PROGRAMMING PARAMETERS

Error Messages:

FAIL:

 Displays “FAiL”

message in case of sensor

failure, measurement out of

range or hardware fails to

measure input signal.

Err:

 Hardware failure.

Gürbüzo

ğ

lu Elektronik San. ve Tic. Ltd. 

Ş

ti.

http://www.gemo.com.tr.

Çamlıtepe Cad. No:297 / 3-4 Siteler, Ankara, Türkiye

e-posta: [email protected]

Tel: +90-312-3503900, Fax: +90-312-3511117

3

SET

H.hys /

C.hys

0..50 / 

0.0 .. 5.0

o

C (3)

End Prog.

SET

Heat/Cool Hysteresis (

o

C):

PID is active if set to 0
(for H.Hys) (

o

C)

A.hys

1..50 / 

0.0 .. 5.0

o

C (3)

SET

Pb.C

10..130 

o

C

SET

Ct

4..200 sec

SET

oFFS

-100 .. +100 /

-10.0 .. +10.0 

o

C (3)

SET

td

0..10.0 min

SET

+

CodE

Enter 162

SET

UP.L

Lo.L ..

Upper Scale (

o

C) 

SET

Upper limit value for Lo.L,
H.SET and A.SET. Upper Scale value
differs according to the selected
sensor type.

AL.tY

SET

r.ALr/

b.ALr

-100 .. +100 /

 -10.0 .. +10.0 

o

C (3)

SET

ti

0..30.0 min

SET

AL.tY=

 Abs,-Abs

Inpt

Sensor Type (1)

SET

J: J type T/C
K: K type T/C
t: T type T/C
S: S type T/C
r: R type T/C
Pt: Pt100
Pt.0: 0.1

o

C resolution Pt100

h-C

Select

function (2)

SET

HeAt: heating function
Cool: cooling function

Lo.L

Lower Scale ..

UP.L (

o

C) 

SET

Lower limit value for UP.L,
H.SET and A.SET. Lower Scale value
differs according to the selected
sensor type.

P.Err

% 0..100

SET

Determines the duty cycle of OUT output
when “Fail” message is displayed. If 0, OUT is always
OFF. If 100, OUT is always ON, when device “fails”.
Period is Ct.

C.Hys/

H.Hys

not  0

(1) When sensor type is changed, Up.L, Lo.L, H.Set or A.Set may be set to a new value 
     automatically, if any of them violates measuring scale of the selected sensor.
(2) ON-OFF control is the only option for Cooling function 
(3) If sensor type is selected as Pt.0.

Back

Press “Back”

to return to the 

top of  

parameters 

programming 

block

Integral Time:
In minutes. If set to 0,
P, PD is active (integral OFF).

Derivative Time:
In minutes. If set to 0,
P, PI is active (derivative OFF).

Alarm Hysteresis (

o

C)

Proportional Band in (

o

C)

Control period (sec)

Offset Value; Offset is directly added
to the measured value. This feature shall
be used for user calibration. Normally set to 0.

Enter 162 to pass
to parameter prog. mode

Relative or band Alarm
Value. Displayed if AL.ty is
other then Abs or –Abs. 

Press for 2 sec.

Upper Display

C.dLY

0..30 sec

SET

Active only in cooling mode.
Minimum delay before OUT
becomes ON after it becomes OFF. 

Abs,rel,bnd,bn.i

-Abs,-rel,

-bnd,-bn.i 

Alarm Type:
Abs: Absolute         -Abs: Absoloute, invert out
rel: Relative             -rel: Relative, invert out
bnd: band                -bnd: band, invert out
bn.i: band inhibit     -bn.i: band, invert out

h-C=

heat

CodE

Enter 262

to start

auto-tune

SET

Upper Display

“tunE”

flashes

 Before starting Auto-tune, adjust H.SET.
 Auto-tune does not start in “cooling” mode.
 Process value may exceed H.Set during auto-tuning.
 After auto-tuning, control form automatically switches
  to PID mode.
 Auto-tuning is stopped (interrupted) any time by 
  pressing any key. In this case, the parameters before 
  auto-tuning is valid.
 Auto-tuning may not always determine the best values
   for your process.

Factory SET Values:
H.SEt: 100 

o

C

A.SEt: 400 

o

C

Inpt : J
H-C : Heat
H.hys: 0 

o

C

A.hys: 3 

o

C

Pb.C: 30 

o

C

Ct: 4 sec
ti: 5.0 min
td: 1.0 min
UP.L: 400 

o

C

Lo.L: 0 

o

C

oFFS: 0 

o

C

AL.tY : rel
r.ALr: 3 

o

C

C.dLY: 15 sec
P.Err: 0