RemoDAQ-8017S User’s Manual
3.3 #AAN
Name
:
Analog Data From channel N
Description
:
The command will return the input value from
one of the 8 channels of a specified (AA) module in
the currently configured data format.
Syntax
:
#AAN(cr)
# delimiter character.
AA address of reading module(00~FF)
N channel (0~7)
(cr) is the terminating character, carriage return (0Dh).
Response
:
>(data)(cr)
Syntax error or communication error may get no response.
> delimiter character.
data AI input value.(For data formats, refer
sec
.
1.7).
Example
:
Command
:
#32 Response
:
>+02.455
Read address 03 and channel 2, 02.455