GEM WLP-150 Скачать руководство пользователя страница 6

Copyright © All Rights Reserved.  P-MU-WLP-150   Published: 2021.03.10

6

13.8VDC / 1.5Amp

GML-800 (Lock)

Fail-Secure Mode

IN+
IN -

N.O.1

COM.1

N.C.1

PB

PB

REED

REED

N.O.2

COM.2

N.C.2

COM. N.O.

COM.

N.O.

COM.

N.O.

COM.

N.O.

N.C.

COM.

N.O.

N.C.

POWER
SUPPLY

DG-15LD

TLM-300S

WLP-150 Wiring Diagram (2)

Lock Status LED Indicator

Door Status Output:

N.O. contact when door close
N.C. contact when door open

Anti-tailgating function for Relay 2 only

Digital Keypads

Problem

No power

Installation position 
is incorrect

Solution

Possible Cause

Unable to 
    unlock

No sensor 
    output 

No door status
output

No lock status 
output

Check that the power supply is connected and works properly 
Make sure access control relay contact is wired correctly (N.O.)
Check door opening time is not too long (the interval time is 30 seconds)

Check installation position/alignment is correct
Check door gap does not exceed maximum recommended distance 
(Package including washers for minimizing gap)

Check installation position/alignment is correct

Check installation position/alignment is correct
Make sure lock status wires are connected to wireless power source

   Insufficient 
power output

Transmitter

Unit

Receiver 

Unit

(Transmitter)

(Both)

(Both)