- 16 -
MAINTENANCE
7 - SENSOR RESISTANCES
The resistance of the sensors must be measured
after they have been disconnected from the control
panel.
8 - PRESSURE SENSOR
The output voltage on the water pressure sensor is measured between the terminals GND (-) and OUT.
Resistance values of the sensors
Temperature
Heating outlet sensor
Boiler return sensor
Flue gas sensor
0.00 °C
32624
10.00 °C
19897
15.00 °C
15711
20.00 °C
12493
25.00 °C
10000
30.00 °C
8056
40.00 °C
5324
50.00 °C
3599
60.00 °C
2483
70.00 °C
1748
80.00 °C
1252
90.00 °C
912
Resistance values of the sensors
Temperature
Outside sensor
-20.00 °C
7578
-15.00 °C
5861
-10.00 °C
4574
-5.00 °C
3600
0.00 °C
2857
5.00 °C
2284
10.00 °C
1840
15.00 °C
1492
20.00 °C
1218
Resistance values of the sensors
Temperature
Heating outlet sensor
Boiler return sensor
Flue gas sensor
100-75-0
GND (-)
OUT
IN (+)
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
Input pressure (bar)
100-74-0
Output voltage (Volt)
Fig. 11