background image

21

80951C_MHW_GF_VEDO EL35CT-EL57CT_03-2010_ENG

Model

GF_VEDO EL35CT

GF_VEDO 57CT

Power supply

Power supply

24Vdc, ±25% (3-pin screw-type female connector)

Max consumption

without integrated I/O

240mA, 5W

480mA, 8,5W

with integrated I/O

360mA, 7W

490mA, 9W

Protection

Against reversed polarity

Against reversed polarity and

overcurrents on input circuit

Battery

3V 65mA/h rechargeable Lithium Manganese Dioxide (ML2032T6)

Life without power supply > 7500 h; expected life > 7 years;

low voltage signal

Display

Type

TFT Colors

TFT Colors

No. colours

262k

262k

Size

3.5”

5.7”

Display area

70.08x52.56 mm

117.2x88.4 mm

Resolution

320x240

320x240

Luminosity

400 cd/m

2

500 cd/m

2

Contrast

400:1

400:1

Backlighting

6 LEDs white

18 LEDs white

Visual angle O/V

75° / 55°-75°

75° / 60°-75°

Keyboard

No. keys

6

-

Operating

> 3M operations

-

Touch Screen

Type

4 wires resistance

Life

>1M operations

Controller

integrated

Processor

Type

EP9307 Cirrus Logic

Frequency

200MHz

Core

ARM9

Memory

System (DRAM)

64MB

User (SRAM)

256KB

Mass (FLASH)

64MB

Peripherals

ETH port

Ethernet 10/100 Mbps (RJ45 with LED)

RS-485 port

RS485 optoisolated from 9.6 to 115kBaud (RJ10)

USB port

USB 2.0 Host (500mA) (connector: 4-pin type A)

CAN [CANopen] port

Optoisolated 20k...1Mbit/s (D-Sub 9 PM)

BUS-G

Parallel bus for GILOGIK II modules

Operative Systems

Linux

Various

RTC hardware clock

Clock/calendar with buffer battery

Faceplate protection

IP65 (IEC 529)

Certifications

CE, UL

Dimensions

Faceplate (mm)

100x100x64

169x120x76

with GILOGIK II modules

100x100x171

169x120x187

Drilling (mm)

93x93

162x115

Max panel thickness (mm)

4

3

Weight (Kg)

0,4

0,8

with 4 GILOGIK II modules

1

1.4

Mechanics

Vibrations

10 ... 57Hz 0,075 mm peak

57 ... 150Hz, 1G

(IEC 68-2-6)

Shock

50g, 11 ms, 3 pulses for axis (IEC 68-2-27)

Protection

Faceplate IP65 (IEC 529)

Operating/Storage condition

Operating temperature

0 ... +50°C (IEC 68-2-14)

Storage temperature

-20° ... +70°C (IEC 68-2-14)

Operating and storage humidity

5 ... 95% RH non-condensing (IEC 68-2-3)

5 • SUMMARY OF CHARACTERISTICS

Table 10 - Summary of characteristics

Содержание Vedo EL35CT

Страница 1: ...gnetic compatibility 4 Instrument power supply 5 Inputs and outputs connection 5 Dimensions 6 Fixing 8 3 Technical Specifications 10 3 1 Display 10 3 2 CPU and Memory 10 3 3 Supported Operating Systems 10 3 4 Keyboard 10 3 5 User connections 11 3 5 1 Power supply port 12 3 5 2 RS 485 port 13 3 5 3 Ethernet port 13 3 5 4 USB port 14 3 5 5 CAN CANopen port 14 3 5 6 CAN DeviceNet port 14 3 5 7 Batter...

Страница 2: ... of Microsoft Corporation PREFACE This manual provides a detailed description of the main technical data of the various versions of Gefran s pro duct The following information is indispensable for the cor rect use of the product proper wiring correct jumper settings and the correct connection to external devices Keep in mind that most of the hardware options can be configured via software by means...

Страница 3: ...tandard PCs and or Gefran Industrial PCs and Gefran Programmable Instruments may access the various Technical Reference Documents in PDF format available on Gefran s website www gefran com In the event of presumed instrument malfunction before contacting Gefran Technical Service Assistance refer to the Troubleshooting Guide given in Section Maintenan ce and if necessary refer to the F A Q Section ...

Страница 4: ...T be installed in flammable or explosive environments it may be connected to equipment operating in such atmospheres only by means of appropriate and adequate types of interface conforming to the applicable safety standards Notes Concerning Electrical Safety and Electromagnetic Compatibility CE MARKING EMC Conformity electromagnetic compatibility in accordance with Directive 2004 108 CE The termin...

Страница 5: ... from the instrument input and output ones Inputs and outputs connection To connect the analogue inputs strain gauge linear TC RTD the following is necessary physically separate the input cables from those of the power supply the outputs and the power connections use woven and screened cables with the screen earthed in one point only To connect the control outputs alarm contactors solenoid valves ...

Страница 6: ...imensions All measurements are expressed in mm with tolerance of 0 5 GF_VEDO EL35CT dimensions Fig 1 Dimensions and cut out GF_VEDO EL35CT 3 max 12 9 66 9 90 5 93 93 92 4 61 12 5 100 8 3 100 Fig 2 Dimensions GF_VEDO EL35CT GILOGIK II modules optional ...

Страница 7: ...W_GF_VEDO EL35CT EL57CT_03 2010_ENG Fig 3 Dimensions and cut out GF_VEDO EL57CT 179 88 5 65 3 max 7 5 162 115 120 169 Fig 4 Dimensions GF_VEDO EL57CT GILOGIK II modules BUS G GF_VEDO 57CT GF_VEDO EL57CT dimensions ...

Страница 8: ... EL35CT and GF_VEDO EL57CT panels are designed for front panel installation After making the opening shown on the template drawing fasten the terminal with the blocks required and supplied with the product Fig 5 Panel mounting GF_VEDO EL35CT Fig 6 Panel mounting GF_VEDO EL57CT ...

Страница 9: ...wing points make the edges of the hole for the panel perfectly smooth and flat tighten each fastening screw The terminals also have an O Ring inserted at the rear of the display frames Cleaning the device Clean the device only with a soft cloth and non abrasive neutral soap Do not use solvents Fig 7 O Ring on GF_VEDO EL57CT terminals ...

Страница 10: ...oard integrated in the lexan front panel 3 1 Display 35CT 3 5 color LCD TFT Thick Film Transistor display 57CT 5 7 color LCD TFT Thick Film Transistor display 3 2 CPUs and Memories The terminals are equipped with EP9307 processors with ARM9 core Memories 64MB FLASH mass 64MB DRAM system 256KB cache 3 3 Supported Operating Systems The terminal is supplied with the operating system Linux ...

Страница 11: ...r future use 3 Power supply 4 USB 5 Ethernet 10 100 6 RS485 serial 7 BUS G 8 Rotary switch 9 Enabling battery Table 4 Terminals connector description 3 5 User connections The user connections specified on Table 4 are made at the bottom by means of Gefran standard and custom con nectors 3 6 5 4 8 9 1 7 2 Fig 10 GF_VEDO EL57CT connector ...

Страница 12: ... must be grounded Ground the devices in a manner conforming to applicable standards and regulations Max consumption GF_VEDO EL35CT Max consumption GF_VEDO EL57CT without integrated I O 240mA 5W without integrated I O 480mA 8 5W with integrated I O 360mA 7W with integrated I O 490mA 9W Fig 12 Power supply connector Pin Name Description 1 24 VDC Positive feed 2 0 V GND 3 GND Ground 1 2 3 To limit su...

Страница 13: ... Fig 14 Ethernet port connector Pin Name Description 1 TX_D Transmit data 2 TX_D Transmit data 3 RX_D Receive data 4 N C Not connected 5 N C Not connected 6 RX_D Receive data 7 N C Not connected 8 N C Not connected Table 6 Signal assignment of the Ethernet port 3 5 3 Ethernet port The terminal uses Ethernet port to dialog via IEEE 802 3 Ethernet protocol The Ethernet port can dialog at 10 100 Mbps...

Страница 14: ...as CAN bus The GF_VEDO EL35CT implements the CANOpen Layer 2 standard The CAN port is optically isolated and uses a 9 pin male D sub connector Signal assignment is shown in Table 8 Fig 17 CAN port connector Pin In Out Code Description 1 2 O CAN_L CAN Low 3 O CAN_GND CAN Ground 4 5 EARTH Ground 6 7 O CAN_H CAN High 8 9 Table 8 Signal assignment of the CAN port The communication cable to be used dep...

Страница 15: ...sing keys F1 and F6 on the GF_VEDO EL35CT when requested during termi nal startup or by setting the rotary switch to position F The menu is divided into the following sections Touch Screen Calibration F3 touch screen calibration program launched by pressing key F3 on the GF_VEDO EL35CT or by starting up the terminal with the rotary switch in position E Pointer Device Selection lets you select the ...

Страница 16: ...red separately It is a 4 slot back plane that supports a maximum of 4 GILOGIK II I O modules Run the following procedure after this module is installed Shut down the system by detaching it from the outside power source Insert the module in its connector as shown in the drawing Switch on the system 10 10 N 2 M4 holes Fig 20 L BUS4 modul Fig 21 L BUS4 mounting on GF_VEDO EL35CT ...

Страница 17: ...17 80951C_MHW_GF_VEDO EL35CT EL57CT_03 2010_ENG Fig 22 L BUS4 mounting on GF_VEDO EL57CT Fig 23 Ground connection on GF_VEDO EL35CT 24V 0V GND ...

Страница 18: ...18 80951C_MHW_GF_VEDO EL35CT EL57CT_03 2010_ENG 1 2 Fig 25 Assembling GILOGIK II modules 2 1 Fig 26 Disassembling GILOGIK II modules Fig 24 Ground connection on GF_VEDO EL57CT 24V 0V GND ...

Страница 19: ...d and removed as follows 1 expose the wire to be connected 2 insert the screwdriver in the slot 3 open the lock spring by pressing and levering with the screwdriver 4 insert the wire in the slot with the open spring Strip the wires for a maxi mum of 7mm do not attach a lug or solder the wires Do not use rigid wire 5 insert the wire and return the spring to its original position ...

Страница 20: ...GF_VEDO EL35CT EL57CT_03 2010_ENG 4 CONNECTION EXAMPLES Modbus RTU Modbus RTU Modbus TCP IP Example 1 Company Ethernet HMI GF_VEDO EL35CT Example 3 HMI GF_VEDO EL35CT HMI GF_VEDO ML104CK Example 2 HMI GF_VEDO EL57CT ...

Страница 21: ...e EP9307 Cirrus Logic Frequency 200MHz Core ARM9 Memory System DRAM 64MB User SRAM 256KB Mass FLASH 64MB Peripherals ETH port Ethernet 10 100 Mbps RJ45 with LED RS 485 port RS485 optoisolated from 9 6 to 115kBaud RJ10 USB port USB 2 0 Host 500mA connector 4 pin type A CAN CANopen port Optoisolated 20k 1Mbit s D Sub 9 PM BUS G Parallel bus for GILOGIK II modules Operative Systems Linux Various RTC ...

Страница 22: ...o be identified immediately and so it is essential to quote the order code each time the Gefran Customer Care Service is contacted for assistance with any problems Order code 1 Kindly contact GEFRAN for information on available codes MODEL 35CT GF_VEDO 3 5 color display touch screen OPERATING SYSTEM LX0 Linux EXPANSION 1 00 None S1 RS485 serial EXPANSION 2 00 None C1 CANopen EXPANSION 3 0 None U U...

Отзывы: