Chapter 1 - Product Specifications
Product Specifications
Overview
The Geist Upgradeable (GU) PDU gives data center managers the flexibility to install the intelligence
required today, with the option to upgrade technology as needs evolve. From basic power to power
monitoring, the Geist Upgradeable product line adapts to a business' needs now and in the future.
To establish this upgrade path, Geist engineers took the robust PDU design and incorporated an
Interchangeable Monitoring Device (IMD). Geist PDUs last for many years, and with the IMD design,
businesses will be able to upgrade their PDUs to newer monitoring technologies in the future without
having to replace the entire PDU. The hot-swappable IMD can be changed out in a few simple steps,
without interrupting power to critical servers.
Environmental
The operational environmental limits pertaining to Temperature, Humidity and Elevation are
as defined below.
Temperature
Table 1-1
Temperature Limits
Minimum
Maximum
Operating
10°C (50°F)
45°C (113°F) (standard models)
60°C (140°F) (high temperature models)
Storage
-25°C (13°F)
65°C (149°F)
Humidity
Table 1-2
Humidity Limits
Minimun
Maximum
Operating
5%
95% (non-condensing)
Storage
5%
95% (non-condensing)