DeviceNet
4 Correct use
DANGER
Danger of explosion
▶
Danger of death or severe injury.
●
Only use the product in potentially explosive zones confirmed in the declaration of conformity.
WARNING
Improper use of the product!
▶
Risk of severe injury or death.
▶
Manufacturer liability and guarantee will be void.
●
Only use the product in accordance with the operating conditions specified in the contract documentation and this docu-
ment.
The GEMÜ 1242 is designed to be fitted to a GEMÜ valve in order to detect the position of linear actuators optically and elec-
trically. The product has a microprocessor controlled intelligent position sensor as well as an analogue travel sensor system
(potentiometer) and is connected in a force-locking way with the actuator spindle by means of a mounting kit (spring, operat-
ing bush). The valve end positions and the integrated travel sensor can be controlled via the electrical connections.
4.1 Product without special function X or Y
The product is not intended for use in potentially explosive areas.
4.2 Product with special function Y
The product with special function Y is UL/CSA certified and protected against explosion in accordance with ISA 12.12.01 (see
"Technical data").
The product with special function Y can be connected to switches, power supplies, PLC outputs and PLC inputs.
The energy supply must be equipped with a switch or an overcurrent protective device in the system. The switch or overcur-
rent protective device must be placed in a suitable and accessible position and also labelled as an isolating device for the
product with special function Y.
The product user is responsible for providing connections that comply with standards, a locking mechanism, cable compatibil-
ity and warning signs.
Suitable locking clips must be used to secure the circular connectors against becoming unintentionally loose or being
loosened without the use of tools
Installation, operation and servicing must only be carried out by qualified trained personnel.
Do not repair the device yourself if it is faulty. Instead, replace it with an equivalent new device. Repairs must only be carried
out by the manufacturer!
The device must only be used if its materials are resistant against mechanical and/or chemical influences or corrosion under
the respective operating conditions to such a sufficient degree that the explosion protection is not impaired or nullified.
Correct use