do not operate the 

generator until its exhaust system has been 

inspected and properly repaired.

n

 

 Never tee the generator engine exhaust pipe 

into the vehicle engine exhaust piping. This 

causes excessive back pressure on the gen-

erator engine. Also, water from one engine 

can damage the other engine.

2.5.1 SPARK 

ARRESTOR

This spark arrestor assembly meets code and standard require-

ments of the U.S. Forest Service. Use only mufflers and parts 

approved by the manufacturer. Any person(s) installing an unap-

proved muffler, or an unapproved exhaust system part, or modify-

ing an exhaust system in any way that might cause a hazard, is 

liable for any damage, injury or warranty expense that might be 

caused by such unapproved installation or modification.
Failure to provide and maintain a spark arrestor may be in violation 

of the law. If this generator is used on any forest covered, brush 

covered or grass covered unimproved land, provide a spark arres-

tor. The vehicle owner or operator must maintain this device in 

good condition. In the state of California, the preceding is required 

by law (Section 4442 of the California Public Resources Code). 

Other states may have similar laws. Federal laws apply on federal 

lands.
When installing/replacing the tailpipe or spark arrestor compo-

nents, verify that the tailpipe has a hole to securely fasten the 

spark arrestor components (see Figures 2.11 and 2.12). Use only 

manufacturer supplied hardware. Substitution of parts may cause 

damage to the screen or a loose fit to the tailpipe.

Installation

Содержание 004709-0

Страница 1: ...This manual should remain with the unit Air cooled Recreational Vehicle Generators Quietpact 40G Models 004709 0 005852 0 Owner s Manual and Installation Instructions...

Страница 2: ...Spark Arrestor 12 3 8 Cleaning the Generator 13 3 9 Battery Maintenance 13 3 10 Major Service Manual 14 3 11 Exercising the Generator 14 3 12 Out of Service Procedure 14 3 13 Adjusting Valve Clearance...

Страница 3: ...t and the safety of all vehicle occupants We strongly recommend that the operator read this manual and thoroughly understand all instructions before using this equipment We also strongly recommend ins...

Страница 4: ...icle while the genset is running unless the vehicle has a working carbon monoxide detector The exhaust system must be installed in accordance with the genset instal lation manual Make sure there is am...

Страница 5: ...ety the generator must be installed and maintained properly Installation always must comply with applicable codes standards laws and regulations Adhere strictly to local state and national electrical...

Страница 6: ...CHECK DAILY AIR FILTER CLEAN PREFILTER EVERY 100 HOURS REPLACE ELEMENT EVERY 250 HOURS OIL OIL FILTER CHANGE EVERY 100 IF NECESSARY EVERY 500 HOURS HOURS REPLACE PLUGS PLUGS EVERY 100 INSPECT CLEAN S...

Страница 7: ...rs require more watts of power or amps of cur rent for starting than for continuous opera tion 1 3 SAFETY Before attempting to use the generator set carefully read the Safety Rules section of this man...

Страница 8: ...47 in Maximum wattage and current are subject to and limited by such factors as fuel Btu content ambient temperature altitude engine condition etc Maximum power decreases about 3 5 for each 1 000 feet...

Страница 9: ...l is available that allows start ing and stopping the generator engine conveniently from inside the vehicle Order part number 0F0429 or 0F0430 a remote panel that includes a Start Stop switch a genera...

Страница 10: ...le manufacturer s instructions The owner operator should become familiar with the vehicle in which this generator is installed Differences exist between vehicles For example some vehicles may use a tr...

Страница 11: ...e generator Do not apply heavy electrical loads for the first two or three hours of operation 2 9 PROTECTION SYSTEMS 2 9 1 LOW OIL PRESSURE SWITCH This switch Figure 2 2 has normally closed N C contac...

Страница 12: ...wipe it dry with a clean lint free cloth 3 Install and tighten the dipstick cap then remove it again The oil level should be at the dipstick Full mark 4 If necessary remove the oil fill cap on the ro...

Страница 13: ...ently if operating the generator in extremely dusty or dirty conditions Use the following procedure Figure 3 2 1 Follow steps 1 3 in Cleaning the Foam Precleaner service the foam precleaner if necessa...

Страница 14: ...the Spark Plug Gap nSparking can occur if the wire terminal does not fit firmly on the spark plug terminal end If necessary re form the wire terminal to obtain a tight fit 3 6 FUEL FILTER Remove and...

Страница 15: ...ttery is to be performed or supervised by personnel knowledgeable of batteries and the required precau tions Keep unauthorized personnel away from batteries Damage will result if the battery connectio...

Страница 16: ...into the spark plug threaded openings Reinstall and tighten the spark plug 6 Remove the battery and store it in a cool dry room on a wooden board Never store the battery on any concrete or earthen fl...

Страница 17: ...lve clearance to make sure it did not change Figure 3 8 Figure 3 8 Tightening Jam Nut CROW S FOOT 3 14 RV GENERATOR SERVICE INTERVAL 50 Hours Clean Spark Arrestor 100 Hours Change Engine Oil filter 10...

Страница 18: ...16 Notes...

Страница 19: ...PART II INSTALLATION INSTRUCTIONS ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION...

Страница 20: ...al start up and maintenance of this equipment is carried out by an Authorized Service Dealer The engine exhaust fumes contain carbon monoxide which can be DEADLY This dangerous gas if breathed in suff...

Страница 21: ...m from the live conductor If the victim is unconscious apply first aid and get immediate medical help Never wear jewelry when working on this equipment Jewelry can conduct electricity resulting in ele...

Страница 22: ...llowing standards booklets latest revi sion are available from the sources indicated 1 NFPA Standard 501C Standard for Recreational Vehicles available from the National Fire Protection Association Bat...

Страница 23: ...21 Figure 1 2 Major Features and Dimensions Drawing No 0D8716 K General Information...

Страница 24: ...ngle iron A typical supporting frame with horizontal support tubing is shown in Figure 2 1 The generator can be installed so that it sits on top of the horizontal support tubing if the vehicle design...

Страница 25: ...f a double thickness of 1 2 inch plywood with the grain of the wood at cross section for added strength Figure 2 5 Figure 2 5 Typical Compartment Construction If constructing a compartment line the ex...

Страница 26: ...aterial is used 2 2 4 ACOUSTICS For additional noise abatement the installer may wish to consider the following Using special sound insulating materials Construction of a special noise abatement compa...

Страница 27: ...25 Figure 2 8 Compartment Floor Cutout Drawing 0G3723 A Installation...

Страница 28: ...lation of a gasoline fuel system Figure 2 10 for a recreational vehicle generator set must comply with applicable codes standards and regulations The entire fuel system must be completely free of leak...

Страница 29: ...d to prevent the hose from rupturing if the generator shifts or settles 2 5 EXHAUST SYSTEM The generator exhaust system must be safely and properly installed Only approved mufflers and other exhaust s...

Страница 30: ...damage the other engine Plan exhaust system installation carefully Comply with all appli cable codes standards and regulations 2 6 ELECTRICAL CONNECTIONS The following general rules apply to electric...

Страница 31: ...the required length and allow extra wire for junc tion box connections Carefully prepare conduit ends to prevent sharp edges from cutting through wiring insulation Route conduit so it does not interfe...

Страница 32: ...30 Figure 2 14 Transfer Switch Isolation Method Figure 2 15 Installation With Isolation Receptacle Installation...

Страница 33: ...ERY COMPARTMENT Install the generator battery in its own vented compartment Place the battery compartment away from any source of heat sparks or flame Provide ventilation openings in the battery compa...

Страница 34: ...of the primer switch will shorten this time 3 Let the engine warm up for about five minutes to allow internal temperatures to stabilize 4 Carefully inspect the engine generator for fuel oil and exhau...

Страница 35: ...system is properly and safely installed ELECTRICAL CONNECTIONS Connections comply with local code requirements and all National Electrical Codes Junction box is properly installed Wiring meets all st...

Страница 36: ...shuts 1 Engine oil level low 1 Check oil and add oil as needed down when the Start Stop 2 Defective low oil pressure switch 2 Replace pressure switch switch is released 3 Defective high temperature sw...

Страница 37: ...Generac Power Systems Inc 35 35 Notes...

Страница 38: ...5 18 1 0I 17 66 85 85 3 3 6 5 4 6 5 4 1 2 1 2 PANEL REMOTE LOP 0 0 SP 0B START STOP SW1 IM SC 14 CH CS 0 0 0 FS FP SM HTO SWITCH HIGH TEMP OIL CLOSES ON HIGH TEMP L1 LIGHT RUN OPTIONAL LOP SWITCH LOW...

Страница 39: ...17 0 15 SW1 SW2 TC 0K 0 0 0 0B 17 18 GT 0 0I 4 2 0 11S 13 0K 4 22S 4 2A 6 2A REGULATOR VOLTAGE ELECTRONIC 14A 15 14A 14A 0F 44 14 0F 17 11P 22P 77 22S 11S 33 66 RED 22P 11P 44 55 6 2 R1 CONNECTOR 17...

Страница 40: ...38 Exploded Views Parts Lists Enclosure Drawing No 0D8352 N...

Страница 41: ...16 X 1 28 0A4456 1 3 8 SPECIAL L WASHER 30 049813 2 NUT HEX M6 X 1 0 ITEM PART NO QTY DESCRIPTION 31 022237 1 WASHER LOCK 3 8 32 022131 2 WASHER FLAT 3 8 M10 33 0C5443 1 BLOCK TERMINAL BATTERY POST 34...

Страница 42: ...40 Exploded Views Parts Lists Generator Drawing No 0D8353 M...

Страница 43: ...T 5 16 19 030231 3 SCREW HHC 5 16 18 X 1 1 2 20 0C3168 1 5 16 SPECIAL LOCK WASHER 21 022259 10 NUT HEX 5 16 18 22 0C8565 2 SCREW SHC M8 1 25 X 18MM 23 0D8048 4 VIBRATION MOUNT 24 083512 6 SCREW HHTT M...

Страница 44: ...42 Exploded Views Parts Lists Control Panel Drawing No 0D8354 H...

Страница 45: ...047411 2 SCREW HHC M6 1 0 X 16mm 17 049226 5 WASHER LOCK M5 18 051716 1 NUT HEX M5 0 8 19 075476 2 SCREW PPHM M4 0 7 x 16mm 20 022264 2 WASHER LOCK 8 M4 21 051715 4 NUT HEX M4 0 7 22 0A2053 1 SCREW HH...

Страница 46: ...44 Exploded Views Parts Lists GN 220 H SH Engine Drawing No 0D8355 AG Part 1...

Страница 47: ...E LINKAGE ITEM PART NO QTY DESCRIPTION 35 091638A 1 SPRING GOVERNOR 36 0G7967 1 SCREW HHTT 5 16 X SEMI GIMLET 37 082025 1 NUT M5 0 8 LOCK 38 092984 1 TOP WRAPPER 39 094820 1 PLUG EXPANSION 40 089739 1...

Страница 48: ...46 Exploded Views Parts Lists GN 220 H SH Engine Drawing No 0D8355 AG Part 2...

Страница 49: ...IL PRESSURE SPRING 24 0A5776 1 11 32 BALL 25 074908 1 M5 FORM SCREW 26 078606 4 M6 1 0 X 12MM SCREW 27 076361 1 GOVERNOR GEAR THRUST WASHER 28 0D2414 6 SCREW HHFC M8 1 25 X 35MM 29 099922 1 SPRING WAS...

Страница 50: ...e to abuse neglect improper maintenance or unapproved modifications or the use of counterfeit and or grey market parts not made supplied or approved by Generac You are responsible for presenting your...

Страница 51: ...ed under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions related part 4 Repair or replacement of any...

Страница 52: ...PLY TO THE FOLLOWING Generac generators that utilize non Generac replacement parts Costs of normal maintenance adjustments installation and start up Repairs or diagnostics performed by individuals oth...

Отзывы: