background image

GEMO

GEMO

GEMO

GEMO

DT109A / DT107A / DT106A / DT105A / DT104A

AUTO-TUNE PID TEMPERATURE CONTROLLER

  Attention, Risk of,   

        High Voltage,

  Double / Reinforced               NOT                        CE Mark

  Danger, Warning            Risk of Electric Shock

          Insulation

        Litter

TECHNICAL SPECIFICATION

Dimensions

: DT109:96x96, DT107:72x72, DT105/DT106:48x96, DT104:48x48mm

Panel Cut-out

: DT109:91x91, DT107:68x68, DT105/DT106:93,5x45,5, DT104:45,5x45,5mm

Display

: 4 Digits 7 Segment (PV), 4 digits 7 Segment (SV)

Sensor Type

: J,K,T,S,R type T/C, Pt100 selectable

Measuring Scale

: -100 .. 600 

o

C, J type T/C, (Inpt=J),   -100 .. 1300 

o

C, K type T/C, (Inpt=k)

  -100 .. 400 

o

C, T type T/C, (Inpt=t),     0 .. 1750 

o

C, S type T/C, (Inpt=S)

  0 .. 1750 

o

C, R type T/C, (Inpt=r),      -100 .. 600 

o

C, Pt100, (Inpt=Pt)

  -99.9 .. 600.0 

o

C, Pt100, (Inpt=Pt.0)

Resolution

: ± 1

 o

C or ± 0.1

 o

C

Accuracy

: ± 0.3 % (Over full scale)

Control Form

: ON-OFF or P, PI, PD, PID - selectable

Out Output

: Relay (NO + NC), 250VAC, 2A, Resistive load, (optional SSR)

Alarm Output

: Relay (NO + NC), 250VAC, 2A, Resistive load, (only NO for DT104)

Heat SET

: Lower Limit .. Upper Limit 

o

C (H.Set)

Alarm SET

: AL.tY = Abs,-Abs; Lo.L .. UP.L 

o

C (A.Set)

  AL.tY = rel, -rel, bnd, -bnd, bn.i, -bn.i; -100 .. +100 / -10.0 .. +10.0 (Pt.0)

Heat Hysteresis

: 0 .. 50 / 0.0 .. 5.0 

o

C (H.Hys); PID is active if set to 0

Alarm Hysteresis

: 1 .. 50 / 0.1 .. 5.0 

o

C (A.Hys)

Proportional Band

: 1 .. 130 

o

C (Pb.C)

Integral Time

: 0 .. 30,0 min. (OFF if set to 0)

Derivative Time

: 0.. 10,0 min. (OFF if set to 0)

Control Period

: 4 .. 200 sec. (Ct)

Offset

: -100..+100 

o

C / -10.0 .. +10.0 

o

C (oFFS)

Heating/Cooling

: Selectable (only ON-OFF control form is active for cooling)

Cold. Junc. Comp.

: 0 .. 50 

o

C (T/C)

Line Comp.

: 10 Ohm max. (3 wire Pt100)

Sensor Failure

:  ALARM output is always OFF, OUT output is active according to P.Err and

  Ct parameters in case of sensor failure, measurement out of range or
  hardware fails to measure input signal (OUT output is OFF if Perr is 0)

Supply Voltage

: 100..240VAC, 50-60Hz or 24VDC/AC (isolation voltage: 40VAC max.)

Power Consumption : < 8VA

Humidity

: 80% up to 30

o

C, then linearly decreases to 50% at 50

o

C (non-condensing)

Altitude

: < 2000 m

EMC

: EN 61000-6-1, EN 61000-6-3 (Only light industrial environment)

Safety

: EN 61010-1; Pollution degree 1, measurement category 

I

, (Only light industrial

  environment, double/reinforced isolated, non-conductive pollution environment)

Protection Class

: IP20; according to EN 60529

Operation Temp.

: 0 .. 50 

o

C

Storage Temperature : -10

o

C .. 60

o

C (no icing)

Weight

: < 0.5 kg

Torque for screwing : Max. 0.5 N.m

WARNING

 

 :  

 if 2 wire Pt100 is used, connect compensation lead

to measuring lead: (DT109 / DT105 / DT106:17-18,
DT107: 13-14, DT104: 10-11)

no: normally open
nc: normally closed

Отзывы: