9. Electrical connections and safety instructions
H
Caution: Important installation instructions.
Please follow all instructions since incorrect installation can lead to
the destruction of the motor and the switching unit.
H
Before commissioning, all connections must be made correctly.
Drive and electronic control connections
The 230 V connection is coded in such a way that it is impossible to
insert it incorrectly into the 12 V connections. The maximum distance
between drive and electronics must not exceed 2,5 m.
Electric mains
H
Work on the electrical installation may only be
carried out by a qualified electrician.
Connecting cables with plug connectors of the Hirschmann Company
are tested and approved with couplings of the Hirschmann Company.
I
The battery is not plugged in on delivery. Before
commissioning, connect the connectors in the
battery compartment. Please note the warning in
chapter 10 „Battery replacement“.
12V connections
I
Wires and contacts which are marked with nc (not connected) have
no function. Wires without a function are cut at the end of the sheath
(green-yellow or orange and grey).
Connection of operating and setting switch
H
Danger of electric shock!
Potential-free contacts must be used for opera-
tion and setting.
Only the setting switch M56F155 may be used for the setting
(see spare parts).
Do not connect plug connectors that are used for 230V to 12V
connections.
If 230V is connected incorrectly to 12V connections, the device will
be destroyed and all 12V circuits will be put under mains voltage.
H
Incorrect connection can lead to death and
serious injuries due to electric shock.
A
B
C
A
B
C
L
N
PE
green-yellow
blue
brown
PE
N
nc
nc
L
grey
blac
k
grey
blue
brown
green/ yellow
blac
k
grey
Setting switch
Operating switch
blue
brown
green/ yellow
blac
k
up
down
12
V
nc
up
down
12
V
1
Encoder
with hall sensor
2
Motor/brake
3
LED display
4
Operating switch
5
Central fire alarm
system
6
Mains connection