1080 North Crooks Road, Clawson, MI 48017  •  Phone: 248-435-0700 

A.1: Troubleshooting for 952 QD

Troubleshooting describes common problems 

that may occur when installing the LDT and offers 

possible solutions to these problems. If, after 

reading this appendix, you are unable to resolve a 

problem, contact factory. Troubleshooting is divided 

into the following two groups:

•  General Checks

•  Power Supply

General Checks

Make sure that the magnet is located within 

the LDT’s active stroke area. Captive magnet 

assemblies should be positioned so that they can 

move freely over the entire area of the active stroke 

without binding or pushing on the rod. Non-captive 

magnet assemblies should be situated so that the 

magnet is no farther than 0.2" from the rod at any 

point in the magnet assembly’s movement.

NOTE

: Ferromagnetic material (material readily 

magnetized) should be located no closer than 0.25" 

from the magnet or LDT rod end. This includes 

mounting brackets, magnet spacers, magnet 

brackets, and mounting screws. Ferromagnetic 

material can distort the magnetic field, causing 

adverse operation or failure of the LDT.

Check all LDT wires for continuity and/or shorts. It 

is preferable that the cable between the LDT and 

the interface device be one continuous run. If you 

are using a junction box, it is highly recommended 

that the splice junction box be free of AC and/or 

DC transient-producing lines. The shield should 

be carried through the splice and terminated at the 

interface device end.

Unipolar Power Supply Check

This section will help you to determine if your power 

supply is adequate for the LDT to operate properly, 

or if the LDT’s cable has a short or open.

In order for the BlueOx to operate properly, the 

external power supply must provide a level between 

+11 to +28 VDC. A power supply providing voltage 

above this specified range may damage the LDT. A 

power supply providing power below this specified 

range will not be sufficient to power the LDT. When 

powering more than one BlueOx on a single power 

supply, remember that each BlueOx requires three 

(3) watts of power maximum (1 watt typical). The 

amount of current draw will vary based on the input 

voltage used. To calculate the current draw for a 

particular LDT, divide the LDT wattage by the input 

voltage. For example, 3 watts divided by 24 VDC 

equals 125mA.

If your LDT is not operating properly, the LDT’s 

cable may have an open or short, or the power 

supply is not supplying sufficient power. To verify 

this, perform the following steps:

1. Turn the power supply off.

2. Remove the mating connector from the LDT

3. Turn the power supply on.

4. Using a digital voltmeter, check pins B (GND) 

and C (+) from the mating end of the cable for a 

level b11 and +28 VDC.

NOTE:

 LDTs with potted cable assemblies should 

be checked for proper voltage at the power supply 

terminals. This cable assembly cannot be removed 

from the LDT.

If reading is b11 and +28 VDC, turn power 

supply off and go to step 7. If reading is below +11 

VDC, either your power supply is not providing 

Appendix A: Troubleshooting

24

Содержание 952 BlueOx

Страница 1: ...952 BlueOx Linear Displacement Transducer ABSOLUTE PROCESS CONTROL KNOW WHERE YOU ARE REGARDLESS Linear Displacement Transducers Installation Manual Series 952...

Страница 2: ...ntents or selected pages of this manual All rights to the contents of this manual are reserved by AMETEK BlueOx is a registered trademark of GEMCO The GEMCO Model 952 BlueOx is a Magnetostrictive Line...

Страница 3: ...Toll Free 800 635 0289 Email apt sales ametek com Web www ametekfactoryautomation com Figure 1 1 BlueOx Linear Displacement Transducer Drawing D0234200 1 1 Dimension Drawing for all 952 LDTs 3...

Страница 4: ...ay damage the LDT and will void your warranty To tighten the LDT within the bracket use the 1 75 hex mounting base on the head assembly Chapter 2 Installing the LDT If the length of the LDT s rod end...

Страница 5: ...not be closer than 2 0 from the base of the LDT s hex head when the piston rod is fully retracted In instances where space restraints exist it may be required to countersink the magnet into the piston...

Страница 6: ...e inserting the LDT The end cap should contain a 3 4 16 UNF 2B threaded hole Screw the LDT into this hole using the threads protruding from the LDT s hex mounting base WARNING Do not use the blue alum...

Страница 7: ...il SAE J1926 1 OPTIONAL ROD BUSHING MAGNET SPACER O RING SEAL CABLE NUT STANDARD 4 HOLE MAGNET 0 5 BORE MINIMUM A 004 A 008 A 125 125 PITCH DIA REF SEE NOTE 4 094 MAX R 015 MAX 008 004 R RECOMMENDED M...

Страница 8: ...e and terminated at the interface device end NOTE When grounding the LDT a single earth ground should be connected to the power supply common circuit ground The LDT power supply common pin B should be...

Страница 9: ...ot lose programmed parameters on power loss The analog output is referenced to the analog common terminal and should not be referenced to any of the other common terminals To wire the 952A voltage LDT...

Страница 10: ...8 2 1 6 4 1 White White Blue Stripe Power Supply Common 2 Brown Blue White Stripe No Connection 3 Gray White Orange Stripe Position Common 4 Pink Orange White Stripe Position Output 5 Red White Green...

Страница 11: ...erential RS 422 output The maximum cable length for the differential digital LDTs is 1 500 feet To initiate a start pulse an external device is used This start pulse should be 1 0 microsecond in durat...

Страница 12: ...0 2 MICROSECONDS MINIMUM WIDTH OF PULSE IS PROPORTIONAL TO DISTANCE BETWEEN MAGNET AND HEX HEAD OUTPUT PULSE WITHIN 50 NANOSECONDS AFTER INTERROGATION TO DISTANCE BETWEEN MAGNET AND HEX HEAD OUTPUT PU...

Страница 13: ...t The maximum cable length for differential LDTs is 1 500 feet To initiate a start pulse an external device is used This start pulse should be a minimum of 1 0 microsecond in duration Within 50 nanose...

Страница 14: ...GATION 15 TO 26 VDC POWER SUPPLY ORANGE NO CONNECTION PINOUT FOR STANDARD CIRCULAR CONNECTOR AT TRANSDUCER HEAD GREEN YELLOW PURPLE NO CONNECTION NO CONNECTION 15 VDC FOR BIPOLAR POWER SUPPLY POWER SU...

Страница 15: ...his feature is hardware specific and must be specified at time of order The differential feature allows the distance between two magnets to be measured The magnets must remain within the active stroke...

Страница 16: ...lication Note Overview This application note will attempt to clarify the type of signals coming out of and going into the 952QD quadrature probe Inputs The quadrature probe has two inputs the Zero and...

Страница 17: ...e and signal pins The value of the termination resistor is by RS 422 specifications typically 100 ohms However some receivers will work with greater resistance values and some with no termination resi...

Страница 18: ...y Connections including grounding and shielding LDT Input Output Connections Power Supply Ground Connections The BlueOx standard cable is Alpha XTRA GUARD 2 25110 SUPRASHIELD a multi conductor cable w...

Страница 19: ...ero position In probes with volatile storage the zero point will The type of signal needed for the Burst Zero inputs E Sinking PLC Sourcing Outputs C Sourcing PLC Sinking Outputs T TTL See Appendix C...

Страница 20: ...1080 North Crooks Road Clawson MI 48017 Phone 248 435 0700 Figure 4 2 952QD Wiring Diagram Drawing E0237900 4 6 952 QD Wiring Diagram 20...

Страница 21: ...Toll Free 800 635 0289 Email apt sales ametek com Web www ametekfactoryautomation com Figure 4 3 Input Signal Connections for 952 QD LDT Drawing E0237700 21...

Страница 22: ...QD LDT Drawing E0237600 Rt is the termination resistor typically used for differential connections If these termination resistors are not internal to the controller they should be installed externall...

Страница 23: ...ses at a fixed rate of speed The frequency or pulse rate of the 952QD is factory set to 10KHZ 1 00MHZ consult part numbers for your model The input to the PLC or display will determine the frequency n...

Страница 24: ...rough the splice and terminated at the interface device end Unipolar Power Supply Check This section will help you to determine if your power supply is adequate for the LDT to operate properly or if t...

Страница 25: ...cable between the power supply and the LDT Check for continuity from one end of the cable to the other Also verify that no shorts exist between pins 7 Reconnect the mating connector to the LDT 8 Turn...

Страница 26: ...terface device end Unipolar Power Supply Check This section will help you to determine if your power supply is adequate for the LDT to operate properly or if the LDT s cable has a short or open In ord...

Страница 27: ...ansient producing lines The shield should be carried through the splice and terminated at the interface device end Unipolar Power Supply Check This section will help determine if the power supply is a...

Страница 28: ...r short or the power supply is not supplying sufficient power To verify this perform the following steps 1 Turn the power supply off 2 Remove the mating connector from the LDT 3 Turn the power supply...

Страница 29: ...the active measuring range will be 2 5 less than the specified stroke due to the 2 5 magnet to magnet separation distance requirement Null Zone X _ Standard 2 inch Null N Insert non standard Null over...

Страница 30: ...es D _ Insert non standard Dead Zone over 2 5 inches If option E environmental connector is selected mating connector and or pigtail must be ordered separately NOTE 1 On unsupported stroke lengths gre...

Страница 31: ...E F7 M1 D N Output Resolution Cycles per inch maximum internal resolution is 0 001 inches 1000 standard available range is 0001 through 9999 Input Type E Sinking typically used with sourcing output t...

Страница 32: ...00 50 8 mm standard Head Enclosure 3 76 20 mm high with 1 75 44 45 mm diameter hex and cover are NEMA 4 Electrical Specifications Input Voltage Unipolar Bipolar Analog 13 5 to 26 4 VDC Digital 13 5 to...

Страница 33: ...ion S Only Output May Vary by 0 1 when Subjected to Severe Levels of Electrical Noise Digital Specification Update Time Controller Dependent Digital Output CP RS 422 Control Pulse VP RS 422 Pulse Widt...

Страница 34: ...to derive position Input Type Used on 952 QD to determine input type for Burst and Zero modes ie sinking sourcing or TTL Internal Interrogations Pulses generated by the LDT usually to initiate a puls...

Страница 35: ...ls Return Stop Pulse A pulse generated by the BlueOx to determine the location of the magnet assembly on the rod end Rod A stainless steel tube on which the magnet assembly travels RS422 Differential...

Страница 36: ...17 Copyright 2005 by AMETEK FACTORY AUTOMATION All Rights Reserved Made in the USA Other Products 1080 North Crooks Road Clawson MI 48017 Phone 248 435 0700 Toll Free 800 635 0289 Email apt sales amet...

Отзывы: