6.6 Electrical data
Power consumption:
AC operation
Pull in
DN 15 - 20
125 VA
DN 25 - 50
400 VA
Hold in
DN 15 - 20
12 VA
DN 25 - 50
30 VA
DC operation
Pull in
DN 15 - 20
35 W
DN 25 - 50
70 W
Hold in
DN 15 - 20
7 W
DN 25 - 50
18 W
Permissible voltage toler-
ance:
±10 % to VDE 0580
Duty cycle:
Continuous duty
Wiring note:
Special wiring on request. When using electronic switches and additional wiring, carefully design
out any potential residual currents upon installation.
Installation note:
Please note: The DC solenoid is designed for unsmoothed voltages, e.g. as obtained from a bridge
rectifier.
GEMÜ 225
www.gemu-group.com
9 / 24
6 Technical data
Содержание 225 DN 10