background image

Location

The water heater should be located as close as possible 

to the chimney and to the main use of hot water. This 

location  must  not  be  subject  to  freezing  tempera-

tures. The water heater should be positioned, so that 

there is easy access to the burner, gas control valve, 

and  drain  valve.  It  must  be  located  close  to  a  suit-

able  free-flowing  floor  drain.  Where  a  floor  drain  is 

not adjacent to the water heater, a suitable drain pan 

must be installed under the water heater (see Figure 

8). 

This drain pan should be at least four (4) inches 

(10.2 cm) larger than the diameter of the water heat-

er, and at least one (1) inch (2.5 cm) deep providing 

access to the drain valve. This pan must not restrict 

the flow of ventilation and combustion air. This pan 

must be piped to a suitable drain to prevent damage 

to property in the event of a water leak from the piping, 

the relief valve, or the water heater.

Sooner or later, all water heaters leak. The 

 

manufacturer, based on national building codes, 
has given the necessary instructions to prevent 
damage to the building. Under no circumstances 
is the manufacturer to be held liable for any water 
damage in connection with this water heater. 

This water heater is approved for installation on either 

a  combustible  or  non-combustible  floor.  However, 

should this water heater be installed directly on car-

peting, the carpeting must be protected by a wood or 

metal panel beneath the water heater. This panel must 

extend at least three (3) inches (7.6 cm) beyond the 

width and depth of the water heater. Should the water 

heater  be  installed  in  an  alcove  or  closet,  the  entire 

floor area must be covered by the panel. 

Minimum Clearances

The minimum clearances from combustible material 

for  this  water  heater  are:    Two  (2)  inches  (5.1  cm) 

from  the  sides  and  rear,  four  (4)  inches  (10.2  cm) 

from  the  front,  and  eighteen  (18)  inches  (45.7  cm) 

from the top (see Figure 1).

Combustion and Ventilation Air Supply

In order for the water heater to operate properly, it must 

be supplied with an uninterrupted flow of clean com-

bustion and ventilation air. The area around the water 

heater must always be kept clear and the combustion 

air  intake  holes  at  the  bottom  of  the  water  heater 

must never be blocked. An inadequate supply of air 

to the water heater will produce a bright yellow burner 

flame  causing  sooting  in  the  combustion  chamber, 

on the burner, and in the flue tube. This can result in 

damage to the water heater and serious bodily injury, if 

not corrected.

Combustion  and  ventilation  air  requirements  are  

determined by where the water heater is to be locat-

ed. Water heaters are installed in either open (uncon-

fined) spaces or smaller (confined) spaces, such as 

closets or small rooms. 

4

INSTALLATION INSTRUCTIONS

18''

min.

2'' min.

2'' min.

2'' min.

4'' min.

IMPORTANT 

 

These instructions have been written as a guide for the proper installation and operation of your water heater, 

and the manufacturer of this water heater will not accept any liability where these instructions have not been fol-

lowed. However, for your safety and to avoid damage caused by improper installation, this water heater must be 

installed by a Certified Licensed Professional, and meet all local codes or, in the absence of local codes, CAN/

CGA B149.1 Natural Gas Installation Code or CAN/CGA B149.2 Propane Gas Installation Code, in Canada, and/

or the National Fuel Gas Code, ANSI Z223.1, in the United States.

Before proceeding with the installation instructions:

1)

 Inspect the water heater and its component parts for possible damage. 

DO NOT 

install or attempt to 

repair any damaged component parts. If you detect any damage, contact the dealer where the water 

heater was purchased or the manufacturer listed on the warranty card.

2)

 Verify that the type of gas being supplied corresponds to that which is marked on the rating plate and 

gas control valve of the water heater. 

Figure 1

Содержание GE-IM016En-0312

Страница 1: ...sing property damage personal injury or death DO NOT store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS DO NOT try...

Страница 2: ...f an FVIR technology equipped water heater due to a flammable vapour shutdown is not covered under the terms of the Standard Basic Limited Warranty Safety Information 3 Installation Instructions 4 Loc...

Страница 3: ...tial hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER or WARNING Serious injury or death can occur if you do not follow t...

Страница 4: ...hteen 18 inches 45 7 cm from the top see Figure 1 Combustion and Ventilation Air Supply In order for the water heater to operate properly it must be supplied with an uninterrupted flow of clean com bu...

Страница 5: ...eans of a duct This duct shall be sized accord ing to CAN CSA B149 1 and terminate within 1 foot above and within 2 feet horizontally from the burn er level of the appliance having the largest input I...

Страница 6: ...eing highly flam mable become highly corrosive acid compounds when burned Exposure to such compounds can be hazardous and lead to premature product failure Should the water heater fail due to exposure...

Страница 7: ...not exceed 75 of the vertical vent height in no case exceeding 20 feet 6 1 m All horizontal runs must have a minimum rise of 1 4 inch per foot 21 mm m of run See Figure 8 All joints must be securely...

Страница 8: ...nts of the new water heater This new relief valve must meet all local codes or at a minimum the require ments listed above Never install any other type of valve between the relief valve and the water...

Страница 9: ...tional Fuel Gas Code ANSI Z223 1 in the United States Only new piping with cleanly cut threads may be used together with a suitable sealing compound that is approved for natural and propane gases It i...

Страница 10: ...an the potable water heating system 5 Where water temperature in excess of 140o F 60o C is required for a space heating application a mixing valve must be installed in the potable side of the system T...

Страница 11: ...manufacturer s supplied drafthood been installed correctly L Is the vent piping made of an approved material and sized correctly L Has the venting been installed with 1 4 inch rise per foot 21 mm m of...

Страница 12: ...light any appliance DO NOT touch any electric switch DO NOT use any phone in your building From a neighbour s phone immediately call your gas supplier Follow the gas supplier s instructions 1 STOP Rea...

Страница 13: ...decrease the temperature or coun terclockwise to increase the temperature The reference mark on the temperature dial indicated by a large triangle represents 130 F 54 C see Figure 9 Each mark to the...

Страница 14: ...ass to examine the flames A soft blue flame indicates proper gas combustion A yellow tipped flame indicates poor combustion With a vacuum cleaner remove any dust lint and dirt accumulation on or aroun...

Страница 15: ...ve 5 Connect one end of a garden hose to the water heater drain valve and put the other next to a free flowing drain 6 Open the drain valve by inserting a flat head screwdriver into the slot on the he...

Страница 16: ...rain valve 7 Overflow tube 8 Baffle 9 Flue reducer 10 Drafthood 11 Anode 12 Dip tube 13 Temperature pressure relief valve 1 Burner 2 Inner door Part 1 3 Outer access door 4 Resettable thermal switch 5...

Страница 17: ...ve The flame burns at the orifice Low gas pressure Check with gas utility company Defective gas control valve Replace with new gas control valve The pilot will not light or remain lit No gas Check wit...

Страница 18: ...ater drips from the relief valve Heater stacking Lower gas control valve setting Excessive water pressure Install a pressure reducing valve Thermal expansion in a closed water system Install an expans...

Страница 19: ...age caused by not having the water heater installed adjacent to a free flowing drain in the event of water leakage 10 If the heater is operated at water temperatures exceeding the maximum setting of t...

Страница 20: ...___________________________________________________________ ________________________________________________________________________________ ___________________________________________________________...

Отзывы: