Maintenance
18
Owner’s Manual for 50 Hz Air-Cooled Generators
Service Schedule
Maintenance Log
Battery inspection and charge check
Dates Performed:
Oil, oil filter, air filter and spark plug replacement
Dates Performed:
Valve Adjustment
Dates Performed:
Table 4-1. Service Maintenance Schedule
Service
Daily If Running Continuously
or Before Each Use
Every
Year
Schedule A
Every Two Years
or 200 Hours
Schedule B
Every Four Years
or 400 Hours
Check Enclosure Louvers for Dirt and Debris *
●
Check Lines and Connections for
Fuel or Oil Leaks
●
Check Engine Oil Level
●
Check for Water Intrusion **
●
Check Battery Condition, Electrolyte Level, and
State of Charge
●
●
●
Replace Engine Oil and Oil Filter †
●
●
Replace Engine Air Filter
●
Check Gap / Replace Spark Plugs
●
Inspect / Adjust Valve Clearance ‡
●
Contact the nearest independent Independent Authorized Service Dealer for assistance if necessary.
* Remove any shrubs or tall grasses which have grown within 3 ft. (0.91m) of the intake and discharge louvers on the sides of the enclosure. Clean any debris (dirt,
grass clippings, etc.) which have accumulated inside the enclosure.
** Verify that all sources of potential water intrusion such as water sprinklers, roof run-off, rain gutter down spouts and sump pump discharges are directed away from
the generator enclosure.
† Change engine oil and filter after the first 25 hours of operation. In cold weather conditions (ambient below 40
º
F / 4.4
º
C), or if unit is operated continuously in hot
weather conditions (ambient above 85
º
F / 29.4
º
C), change engine oil and filter every year or 100 hours of operation.
‡ Check / adjust valve clearance after the first 25 hours of operation.