Installation Procedures

The RAC10 relies on the building installation for protection from overcurrent. A Listed circuit breaker is required in the building 
installation. The circuit breaker should be rated at 15 or 20 Amps. Install the RAC10 so the input plug may be disconnected 
for service.

18 ga. 

hanger 

wire

Four #10 2” 
wood screws 

Installation Precaution Guidelines

•  Read and save these installation instructions. 

•  Install the equipment such that the amount of airfl ow required for safe operation of 

equipment is not restricted.

•  The equipment relies on the building installation for over current protection. 

•  A listed 20 amp circuit breaker is required in the building installation. 

•  Model RAC10 is equipped with a grounded pin plug, reliable earth ground should 

be maintained. 

•  Install the equipment so the input plug or appliance coupler may be disconnected 

for service.

•  Caution: Disconnect all power before performing any type of maintenance such as 

cleaning and dusting.

•  Contact Geist Customer Service for any service issue at 800-432-3219.

Specifi cations

Input:

 120 VAC, 50/60 Hz, 160 

watts, 10FT Cord, NEMA 5-15P

Fan Speed Regulation:

 Automatic 

temperature control with Ethernet 
remote adjustment

Airfl ow:

1100 CFM Maximum

Environmental Monitoring:

 Ethernet  

remote access and alarms, up to 
four RJ12 Temperature sensors with 
20 FT cords (two included)

Regulation: 

Temperature based, 

range: 60 to 120F

Physical: 

23.75 L x 14.00 W x 

3.52 H

Network: 

HTTP / HTTPS / SNMP 

/ DHCP

Regulatory: 

UL, cUL 507, FCC 

Part 15 Class A

Warranty

2 Years

System Components

Wall or ceiling mount for automated heat exhaust and critical monitoring / alerts. 

Optional SC System for room air supply required for some room and load conditions.

Temp Sensor Port (4)

Internal Temp Sensor

Cable Tie Loop

Power Input

Ethernet RJ45

Optional Duct Kit

Redundant Fans

Wall Stud Mounting Flange 

Ceiling  Mount Wire Hanger Loop  