1080 North Crooks Road, Clawson, MI 48017  •  Phone: 248-435-0700 

4.1: Quadrature Output

A new method of interfacing magnetostrictive 

transducers offers customers an interface as 

common as analog with the speed and accuracy of 

pulsed type signaling. The GEMCO 952 QD Linear 

Transducer provides quadrature output directly from 

the transducer to the controller (see drawing below). 

The output from the transducer can be wired directly 

to any incremental encoder input card, without 

the need for a special converter module or PLC 

interface card designed specifically for use with a 

pulse output magnetostrictive transducer.

The quadrature output provides absolute position 

data in engineering units. This means that the 

need for the calibration constant (wire speed) 

programming has been removed, thereby 

eliminating the possibility of having an improperly 

calibrated system. The output signal wires are 

driven by differential RS-422 line drivers, similar 

to the drivers used in most magnetostrictive pulse 

type transducers, providing a high degree of noise 

immunity.

A unique feature of this transducer is a Burst mode 

of operation. An input on the transducer triggers 

a data transfer of all the incremental position data 

relative to the transducer’s absolute zero position. 

This can be used to achieve absolute position 

updates when power is restored to the system or 

anytime an update is needed to re-zero or home 

the machine. Additionally, another input to the 

transducer can be used to establish a Zero position 

for the transducer.

4.2: Signal Connection 

Application Note

Overview

This application note will attempt to clarify the type 

of signals coming out of and going into the 952QD 

quadrature probe.

Inputs

The quadrature probe has two inputs, the Zero and 

Burst inputs. These inputs are single ended. That 

is, the connection for each input consists of only 

one wire, the corresponding signal wire. For these 

(single ended) inputs, the signal is measured with 

reference to the power supply ground, which is also 

sometimes referred to as common.

The quadrature probe is available with 24 

VDC level signal thresholds or TTL level thresholds. 

The signal voltage level required to activate the 

input for the +24 VDC level signals is proportional 

to the power supply voltage that the customer is 

supplying to the probe. This level is approximately 

41% of the power supply voltage. For example; if 

the power supply voltage powering the probe is 

e24 VDC, the threshold voltage would be 

about 9.84 volts.

The TTL level threshold signals are activated when 

these inputs exceed the typical TTL level threshold, 

which is 2.0 VDC.

Additionally, for the +24 VDC level signals, the 

customer can specify either a sourcing or sinking 

type of input. A sourcing input type is pulled high 

internal to the probe. To activate a sourcing input, 

the customer must pull the signal lower than the 

threshold voltage to activate the input. A sourcing 

input is usually driven by a sinking output or a 

switch connected to ground. A sinking input type is 

pulled low internal to the probe. To activate a sinking 

input, the customer must pull the signal higher than 

the threshold voltage to activate the input. A sinking 

input is usually driven by a sourcing output or a 

switch connected to the power supply.

Chapter 4: 952 QD Overview

16

Содержание 952 BlueOx

Страница 1: ...952 BlueOx Linear Displacement Transducer ABSOLUTE PROCESS CONTROL KNOW WHERE YOU ARE REGARDLESS Linear Displacement Transducers Installation Manual Series 952...

Страница 2: ...ntents or selected pages of this manual All rights to the contents of this manual are reserved by AMETEK BlueOx is a registered trademark of GEMCO The GEMCO Model 952 BlueOx is a Magnetostrictive Line...

Страница 3: ...Toll Free 800 635 0289 Email apt sales ametek com Web www ametekfactoryautomation com Figure 1 1 BlueOx Linear Displacement Transducer Drawing D0234200 1 1 Dimension Drawing for all 952 LDTs 3...

Страница 4: ...ay damage the LDT and will void your warranty To tighten the LDT within the bracket use the 1 75 hex mounting base on the head assembly Chapter 2 Installing the LDT If the length of the LDT s rod end...

Страница 5: ...not be closer than 2 0 from the base of the LDT s hex head when the piston rod is fully retracted In instances where space restraints exist it may be required to countersink the magnet into the piston...

Страница 6: ...e inserting the LDT The end cap should contain a 3 4 16 UNF 2B threaded hole Screw the LDT into this hole using the threads protruding from the LDT s hex mounting base WARNING Do not use the blue alum...

Страница 7: ...il SAE J1926 1 OPTIONAL ROD BUSHING MAGNET SPACER O RING SEAL CABLE NUT STANDARD 4 HOLE MAGNET 0 5 BORE MINIMUM A 004 A 008 A 125 125 PITCH DIA REF SEE NOTE 4 094 MAX R 015 MAX 008 004 R RECOMMENDED M...

Страница 8: ...e and terminated at the interface device end NOTE When grounding the LDT a single earth ground should be connected to the power supply common circuit ground The LDT power supply common pin B should be...

Страница 9: ...ot lose programmed parameters on power loss The analog output is referenced to the analog common terminal and should not be referenced to any of the other common terminals To wire the 952A voltage LDT...

Страница 10: ...8 2 1 6 4 1 White White Blue Stripe Power Supply Common 2 Brown Blue White Stripe No Connection 3 Gray White Orange Stripe Position Common 4 Pink Orange White Stripe Position Output 5 Red White Green...

Страница 11: ...erential RS 422 output The maximum cable length for the differential digital LDTs is 1 500 feet To initiate a start pulse an external device is used This start pulse should be 1 0 microsecond in durat...

Страница 12: ...0 2 MICROSECONDS MINIMUM WIDTH OF PULSE IS PROPORTIONAL TO DISTANCE BETWEEN MAGNET AND HEX HEAD OUTPUT PULSE WITHIN 50 NANOSECONDS AFTER INTERROGATION TO DISTANCE BETWEEN MAGNET AND HEX HEAD OUTPUT PU...

Страница 13: ...t The maximum cable length for differential LDTs is 1 500 feet To initiate a start pulse an external device is used This start pulse should be a minimum of 1 0 microsecond in duration Within 50 nanose...

Страница 14: ...GATION 15 TO 26 VDC POWER SUPPLY ORANGE NO CONNECTION PINOUT FOR STANDARD CIRCULAR CONNECTOR AT TRANSDUCER HEAD GREEN YELLOW PURPLE NO CONNECTION NO CONNECTION 15 VDC FOR BIPOLAR POWER SUPPLY POWER SU...

Страница 15: ...his feature is hardware specific and must be specified at time of order The differential feature allows the distance between two magnets to be measured The magnets must remain within the active stroke...

Страница 16: ...lication Note Overview This application note will attempt to clarify the type of signals coming out of and going into the 952QD quadrature probe Inputs The quadrature probe has two inputs the Zero and...

Страница 17: ...e and signal pins The value of the termination resistor is by RS 422 specifications typically 100 ohms However some receivers will work with greater resistance values and some with no termination resi...

Страница 18: ...y Connections including grounding and shielding LDT Input Output Connections Power Supply Ground Connections The BlueOx standard cable is Alpha XTRA GUARD 2 25110 SUPRASHIELD a multi conductor cable w...

Страница 19: ...ero position In probes with volatile storage the zero point will The type of signal needed for the Burst Zero inputs E Sinking PLC Sourcing Outputs C Sourcing PLC Sinking Outputs T TTL See Appendix C...

Страница 20: ...1080 North Crooks Road Clawson MI 48017 Phone 248 435 0700 Figure 4 2 952QD Wiring Diagram Drawing E0237900 4 6 952 QD Wiring Diagram 20...

Страница 21: ...Toll Free 800 635 0289 Email apt sales ametek com Web www ametekfactoryautomation com Figure 4 3 Input Signal Connections for 952 QD LDT Drawing E0237700 21...

Страница 22: ...QD LDT Drawing E0237600 Rt is the termination resistor typically used for differential connections If these termination resistors are not internal to the controller they should be installed externall...

Страница 23: ...ses at a fixed rate of speed The frequency or pulse rate of the 952QD is factory set to 10KHZ 1 00MHZ consult part numbers for your model The input to the PLC or display will determine the frequency n...

Страница 24: ...rough the splice and terminated at the interface device end Unipolar Power Supply Check This section will help you to determine if your power supply is adequate for the LDT to operate properly or if t...

Страница 25: ...cable between the power supply and the LDT Check for continuity from one end of the cable to the other Also verify that no shorts exist between pins 7 Reconnect the mating connector to the LDT 8 Turn...

Страница 26: ...terface device end Unipolar Power Supply Check This section will help you to determine if your power supply is adequate for the LDT to operate properly or if the LDT s cable has a short or open In ord...

Страница 27: ...ansient producing lines The shield should be carried through the splice and terminated at the interface device end Unipolar Power Supply Check This section will help determine if the power supply is a...

Страница 28: ...r short or the power supply is not supplying sufficient power To verify this perform the following steps 1 Turn the power supply off 2 Remove the mating connector from the LDT 3 Turn the power supply...

Страница 29: ...the active measuring range will be 2 5 less than the specified stroke due to the 2 5 magnet to magnet separation distance requirement Null Zone X _ Standard 2 inch Null N Insert non standard Null over...

Страница 30: ...es D _ Insert non standard Dead Zone over 2 5 inches If option E environmental connector is selected mating connector and or pigtail must be ordered separately NOTE 1 On unsupported stroke lengths gre...

Страница 31: ...E F7 M1 D N Output Resolution Cycles per inch maximum internal resolution is 0 001 inches 1000 standard available range is 0001 through 9999 Input Type E Sinking typically used with sourcing output t...

Страница 32: ...00 50 8 mm standard Head Enclosure 3 76 20 mm high with 1 75 44 45 mm diameter hex and cover are NEMA 4 Electrical Specifications Input Voltage Unipolar Bipolar Analog 13 5 to 26 4 VDC Digital 13 5 to...

Страница 33: ...ion S Only Output May Vary by 0 1 when Subjected to Severe Levels of Electrical Noise Digital Specification Update Time Controller Dependent Digital Output CP RS 422 Control Pulse VP RS 422 Pulse Widt...

Страница 34: ...to derive position Input Type Used on 952 QD to determine input type for Burst and Zero modes ie sinking sourcing or TTL Internal Interrogations Pulses generated by the LDT usually to initiate a puls...

Страница 35: ...ls Return Stop Pulse A pulse generated by the BlueOx to determine the location of the magnet assembly on the rod end Rod A stainless steel tube on which the magnet assembly travels RS422 Differential...

Страница 36: ...17 Copyright 2005 by AMETEK FACTORY AUTOMATION All Rights Reserved Made in the USA Other Products 1080 North Crooks Road Clawson MI 48017 Phone 248 435 0700 Toll Free 800 635 0289 Email apt sales amet...

Отзывы: