![Geko 12V 4000 G 41 Скачать руководство пользователя страница 102](http://html1.mh-extra.com/html/geko/12v-4000-g-41/12v-4000-g-41_operating-instructions-manual_2206052102.webp)
44
Cooling System, General, HT Circuit
HT cooling pump relief bore check
1. Check relief bore for oil and water discharge.
2. Stop engine ( Page 3 5)and disable engine
start.
3. Clean the relief bore with a wire if it is dirty.
Permissible water discharge: up to 10 drops
per hour;
Permissible oil discharge: up to 5 drops
per hour.
4. If discharge exceeds the specified limits: Contact
Service.
M015403/00E 02-09
© MTU
www.generent.ru
Содержание 12V 4000 G 41
Страница 22: ...II Table of Contents M015403 00E 02 09 MTU w w w g e n e r e n t r u...
Страница 30: ...II Table of Contents M015403 00E 02 09 MTU w w w g e n e r e n t r u...
Страница 38: ...8 Maintenance Schedule Application Group 3A M015403 00E 02 09 MTU w w w g e n e r e n t r u...
Страница 40: ...II Table of Contents M015403 00E 02 09 MTU w w w g e n e r e n t r u...
Страница 116: ...58 Engine Governor Electronic Control System M015403 00E 02 09 MTU w w w g e n e r e n t r u...
Страница 117: ...Table of Contents I 7 Annex 7 1 Abbreviations 7 1 7 2 Index 7 3 M015403 00E 02 09 MTU w w w g e n e r e n t r u...
Страница 118: ...II Table of Contents M015403 00E 02 09 MTU w w w g e n e r e n t r u...
Страница 124: ...w w w g e n e r e n t r u...