12
Section 4 – Maintenance
Standby Generator Set
4.1 SERVICE
SCHEDULE
4.1.1
AUTHORIZED OPERATOR
MAINTENANCE FUNCTIONS
4.1.1.1 Every Month or 100 Hours
(whichever comes first)
• Test standby generator system.
• Inspect battery (batteries) and cables.
• Check engine oil level.
• Check gearbox oil level (if so equipped).
• Check engine coolant level.
• Check generator ground connections.
• Test/inspect starting aids.
4.1.1.2 Every Three Months or Every 120
Hours
(whichever comes first)
• Inspect and test fuel system and connections.
• Inspect exhaust system.
• Inspect/test fuel supply system.
4.1.2
AUTHORIZED SERVICE TECHNICIAN
MAINTENANCE FUNCTIONS
4.1.2.1 After First 30 Hours of Operation
• Inspect wiring.
• Change engine crankcase oil and oil filter.
• Inspect engine fan belts.
• Inspect battery (batteries) and cables.
4.1.2.2 Every Six Months or Every 200 Hours
(whichever comes first)
• Change engine oil and filter.
• Lubricate engine controls.
• Service engine air cleaner.
• Service engine fuel filter.
• Inspect AC generator.
• Test engine safety controls.
• Inspect fan belts.
• Check engine coolant level.
• Inspect engine cooling system hoses.
• Check optional starting aids.
• Check battery (batteries).
• Check electrical connections.
• Check/test annunciator panel.
• Perform operational test.
The following
MUST
be performed by an Authorized
John Deere Dealer ONLY.
• Check engine compression.
4.1.2.3 Annually or Every 600 Hours
(whichever comes first)
• Inspect all wiring.
• Test engine starter operation.
• Drain water from fuel tank.
• Retorque fan bolts.
• Drain and refill gearbox (If so equipped.)
The following
MUST
be performed by an Authorized
John Deere Dealer ONLY.
• Check engine valve clearance.
• Test fuel injection nozzles.
• Test injection timing.
4.1.2.4 Every Two Years
• Replace all rubber hoses.
• Replace engine fan belts.
• Inspect the Standby Generator System.
• Drain, flush, refill cooling system.
4.1.2.5 Every 1,000 Operating Hours
• Retorque engine mounting brackets.
The following
MUST
be performed by an Authorized
John Deere Dealer ONLY.
• Inspect engine DC alternator.
• Inspect engine starter.
• Remove/test fuel injection pump.
• Remove/test cooling system thermostat.
4.1.2.6 As Required
• Bleed engine fuel system.
4.2 PERIODIC
MAINTENANCE
A periodic program of scheduled maintenance should
be established and maintained. Such a program,
if adhered to diligently, provides added assurance
that the power system functions properly when it is
needed.
Keeping a “Maintenance Log” is highly recommended.
Such a log should be a continuous record of repairs,
parts replacements, gauge and instrument readings
during operational tests, etc.
The manufacturer recommends that a “Customer
Maintenance Inspection Agreement” be established
between the user of this equipment and the install-
ing Authorized Service Dealer. Under this agreement,
(Part No. 053263), an Authorized Service Technician
performs prestart and engine running tests and
checks at six-month and one-year intervals. Ask an
Authorized Service Dealer about this agreement.
The tasks listed in the “Service Schedule” sec-
tion cover the minimum recommended maintenance
requirements for this equipment.
Содержание 005366-6
Страница 24: ...22 22 Section 5 Exploded Views and Parts Lists Standby Generator Set Mounting Base Drawing No 0G3967 A ...
Страница 26: ...24 Section 5 Exploded Views and Parts Lists Standby Generator Set Base Tank Drawing No 0D5400V G ...
Страница 28: ...26 Section 5 Exploded Views and Parts Lists Standby Generator Set Enclosure Drawing No 0F1261 C Part 1 ...
Страница 30: ...28 Section 5 Exploded Views and Parts Lists Standby Generator Set Enclosure Drawing No 0F1261 C Part 2 ...
Страница 32: ...30 Section 5 Exploded Views and Parts Lists Standby Generator Set H panel Drawing No 0G5375D A ...
Страница 36: ...34 Section 5 Exploded Views and Parts Lists Standby Generator Set Engine Drawing No 0G0300 A ...
Страница 38: ...36 Section 5 Exploded Views and Parts Lists Standby Generator Set Radiator Drawing No 0G3946 C ...
Страница 40: ...38 Section 6 Electrical Data Standby Generator Set Wiring Diagram H 100 Alternator Drawing No 0F8214 B Part 1 ...
Страница 42: ...40 Section 6 Electrical Data Standby Generator Set Wiring Diagram H 100 Alternator Drawing No 0F8214 B Part 3 ...
Страница 43: ...41 Section 6 Electrical Data Standby Generator Set Wiring Diagram H 100 Alternator Drawing No 0F8214 B Part 4 ...
Страница 44: ...42 Section 6 Electrical Data Standby Generator Set Wiring Diagram H 100 Alternator Drawing No 0F8214 B Part 5 ...
Страница 45: ...43 Section 6 Electrical Data Standby Generator Set Wiring Diagram H 100 Alternator Drawing No 0F8214 B Part 6 ...
Страница 46: ...44 Section 6 Electrical Data Standby Generator Set Wiring Diagram H 100 Alternator Drawing No 0F8214 B Part 7 ...
Страница 47: ...45 Section 6 Electrical Data Standby Generator Set Wiring Diagram H 100 Alternator Drawing No 0F8214 B Part 8 ...
Страница 48: ...46 Section 6 Electrical Data Standby Generator Set Wiring Diagram H 200 Alternator Drawing No 0G6978 A Part 1 ...
Страница 49: ...47 Section 6 Electrical Data Standby Generator Set Wiring Diagram H 200 Alternator Drawing No 0G6978 A Part 2 ...
Страница 50: ...48 Section 6 Electrical Data Standby Generator Set Wiring Diagram H 200 Alternator Drawing No 0G6978 A Part 3 ...
Страница 51: ...49 Section 6 Electrical Data Standby Generator Set Wiring Diagram H 200 Alternator Drawing No 0G6978 A Part 4 ...
Страница 56: ...54 Section 7 Installation Diagram Standby Generator Set Drawing No 0G6990 A ...
Страница 57: ...55 Section 7 Installation Diagram Standby Generator Set Drawing No 0G6990 A ...